Professional Documents
Culture Documents
Replacing A Corroded Column With Packing Internals-Convertido1
Replacing A Corroded Column With Packing Internals-Convertido1
A
na columna de Cooled air
contacto,directo
después de enfriador New column Old column
(DCAC) equipada con bandejas Height (T/T), m 14 14
Chilled water Inner diameter, m 2.7 4.0
de tamiz en una unidad de Packing type MellapakPlus Sieve tray
separación de aire (ASU) fue 252.Y
severamente corroída y tuvo
Table 1
que ser reemplazada. En lugar
de optar por un reemplazo uno
a uno, se seleccionó una laden with water in preference to
Cooling water
solución de empaque moderna CO2. If CO2 is not removed from
basada en una caída de presión compressed air, it can preferen-
menor y una capacidad mucho tially freeze and cause plugging of
mayor. Durante la etapa de Hot air downstream equipment. A simple
diseño del proceso, se confirmó sketch of a DCAC column is
que la altura de empaque shown in Figure 1.
especificada era adecuada para Water An operator in the Asia Pacific
cumplir con el requisito de region approached Sulzer to
transferencia de calor. replace a severely corroded DCAC
Durante la fase de ingeniería column. The existing column was
detallada, se utilizaron simulaci
ones de dinámica de fluidos Figure 1 Sketch of a DCAC 4 m in diameter and 14 m T/T, and
computacionales (CFD) para column was equipped with 10 sieve trays.
evaluar la aceptabilidad de la
disposición de entrada
existente. Las pruebas se
realizaron poco después de que
se erigiera la nueva columna
La temperatura medida del
aire desde la parte superior de
la nueva columna DCAC
coincidía muy bien con el valor
del diseño
tact with chilled and cooling water in the DCAC.
Background The primary function of the DCAC column is to
In an ASU, compressed air is brought into con- cool the hot air and reduce moisture. 1 As the
www.digitalrefining.com/article/1001495
PTQ Q2 2018
water vapour content in compressed air is linked The dimensions of the new column were specified
directly to temperature, the compressed air as in Table 1.
must be cooled to 8°C~15°C. Otherwise, the Besides, a detailed design of the air inlet was
downstream molecular sieve adsorbers may be provided in the specification sheet: an open pipe
type with a disk beneath the downward opening
to direct the incoming vapour upwards.
The proposed operating conditions and
process flows for the new column were
unchanged. Based on the stream data and
packing type, the capacity and the pressure drop
were evaluated, with the results listed in Table
2. It can be seen from the packing hydraulics
that the new column was not highly loaded.
The key function of the DCAC column is to
2 PTQ Q2 www.digitalrefining.com/article/1001495
Packing Operating conditions of the
hydraulics tray column (the critical
case)
Upper Lower section Column top pressure, bar_a 7.03
section Top Bott Top Hot air temperature,°C 95
Capacity, % 51.0 om Chilled water temperature, °C 14
Cooling water temperature, °C 28
P, mbar/m 1.2 51.9 Bottom
1.2 65.3 71.5
Table 2 Table 3
Inlet piping
For this ASU plant, one of the
two feeds was supplied by a
compressor; the other feed
came from a nearby plant. The
feeds were combined in front of
the DCAC column, and the
distance between the joint of
the two inlet pipes and the
DCAC col- umn was about four
times that of the diameter of the
air inlet to the column.
Common practice in industry is
that, in order to avoid
Figure 4 Vapour flow trajectories in the DCAC column and its external inlet
maldistribution of vapour inside pipes
a column, any unavoid- able
upstream piping distur- bance
should be at least 10 times that Column pressure drop and approach temperature
of the inlet size in distance from
Old column New column New column
the column. In the exist- ing (guaranteed)
tray design, maldistribu- tion of (commissioning
P (mbar) 80 14.1 data)
vapour would likely be 12
T (°C) 1.5 (Best) 1.5 0.5
Table 4
mitigated by the high pressure drop of the tray. A CFD study was subsequently carried out to
However, given the much lower pressure drop understand vapour distribution inside the new
for the selected packing, maldistribution became column. Figure 3 shows the CFD model built
a potential issue in the stable operation of the for the DCAC column and its front inlet pipes.
column. While the operator planned to revamp The simulated vapour flow trajectories are illus-
the external inlet piping, Sulzer suggested using trated in Figure 4. It was evident from Figure 4
an advanced inlet device, Shell Schoepentoeter, that vapour distribution was perfectly fine if
instead of the specified simple pipe inlet device. Schoepentoeter was used as the air inlet device.
The operator agreed to leave the external inlet 3 Geankoplis C J, Transport Process and Separation
piping untouched. Process Principles, 4th Ed., Ch. 9 & 10, Prentice Hall, 2003.
4 Duss M, Meierhofer H, Nutter D, Effective interfacial area
Results and liquid hold-up of Nutter rings at high liquid loads,
Shortly after the new DCAC column was erected Chemical Engineering and Technology, Vol. 24, 2001.
on site, commissioning started. The operating
Yang Quan is a Sulzer Senior Technical Expert, specialising
data during commissioning were collected and
in mass transfer components, such as trays, packing, column
they are listed in Table 4.
internals and separators. He is also responsible for air
As expected, the pressure drop of the new separation knowledge management within Sulzer Chemtech.
packed column was 85% lower than that of the He holds a PhD in environmental engineering from the
old tray column, and more importantly it was National University of Singapore.
below the guaranteed value. The approach tem- Markus Duss is a Sulzer Senior Technical Consultant,
perature was consistently at 0.5°C, a degree responsible for the development of in-house tools for
below the guaranteed value and matching very designing heat and mass transfer applications for rings and
well the calculated figure of 0.5°C. The commis- structured packing. He is also the technical focal point for
sioning data demonstrate that Sulzer post combustion carbon capture projects. He graduated
from the Polytechnical School Winterthur, and has been
proprietary packing correlations are very
working with Sulzer Chemtech for more than 30 years.
accurate in heat transfer calculations.
Dong Jiao-Jiao is a Sulzer Senior Application Engineer from
the Separation Technology business unit of Sulzer Chemtech
Conclusions China. In her 10 years with Sulzer, her main responsibilities
A corroded DCAC column was replaced with a have included monitoring the changing needs of the air
new packed column. Due to the high capacity of separation market, and driving for the best design and
packing, the cross sectional area of the new col- optimisation of column internals in tune with times. She
umn was reduced by more than 50%. Revamp holds a master’s degree in chemical engineering from East
of the external inlet piping was eliminated after China University of Science and Technology.
using an advanced gas inlet device. The
operating temperature of the cooled air matches
prediction.
LINKS
References More articles from: Sulzer
1 Gorak A, Schoenmakers H, Distillation: Operation and
Applications, Ch. 6, Elsevier B.V., 2014. More articles from the following
2 Spiegel L, Bomio P, Hunkeler R, Direct heat and mass categories: Corrosion and Fouling
transfer in structured packings, Chemical Engineering & Control
Processing, Vol. 35, 1996. Heat Transfer Mass Transfer