Functions and Characteristics: Advanced Energy Metering
Functions and Characteristics: Advanced Energy Metering
producers and cogeneration applications that need to accurately measure energy bi-
directionally in both generation and stand-by modes. These meters give utilities the
tools to manage complex energy supply contracts that include commitments to
power quality. Integrate them with our StruxureWare Power Monitoring (ION
Enterprise™) operations software or other energy management and SCADA
systems through multiple communication channels and protocols, including MV-90,
Modbus and DNP.
Applications
Tariff metering
Co-generation and IPP monitoring
Compliance monitoring
Power quality analysis
Demand and power factor control
PowerLogic ION8600 socket meter Load curtailment
Equipment monitoring and control
Energy pulsing and totalisation
Instrument transformer correction
Main characteristics
ANSI C12.20 Class 0.2, IEC 62053-22/23 Class 0,2S metering
For interconnection points on medium, high, and ultra-high voltage networks in
compliance with IEC 62053-22/23 Class 0.2S, IEE 519
Power quality compliance monitoring
Monitor compliance with international quality-of-supply standards (EN50160,
IEC61000-4-7, IEC61000-4-15, CBEMA/ITIC)
Digital fault recording
Simultaneous capture of voltage and current channels for sub-cycle disturbances
Complete communications
Multi-port, multi-protocol access serial ports, infrared data port, internal modem, Itron
software support, optional IRIG-B port; supports concurrent Ethernet, serial, and
modem communications
Multiple tariffs and time-of-use
Apply tariffs, seasonal rate schedules to measure energy and demand values for
time periods with specific billing requirements
Multiple setpoints for alarm and I/O functions
A total of 65 setpoints are configurable for 1-second or ½ - cycle operation.
Power quality summary
Consolidation of all the power quality characteristics into a single trendable index
Integrate with software
Easily integrate with StruxureWare Power Monitoring (ION Enterprise) operations
software or other energy management systems; MV-90, DNP, Modbus, UTS, Pacis
and third-party SCADA packages
Transformer/line loss compensation
Determine technical system losses in real time
Instrument transformer correction
Save money and improve accuracy by correcting for less accurate transformers
Alarm notification via email
High-priority alarms, data logs sent directly to the user’s PC. Instant notification of
power quality events by email
Part numbers
ION8600 meters
ION8600A M8600A
ION8600B M8600B
ION8600C M8600C
Options
See page 7.
General
Use on LV, MV and HV systems b b
Current accuracy 0.1 % 0.1 %
Voltage accuracy 0.1 % 0.1 %
Power accuracy 0.2 % 0.2 %
Samples/cycle 256 256
Instantaneous rms values
Current, voltage, frequency (Class 0,2S) b b
Active, reactive, apparent power Total and per phase b b
Power factor Total and per phase b b
Current measurement range 0.001 - 20A 0.001 - 20A
Energy values
Active, reactive, apparent energy b b
Settable accumulation modes b b
Demand values
Current Present and max. values b b
Active, reactive, apparent power Present and max. values b b
Predicted active, reactive, apparent power b b
Synchronisation of the measurement window b b
PowerLogic ION8600 socket meter. Demand modes: Block (sliding), thermal (exponential) b b
Power quality measurements
1 Blades b b
2 Optical port Harmonic distortion Current and voltage
3 Main display status bar Individual harmonics Via front panel 63 31
4 Watt LED Waveform / transient capture b(1) -
5 Navigation, ALT/Enter buttons Harmonics: magnitude, phase and interharmonics b b
6 VAR LED b
7 Form factor label Detection of voltage sags and swells b(1)
8 Demand reset switch IEC 61000-4-30 Class A/S
IEC 61000-4-15 (Flicker) b(1) -
High speed data recording (down to 10 ms) b -
EN50160 compliance reporting b (1) -
Programmable (logic and math functions) b b
Data recording
Onboard memory (in Mbytes) 10 (1), 4 (2) 2
Revenue logs b b
PE86002
Event logs b b
Historical logs b b
Harmonics logs b b
Sags/swells logs b b
Transient logs b b
Time stamping to 1ms b b
GPS synchronisation (IRIG-B standard) b b
Display and I/O
Front panel display b b
Wiring self-test b b
Pulse output (front panel LED) 2 2
Digital or analogue inputs(3) (max) 11 11
Digital or analogue outputs(3) (max, including pulse output) 16 16
Disturbance waveform capture and power quality report Communication
RS 485 / RS 232 port 1 1
RS 485 port 1 1
Infrared port 1 1
Ethernet port (Modbus/TCP/IP protocol) with gateway 1 1
HTML web page server Meterm@ail (email alarms & datalogs) b b
Internal modem with gateway (ModemGate) 1 1
IRIG-B port (unmodulated IRIG B00x time format) 1 1
Modbus TCP Master / Slave (Ethernet port) b/b -/b
Modbus RTU Master / Slave (Serial ports) b/b -/b
DNP 3.0 through serial, modem, and optical ports b b
(1) Feature set ’A’ only.
(2) Feature set ’B’ only.
(3) With optional I/O Expander.
(4) For 9S, 36S only. For 35S system up to 480V line-to-line.
Electrical characteristics
Type of measurement True rms up to the 63rd harmonic
PE86041
Communication
RS 232 / RS 485 port (COM1) User-selectable RS 232 or RS 485.
PE86004
Harmonic distortion Up to 63rd harmonic for all voltage and current inputs
Sag/swell detection Analyse severity/potential impact of dips and swells:
- magnitude and duration data suitable for plotting on
voltage tolerance curves
- per phase triggers for waveform recording or I/O
operations
Instantaneous High accuracy (1s) or high-speed (1/2 cycle)
measurements, including true rms per phase / total for:
- voltage and current
- active power (kW) and reactive power (kVAR)
- apparent power (kVA)
- power factor and frequency
- voltage and current unbalance
- phase reversal
Load profiling Channel assignments are user configurable:
- 800 channels via 50 data recorders (feature set A),
- 320 channels via 20 data recorders (feature set B),
- 32 channels via two data recorders (feature set C).
Configure for historical trend recording of energy,
demand, voltage, current, power quality, other measured
parameter. Recorders can trigger on time interval basis,
calendar schedule, alarm/event condition, manually.
Waveform captures Simultaneous capture of all voltage and current channels
- sub-cycle disturbance capture (16 to 256 samples/
cycle)
- maximum cycles is 214,000 (16 samples/cycle x 96
cycles, 10Mbytes memory)
Alarms Threshold alarms:
- adjustable pickup and dropout setpoints and time
PE86005
Part Numbers
Item Code Description
1 Model M8600 Schneider Electric meter.
2 Feature Set A 10MB memory, 50 data recorders (800 channels), waveform
PE86043
20 mA outputs)
Cable option 0 No cable - cables for the I/O box are no ordered as a separate
part number. Refer to part numbers: CBL-8X00IOE5FT, CBL-
8X00IOE15FT and CBL-8XX0-BOP-IOBOX under Connector
cables, below.
A-base adapters
A-BASE-ADAPTER-9 Form 9S to Form 9A adapter
A-BASE-ADAPTER-35 Form 35S to Form 35A adapter
Optical communication interface
OPTICAL-PROBE Optical communication interface
Connector cables
CBL-8X00BRKOUT Breakout Cable: 24-pin female Molex connector to one DB9
female connector for RS 232, and 2 sets of twisted pair wires for
two RS 485 port connections
CBL-8X00IOE5FT 5’ extension cable, mates with 24-pin male Molex connector from
the meter to the 24-pin female Molex connector on the I/O
Expander box (not for use with breakout panel E8, F8 & G8 form
factors)
CBL-8X00IOE15FT 15’ extension cable, mates with 24-pin male Molex connector
from the meter to the 24-pin female Molex connector on the I/O
Expander box (not for use with breakout panel E8, F8 & G8 form
factors)
CBL-8XX0-BOP-IOBOX 6’ connector cable, 24-pin male to 14-pin male Molex connector
for connecting an ION8600 meter with breakout panel to an I/O
Expander Box