Out-of-Limit Detection High-Speed Data Recording Multiple display formats are available, including bar
Detect, record, and report the specifics of voltage High-speed “burst” recording (as fast as 1/2- graphs with min/max indicators
or current imbalances and loss, frequency/power cycle intervals) stores detailed characteristics of
factor variations, over and undervoltages, etc. disturbances or outages. Trigger recording by a
user-defined setpoint, or from external
Performance Indicators
equipment. Gated recording logs data only during
The units can be configured to meter a wide range
the critical event so that memory is conserved.
of utility performance indicators, including:
w Total outage time (in seconds) Coincident Min/Max Recording
w Out-of-tolerance duration for total harmonic Log the values of key parameters or equipment
distortion, voltage, frequency, power factor conditions coincident with an extreme condition,
and hundreds of other definable indices complete with date/time stamping. For example,
record all feeder voltages and currents at the
Harmonic Distortion Metering moment a peak demand condition occurs.
Complete harmonic distortion metering,
recording and real-time reporting, up to the 63rd Time Synchronization and GPS
harmonic, (127th for ION 7600 via ION Enterprise A real-time clock allows internal events and data Unique vector diagram with magnitude and phase angle
software), for all voltage and current inputs. records to be date-stamped and time-stamped to can help reduce installation time
w Individual harmonics, (including magnitude, millisecond resolution. The clock can be
phase and inter-harmonics for the ION 7600) synchronized to any one of three sources:
w Total even harmonics and total odd harmonics w The meter's internal crystal (+/- 50ppm)
w Total harmonics (even + odd) w The line frequency of the electrical network
w K-factor, Crest factor being metered
w An external GPS receiver with an accuracy of
Symmetrical Components* +/- 1 millisecond
Zero, negative and positive sequences including The serial port used for GPS time synchronization
phase & magnitude for voltage & current inputs. is dedicated exclusively as a GPS input.
Identify harmful voltage & current unbalances in
equipment before they cause damage.
Logic, Math & Control
Sag/Swell Detection Perform on-board calculations on any measured
The ION 7500 and ION 7600 incorporate a value, calculate true quantities from pulse inputs
dedicated sag/swell capture capability that can (e.g. BTUs) and calculate transformer loss View THD and individual harmonics through the front
be used to analyze the severity and potential compensation values. You can also implement panel display screen
Interoperability
Concurrent communications ability via multiple
protocols allows you to use the advanced
features of either meter to extend an existing
Modbus, DNP or ION Enterprise network. Logs
and real-time values are also available through
Modbus.
Flash-Based Firmware
Perform upgrades via communications without
removing the unit from the site.
Inputs/Outputs Dimensions
Standard digital and optional analog I/O let you
monitor a wide range of conditions, such as flow Front view Front view, TRAN model
rates, RPM, fluid levels, oil pressures and
transformer temperatures. You can output energy
pulses to an RTU or perform equipment control
operations.
Digital Inputs/Outputs
w 8 digital inputs can monitor status or count
pulses from external “volts free” dry contact
w 4 solid state relay output ports and 3 on-
board relays can be controlled automatically
by internal setpoints or manually via a
communications port
Analog Inputs/Outputs
Either meter can be equipped with an optional
analog I/O card featuring:
w 8 digital inputs
w 4 analog inputs accepting 0–1mA or 0–20
mA, (scalable to 4-20mA)
w 4 analog outputs accepting -1–1mA or Side view Side view, TRAN model
0–20 mA, (scalable to 4-20mA)
w 4 analog inputs accepting 0-20 mA and 4
analog output accepting 0-20 mA
w 4 analog inputs accepting 0 to 1mA and 4
analog outputs accepting -1 to 1 mA
Contact Power Measurement for I/O
combinations supported
Mounting
The ION 7500 and ION 7600 can be panel-
mounted in a single DIN standard 186 mm X
186 mm cutout.
w Bezel size: 192 x 192 mm (DIN)
w A distance of 160 mm (6-½ inches)
clearance is required behind the panel (plus
allowance for connectors and cables)
w An adapter plate is available to facilitate the
conversion from our 3000 series meters to
the ION 7600 and ION 7500 . Please contact
us for more information.
TRAN models have no integrated display and
can be flush-mounted against any flat surface.
Features List ION 7500 ION 7600 Meet the World Leader
Power Quality Power Measurement is a leading provider of
Sag/Swell Monitoring n n enterprise energy management systems for
Symmetrical Components: zero, positive, negative n energy suppliers and consumers worldwide. Our
Transient detection, microseconds 65 ION® web-ready software and intelligent
Harmonics: individual, even, odd, total up to 63rd 63rd electronic devices comprise a complete, real-time
Harmonics: magnitude, phase and inter-harmonics n information and control network that supports
Sampling rate, maximum samples per cycle 128 256 billing for complex energy contracts and helps
Flicker, (harmonics to EN50160, IEC 6100-4-7/4-15) n improve power quality, reduce energy costs and
Configurable for IEEE 519 - 1992, IEEE159, SEMI n keep operations running enterprise-wide, 24
Uptime in number of nines n n hours a day. Our reputation for unparalleled
Logging and Recording value, quality and service is based on nearly two
Standard memory capacity 1MB 4MB decades of innovation and experience.
Maximum optional memory capacity 8MB 8MB
Min/max logging for any parameter n n
Historical logs, maximum # of channels 320 640
Waveform logs, maximum # of cycles 96 96
Timestamp resolution in seconds 0.001 0.001
Historical trend information via front panel display n n
GPS time synchronization n n
Communications and I/O
RS-232/485 ports 1 1
RS-485 ports 1 1
Ethernet ports 1 1
Infrared optical port 1 1
Internal Modem 1 1
DNP 3.0 through serial, modem and I/R ports n n
Modbus RTU slave on serial, modem and I/R ports n n
Modbus RTU Master on serial ports n n
Modbus TCP through Ethernet n n
EtherGate, data transfer between Ethernet & RS-485 n n
ModemGate, data transfer between internal modem & RS-485 n n
MeterM@il, logged data and alarms via e-mail n n
WebMeter, on board web server n n
Analog Inputs 4 4
Analog Outputs 4 4
Digital status inputs/counter 16 16
Digital relay outputs 7 7
Setpoints, Alarming, & Control
Setpoints, minimum response time ½ cycle ½ cycle
Setpoints, number of 24 24
Math, logic, trig, log, linearization formulas n n
Single & multi-condition alarms n n
Call-out on alarms n n
Revenue Metering & Standards
ANSI C12.16 accuracy compliant n n
Revision Date: October 31, 2001
ANSI C12.20 0.2 compliant n n © Power Measurement Ltd. All Rights Reserved.
IEC 60687 0.2S compliant n n Printed in Canada 70100-0132
IEC 60687 accuracy class 0.5S compliant n n ION, ION Enterprise, ION 7500, ION 7600, MeterM@il,
Measurement Canada Approved n n WebMeter, EtherGate, ModemGate are trademarks of Power
Measurement Ltd. All other trademarks are property of their
ANSI class 2, IEC 1/10 (1A nominal, 10A max) n n respective owners. Any reproduction or re-transmission in
ANSI class 20, IEC 5/20 (5A nominal, 20A max) n n whole or in part of this work is expressly prohibited without the
prior consent of Power Measurement Ltd. Please contact Power
MV-90 on serial, Ethernet ports n n Measurement head office for copyright permission. Information
Multi-year scheduling: hourly activity profiles n n contained herein is subject to change without notice.
Transformer/line loss compensation n n