You are on page 1of 5

Sustitución de una columna

corroída con elementos internos de


embalaje
Una columna corroída fue reemplazada por una nueva columna
equipada con embalaje de alta capacidad. El área de la sección
transversal es menos que la mitad del original.

Yang Quan, Markus Duss y Dong Jiao-Jiao Sulzer


Chemtech

A
na columna de Cooled air
contacto,directo
después de enfriador New column Old column
(DCAC) equipada con bandejas Height (T/T), m 14 14
Chilled water Inner diameter, m 2.7 4.0
de tamiz en una unidad de Packing type MellapakPlus Sieve tray
separación de aire (ASU) fue 252.Y
severamente corroída y tuvo
Table 1
que ser reemplazada. En lugar
de optar por un reemplazo uno
a uno, se seleccionó una laden with water in preference to
Cooling water
solución de empaque moderna CO2. If CO2 is not removed from
basada en una caída de presión compressed air, it can preferen-
menor y una capacidad mucho tially freeze and cause plugging of
mayor. Durante la etapa de Hot air downstream equipment. A simple
diseño del proceso, se confirmó sketch of a DCAC column is
que la altura de empaque shown in Figure 1.
especificada era adecuada para Water An operator in the Asia Pacific
cumplir con el requisito de region approached Sulzer to
transferencia de calor. replace a severely corroded DCAC
Durante la fase de ingeniería column. The existing column was
detallada, se utilizaron simulaci
ones de dinámica de fluidos Figure 1 Sketch of a DCAC 4 m in diameter and 14 m T/T, and
computacionales (CFD) para column was equipped with 10 sieve trays.
evaluar la aceptabilidad de la
disposición de entrada
existente. Las pruebas se
realizaron poco después de que
se erigiera la nueva columna
La temperatura medida del
aire desde la parte superior de
la nueva columna DCAC
coincidía muy bien con el valor
del diseño
tact with chilled and cooling water in the DCAC.
Background The primary function of the DCAC column is to
In an ASU, compressed air is brought into con- cool the hot air and reduce moisture. 1 As the
www.digitalrefining.com/article/1001495
PTQ Q2 2018
water vapour content in compressed air is linked The dimensions of the new column were specified
directly to temperature, the compressed air as in Table 1.
must be cooled to 8°C~15°C. Otherwise, the Besides, a detailed design of the air inlet was
downstream molecular sieve adsorbers may be provided in the specification sheet: an open pipe
type with a disk beneath the downward opening
to direct the incoming vapour upwards.
The proposed operating conditions and
process flows for the new column were
unchanged. Based on the stream data and
packing type, the capacity and the pressure drop
were evaluated, with the results listed in Table
2. It can be seen from the packing hydraulics
that the new column was not highly loaded.
The key function of the DCAC column is to

2 PTQ Q2 www.digitalrefining.com/article/1001495
Packing Operating conditions of the
hydraulics tray column (the critical
case)
Upper Lower section Column top pressure, bar_a 7.03
section Top Bott Top Hot air temperature,°C 95
Capacity, % 51.0 om Chilled water temperature, °C 14
Cooling water temperature, °C 28
P, mbar/m 1.2 51.9 Bottom
1.2 65.3 71.5
Table 2 Table 3

achieve the required temperature specification of


Process simulations provide useful insights,
the cooled air stream. A temperature outside this
such as the driving force for respective heat
range will negatively impact the vital downstream
transfers as well as the thermal properties of the
molecular sieve adsorbers’ ability to condition the
two phases. However, they can not predict how
incoming air stream. Table 3 summarises the top
fast heat will be transferred over a specific type
pressure of the DCAC column and the tempera-
of packing.
tures of various feeds. Based on past operation of
Specifically, for sensible heat transfer, the heat
the old column, the best ever achieved tempera-
transfer coefficient in the gas phase should be
ture of cooled air from the top of the DCAC was
known. This, apart from the thermal properties
15.5°C. Sulzer was asked to evaluate the specifi-
of the gas, is also related to gas turbulence inside
cations and guarantee an approach temperature
the packing. Subsequently, the required packing
(the temperature difference between the cooled
area2 can be calculated as follows:
air and the chilled water) of less than 1.5 °C.
𝑄𝑄!
To guarantee the temperature of the cooled air, 𝐴𝐴! = (1)
𝑈𝑈×(𝑇𝑇! − 𝑇𝑇! )
heat transfer calculations must be carried out to
evaluate the process risks. where QS (W) is sensible heat, U (W · m-2 · K-1) is
gas heat transfer coefficient, and TG and Ti (K)
Heat transfer calculations are temperature of bulk gas and temperature of
In the DCAC column, as the temperature of the the
compressed air is higher than that of the water, interface respectively.
sensible heat is transferred from the hot air to As for latent heat, the required packing area 3
the can be determined by:
water. Meanwhile, due to condensation of water
vapour, the latent heat of the hot air is also trans- 𝑄𝑄! (2)
𝐴𝐴
ferred. It should be highlighted that condensa- ! = 𝑘𝑘! ×(ℎ! − ℎ! )×𝑀𝑀!"# ×∆𝐻𝐻!"
tion is essentially a mass transfer matter. Figure
2 illustrates the concentration where QL (W) is latent heat, kG
and temperature profiles of water (kmol· m-2 · s-1) is mass transfer
Interface
in the aircolumn.
a DCAC and water phases
From for
this fig- Air filmLiquid H2O film coefficient, hG and hi (mol · mol
1
-

) are humidity in gas bulk and


H2O concentration
ure, it can be easily understood the interface respectively, Mair
HG humidity
that resistance to sensible heat (g· mol-1) is molecular weight
transfer exists dominantly in the of air and ∆HLV (J/kg) is latent
gas phase while for latent heat T heat of water.
H
transfer or mass transfer there is G
i
Similarly, the mass transfer
no resistance in the liquid phase Latent coefficient is also related to gas
T T
due to a nearly zero concentra- heat turbulence inside the packing.
in gas Sensible
i L
tion difference of water between Sensible heatin Depending on the appli-
water in gas heat
the water phase and a water cation and specific customer
lam- inar film. Therefore, for requirements, the packing sur-
sensible heat transfer and latent face area can be adapted to fit
heat transfer in the DCAC Figure 2 Concentration and the purposes best. It should
column, only the gas phase temperature profiles of water in be noted that the packing area
needs to be looked at closely. air and water phases described above refers to the
effective area available for heat transfer, which may or may not be the same as the geometri- cal
surface area of the packing. 4
Nevertheless, Sulzer’s proprie-
tary packing correlations pre-
dict packing effective area as
well as mass transfer and heat
transfer coefficients at specific
operating conditions.
Based on the specified pack-
ing type and height, and the
flow rates and conditions of
feeds, we calculated the cooled
air out- let temperature to be
14.5°C with an approach
temperature of 0.5°C. The
impact of possi- ble variations
in water flow rate (±10%) was
also investigated. Eventually, Figure 3 CFD model of the DCAC column and its external inlet pipes
Sulzer guaranteed that 1.5°C of
approach tempera- ture could
be achieved.

Inlet piping
For this ASU plant, one of the
two feeds was supplied by a
compressor; the other feed
came from a nearby plant. The
feeds were combined in front of
the DCAC column, and the
distance between the joint of
the two inlet pipes and the
DCAC col- umn was about four
times that of the diameter of the
air inlet to the column.
Common practice in industry is
that, in order to avoid
Figure 4 Vapour flow trajectories in the DCAC column and its external inlet
maldistribution of vapour inside pipes
a column, any unavoid- able
upstream piping distur- bance
should be at least 10 times that Column pressure drop and approach temperature
of the inlet size in distance from
Old column New column New column
the column. In the exist- ing (guaranteed)
tray design, maldistribu- tion of (commissioning
P (mbar) 80 14.1 data)
vapour would likely be 12
T (°C) 1.5 (Best) 1.5 0.5

Table 4
mitigated by the high pressure drop of the tray. A CFD study was subsequently carried out to
However, given the much lower pressure drop understand vapour distribution inside the new
for the selected packing, maldistribution became column. Figure 3 shows the CFD model built
a potential issue in the stable operation of the for the DCAC column and its front inlet pipes.
column. While the operator planned to revamp The simulated vapour flow trajectories are illus-
the external inlet piping, Sulzer suggested using trated in Figure 4. It was evident from Figure 4
an advanced inlet device, Shell Schoepentoeter, that vapour distribution was perfectly fine if
instead of the specified simple pipe inlet device. Schoepentoeter was used as the air inlet device.
The operator agreed to leave the external inlet 3 Geankoplis C J, Transport Process and Separation
piping untouched. Process Principles, 4th Ed., Ch. 9 & 10, Prentice Hall, 2003.
4 Duss M, Meierhofer H, Nutter D, Effective interfacial area
Results and liquid hold-up of Nutter rings at high liquid loads,
Shortly after the new DCAC column was erected Chemical Engineering and Technology, Vol. 24, 2001.
on site, commissioning started. The operating
Yang Quan is a Sulzer Senior Technical Expert, specialising
data during commissioning were collected and
in mass transfer components, such as trays, packing, column
they are listed in Table 4.
internals and separators. He is also responsible for air
As expected, the pressure drop of the new separation knowledge management within Sulzer Chemtech.
packed column was 85% lower than that of the He holds a PhD in environmental engineering from the
old tray column, and more importantly it was National University of Singapore.
below the guaranteed value. The approach tem- Markus Duss is a Sulzer Senior Technical Consultant,
perature was consistently at 0.5°C, a degree responsible for the development of in-house tools for
below the guaranteed value and matching very designing heat and mass transfer applications for rings and
well the calculated figure of 0.5°C. The commis- structured packing. He is also the technical focal point for
sioning data demonstrate that Sulzer post combustion carbon capture projects. He graduated
from the Polytechnical School Winterthur, and has been
proprietary packing correlations are very
working with Sulzer Chemtech for more than 30 years.
accurate in heat transfer calculations.
Dong Jiao-Jiao is a Sulzer Senior Application Engineer from
the Separation Technology business unit of Sulzer Chemtech
Conclusions China. In her 10 years with Sulzer, her main responsibilities
A corroded DCAC column was replaced with a have included monitoring the changing needs of the air
new packed column. Due to the high capacity of separation market, and driving for the best design and
packing, the cross sectional area of the new col- optimisation of column internals in tune with times. She
umn was reduced by more than 50%. Revamp holds a master’s degree in chemical engineering from East
of the external inlet piping was eliminated after China University of Science and Technology.
using an advanced gas inlet device. The
operating temperature of the cooled air matches
prediction.

LINKS
References More articles from: Sulzer
1 Gorak A, Schoenmakers H, Distillation: Operation and
Applications, Ch. 6, Elsevier B.V., 2014. More articles from the following
2 Spiegel L, Bomio P, Hunkeler R, Direct heat and mass categories: Corrosion and Fouling
transfer in structured packings, Chemical Engineering & Control
Processing, Vol. 35, 1996. Heat Transfer Mass Transfer

You might also like