a @) Fire pump stert/steap Setting @
REF. 2010 NFPA 20, A-14-2.5.
When Fire pumps Started by pressure drop,
should be arranged ao Follows.
Sockey Pump Minimum
Shae = Churn + Statrc supply
point Pressure pressure
——_——
=a
Pressure at 50 Pst
Zero Flow
Joc key Jockey
4K pump” = Pump — 10 Pst
Cut-in Cut-out (0.68 bar)
Primary Jockey pump
Mn Fire pump =~ Cut-in =O RSa
Cut in Ress bay)
alp Use 10 PsI increment Por each addition
pump
WP Second pump must start §$-10 Seconds
behind the pninary pump Starting f=
Prevent water hammer
Ref.» NEPA 20 . 7-5.2.5
website: https://ramygh|982.wixsite.com/meplife a.
i } ARS
facebook page: Mechanical is a life
facebook group: Mechanical is a life
mail. lifeamenbamail.comV where the mmimum run times are previded
the pump will continue to operate after
attamma these pressure
V/ The Fmal pressure should not exceed the
pressure rating ef the System.
@ Frample
————_ pump Lo0a GPM
{oo pst
Chur pressure. \15 PST
dockey Gut oFF = 54 50 = 165 Pst
dochey cur-in = 165- 10 = 155 Pst
Fire pump Cut-off z 115 450 = (65 PsI
Fire pump Cut-in = 195- 5 = 150 PstI
Fire pump max chum
= S460 2175 Psi