Donald John Trump is the 45th and current president of the United States. Before entering politics, he was a businessman and television personality. Trump was born and raised in Queens, a borough of New York City.
Donald John Trump is the 45th and current president of the United States. Before entering politics, he was a businessman and television personality. Trump was born and raised in Queens, a borough of New York City.
Donald John Trump is the 45th and current president of the United States. Before entering politics, he was a businessman and television personality. Trump was born and raised in Queens, a borough of New York City.
917222018 Fire damper - Wikipedia
WIKIPEDIA
Fire damper
Fire dampers are passive fire protection products used in heating,
ventilation, and air conditioning (HVAC) ducts to prevent the spread of fire
inside the ductwork through fire-resistance rated walls and floors.
Fire/smoke dampers are similar to fire dampers in fire resistance rating,
and also prevent the spread of smoke inside the ducts. When a rise in
temperature occurs, the fire damper closes, usually activated by a thermal
clement which melts at temperatures higher than ambient but low enough to
indicate the presence of a fire, allowing springs to close the damper blades.
Fire dampers can also close following receipt of an electrical signal from a fire
alarm system utilising detectors remote from the damper, indicating the
sensing of heat or smoke in the building occupied spaces or in the HVAC duct
system.
Regulations and fire test regimes vary from one country to another, which can result in different designs and applications.
Contents
Fire dampers for ducts
Mechanical dampers
Intumescent dampers
PFP/AFP Hybrid
Air transfer dampers
Fire damper inspections and maintenance
See also
References
External links
Fire dampers for ducts
Interior of German mechanical fire
damper inside of a galvanised steel
duct.
Mechanical dampers
hitpsion wikipedia orgwikiFire_dampor
w612272018 Fie damper - Wikipedia.
German fire damper in North American fire Side view of North European fire damper
Underground parking of dampers, ready for American fire damper, with interior fire-resisting
@ commercial building. installation in Durasteel showing the closing board,
Unlike it North fireresistance rated mechanism that shuts
‘American pressurisation ductwork. the interior blades. An
contemporaries, this air gap of maximum 1/8"
damper —_ addresses. per linear foot of width
smoke migration through facilitate installation and
the damper’s annulus. allows smoke migration
through the assembly.
European dampers.
conceal this mechanism,
with exterior firestop
mortar acting as both a
heatsink and smoke
seal
Sa
Fire damper in oversized
hole in a 2-hour rated
conerete slab, The
annulus permits smoke
migration,
Mechanical dampers shut the cross sectional area of a duct in the event of a fire either by means of pivoting a fire-resistant
board (in Europe), or by means of steel shutters, similar to blinds on a window (in North America). In the European
designs, the turning mechanism is fully contained, permitting the dampers (subject to type approval) to be grouted in
place, which permits a heat sink effect to conduct heat from an accidental building fire, which impinges upon a duet and
damper, to be conducted into surrounding structures. This also addresses the topic of smoke migration through the
damper's annulus. In North American damper designs, the closing mechanism for the interior shutters resides on the
le of the damper, which is why NFPA 80 expressly prohibits the installation or presence of any materials in the
hitpsion wikipedia orgwikiFire_dampor an27272018 Fite damper - Wikipedia
damper’s annulus, which are not mentioned in the manufacturer's instructions, which are governed by their certification
listings. The closing mechanism must be allowed to operate, which necessitates that the annulus remain open, apart from
an angle iron lip that surrounds the damper through-penetration in fire-resistance rated wall and floor assemblies.
Maintenance efforts of mechanical dampers of both European and North American mechanical damper designs focus on
the function of the mechanical shutting of the opening (which must be performed during inspection), as well as removal of,
any foreign objects that may otherwise impair this function.
Intumescent dampers
Intumescent damper Round _intumescent
insert, Openings in the damper insert,
unit swell shut as a
result of intumescence
in case of fire or heat
exposure,
Intumescent dampers may be qualified to ISO 10294-5:2005 Fire dampers for air distribution systems—Part 5:
Intumescent fire dampers. They swell shut due to intumescence in the event of a fire, Unlike mechanical dampers, itis a
physical/chemical reaction that causes the closure to work, Provided the intumescent is within demonstrable ageing
and/or shelf life and providing the absence of massive combustible objects (sabotage), the damper is certified to maintain
its functionality subject to its certification listing or type approval. In other words, cleaning (when necessary) and an age
assessment comprise the inspection. The annulus of an intumescent damper
shut as per its certification listing, such
that the intumescent can press against a shut frame to close the opening, thus eliminating annular smoke migration,
PFP/AFP Hybrid
Both mechanical and intumescent dampers form part of passive fire protection (PFP) systems, such as fire-resistance
rated walls floors, or even ducts or cable tray fireproofing. As such, they are PFP systems. However, whether an opening is
‘mechanically closed or whether it is the physical/chemical action of an intumescent that does the work, the fact that they
are activated by heat and then move to fulfil a fire safety function, also technically qualifies them to form part of active fire
protection (AFP) systems
Air transfer dampers
Air transfer fire dampers (ATFD) are not protected by ductwork and must therefore be installed and manufactured to
standards and tests that take into account room fire exposures. Air transfer fire dampers are passive such as intumescent
types or mechanical types. They are designed for fire resistance, direct flame resistance in the open state or for smoke
resistance or for combinations. Some designs are for exterior use, some are for hygienic zone use and some are for Ex-zone
applications.
hitpsion wikipedia orgwikiFire_dampor ar612272018 Fie damper - Wikipedia.
Depending on regional regulation, they are either tested to the same exposure as wall and floor building elements or tested
slightly different such as for cable or pipe penetrations. In Europe, Sm or Sa classifications can be obtained for cold smoke
resistance or cold and hot smoke resistance respectively. In the US, listing can be issued for use in wildfire exposure.
Contrary to dampers in duets the closing time of ATFDs are crucial to avoid fire passing during the open state. For
applications where direct flame penetration is not allowed through openings that are normally in open state, ATFDs must
pass adequate standards. In the US, ASTM E2912 verify direct flame resistance in the open state and ASTM E19 for
closed state.
Air transfer fire dampers for walls or floors are usually designed for flush installation and comes in multiple sizes.
Dampers are listed for vertical or horizontal installation or both and for one- or two-way fire exposure. Performance may
be fire rated resistance as the compartment they serve, with or without smoke resistance. In Europe, the harmonized
ETAG 026 Part 4 apply to classification of ATFDs.
Fire element for air Air transfer damper
transfer dampers for mounted in wall
walls
Air transfer fire dampers for doors are designed and tested for use in the lower part of door leaves and cannot be
installed elsewhere or higher. In Europe, the fire door test EN 14600 and EN 1634-1 applies.
Air transfer fire dampers in facades are vents applied in wall, eave soffit, gable or foundation. In the US, these are
used to protect from exterior fire exposure from neighboring structure or via window-, arson- and wildfire (ASTM E2912
plus ASTM E119) or against wildfire only (ASTM E2886). In Europe, air transfer grilles for walls ean be applied externally
once a national assessment of suitability for the application in regards of embers, direct flame impingement,
environmental impacts ete. has been done.
Ventilating cavity fire barriers is a type of air transfer fire damper used in cavities or voids in constructions with
natural ventilation, typically inside air gaps behind cladding. These are often subject to sudden direct flame impingement.
In the US, ASTM E2912 cover testing, combined with E119 where required. A method to verify performance in the open
state, similar to E2912, is being assessed in Europe by CEN,
hitpsion wikipedia orgwikiFire_dampor an612272018 Fie damper - Wikipedia.
Cavity barrier with Cavity barrier invisible
instant fire stop behind cladding
Dampers for ducts applied as air transfer dampers: Allowances exist for use of duct dampers as air transfer fire
dampers. Since these typically will be too hot, and even allow penetration of flames to the unexposed side during fire, they
‘must be modified and classified for such application, To achieve this they are tested with a grid on either side to prevent
combustibles to be stored too close to hot parts or flaming. Some jurisdictions prescribe a general grid for use in front of
listed duet dampers, which are not listed for use without duetwork.
Fire damper inspections and maintenance
In the US, the Joint Commission,
State Fire Marshals and Other
Authorities Having Jurisdiction
(AHJ's), require Fire and Smoke
Dampers to be tested at specified
intervals. Similarly, European
authorities mandate maintenance
a
and repairs of fire dampers also, as
part of approvals or listings issued
following successful testing of fire
Fire damper deficiency: The
installed annular clearance around damper assemblies. Therefore, fire
the damper violates the certification dampers that are not demonstrably
listing maintained per regulations:
constitute fire code violations
because installed but unmaintained
fire dampers no longer comply with their certification listings.
In regions which enforce NFPA Standards (e.g, North America), fire dampers
and combination fire/smoke dampers require inspection and testing one year
after installation, and then every 4 years; except in hospitals, where the
frequency shall be every 6 years." Documentation indicating the location of
Site kno rpeneoneconst ie shina te
(iletineeed lend be cipeaniseaana hee
‘Pept rusting re noceay hi ste ap nd Sek
The damper's certification listing is.
Violated because the damper shares
the opening with other through-
penetrants and the drywall fire-
separation is not continuous.
the damper, date of inspection, name of inspector and deficiencies discovered is also required |2)
Repairs should begin without delay if a damper is found inoperable]
See also
= Blast damper
hitpsion wikipedia orgwikiFire_dampor
sn917222018 Fire damper - Wikipedia
= HVAC
= Passive fire protection
= Active fire protection
= Fire test
* Listing and approval use and compliance
= Sheet metal
References
1. NFPA 80 Standard for Fire Doors and Fire Windows, section
2. NFPA 80 Standard for Fire Doors and Fire Windows
3, NFPA 80 Standard for Fire Doors and Fire Windows, section 19.5.3.
External links
= UL treatise on fre dampers (http:wmw-ul.comiglobal/eng/pages/offerings/perspectives/regulator/electrical/additionalr
esources/dampers/)
= Abstract on ULSSS Standard on Fire Dampers (hitp:/lulstandardsinfonet.ul.com/scopes/scopes.asp?n=05SS.ntml)
= Abstract on ULS55s Standard for Smoke Dampers (hitp://www.ul.com/global/eng/pages/solutions/standards/accessst
andards/catalogofstandards/standard/?id=555S_4)
= Abstract on ULS5Sc Standard on Gelling Dampers (hitp:/ulstandardsinfonet.ul.com/scopes/scopes.asp7fr
mi)
= UL Marking and Application Guide for Dampers (http:/www.ul.com/globalidocuments/offerings/perspectives/regulator
sipublications/Dampers_MG pd)
= Abstract on UL33 Heat Responsive Links for Fire-Protection Service (hitp:/lulstandardsinfonet ul.com/scopes/scopes.
‘asp?in=0033.html)
+ ASTM £2912 Standard Test Method for Fire Test of Non-Mechanical Fire Dampers Used in Vented Construction (htt
pillwww.astm.org/Standards/E2912.htm)
= ASTM E2886 Access Portal: Standard Test Method for Evaluating the Ability of Exterior Vents to Resist the Entry of
Embers and Direct Flame Impingement (http:/www.astm.org/Standards/E2886.htm)
= NFPA 80 Access Portal: Standard for Fire Doors and Other Opening Protectives (http:/Avww.nfpa.orgicodes-and-stan
dards/document-information-pages?mode=code&code=80)
= NFPA 90A Access: Standard for the Installation of Air-Conditioning and Ventilating Systems (http:/iwww.nfpa.orgicode
s-and-standards/document information-pagesmode=code8&.code=90a)
= NEPA 105 Access: Standard for the Installation of Smoke Door Assemblies and Other Opening Protectives (http:/ww
w.nfpa org/codes-and-standards/document-information-pages 7modo=code&codo=105)
= Access Portal: SMACNA Fire, Smoke, and Radiation Damper Installation Guide for HVAC (http:/www smacna.orgibo
okstore/pdf_tocl02FSDG_F pai)
= 14600 Access Portal: Doorsets and openable windows with fre resisting and/or smoke control characteristics =
Requirements and classification (http: /www.en-standard eulesn-en-14600-doorsets-and-openable-windows-withefire-r
esisting-and-or-smoke-control-characteristics-requirements-and-classifcatior/EN)
= EN 1634-1 Access Portal: Fire resistance and smoke control tests for door and shutter assemblies, openable
windows and elements of building hardware - Part 1: Fire resistance test for door and shutter assemblies and
‘openable windows (hitp:/ww.en-standard.eu/csn-en-1634-1 -ire-resistance-and-smoke-control-tests-for-door-and-sh
Utter-assemblies-openable-windows-and-clements-cof-bullding-hardware-part-1-fire-tesistance-test-or-door-and-shutt
er-assemblies-and-openable-windows/?gclid=CjwKEAjwSqafBRCR YrL.4-fpuFkSJACVocQ HOF !pacGwD9g8EgAXE
kdU4IYEGUBWiQcZdNs4eVBrx0C-Lzw_wcB)
* Abstract DIN EN 15650:2010-09 Ventilation for buildings - Fire dampers; German version EN 15650:2010 (hitpiimwww
beuth.de/en/standard/