Professional Documents
Culture Documents
Exergoeconomic Analysis of Glycol Cold Thermal Energy Storage Systems
Exergoeconomic Analysis of Glycol Cold Thermal Energy Storage Systems
SUMMARY
An exergoeconomic analysis of glycol cold thermal energy storage (CTES) is reported. Glycol CTES is an application of
sensible heat storage where the temperature of a storage material changes in order to store cold energy, usually
generated from electricity when its cost is low. Exergoeconomic analysis combines thermodynamic analysis based on
the first and second laws with principles of economics, mostly cost accounting. Exergy analysis accounts for energy
quality and irreversibilities, and provides more meaningful and useful information than energy analysis about efficiency
and losses. A storage tank with a capacity of 350 000 kg is considered for this investigation and a water solution based
on ethylene glycol is used as the storage medium. Several thermodynamic system factors are analysed, such as change in
storage temperature, coefficient of performance (COP) of the chiller, heat losses from the storage tank, and the mass
flow rates. Simulation results indicate that the system exergy efficiency is much less ( 45%) than the energy efficiency.
The average exergy efficiency of the storage tank is determined to be 35% and the average energy efficiency 80%. The
system exergy efficiency is determined to be 30% and 40% at 45 and 258C ambient temperatures, respectively. The
chiller COP is observed to be strongly related to storage temperature, and to vary approximately between 2.4 and 5.8 at
a 358C ambient temperature. As ambient temperature decreases, COP increases. The exergoeconomic analysis indicates
that the ratio of exergy-based thermodynamic loss to capital cost of the glycol CTES ranges from 0.00233 to 0:00225
kW $1 at a 358C reference environment temperature, and from 0.00235 to 0:00227 kW $1 at a 258C reference
environment temperature. The reference environment temperature affects significantly exergy destruction and efficiency,
e.g. a 108C change in ambient temperature causes a 37.5% change in exergy efficiency. This result implies that cold
energy is more valuable at higher ambient temperatures. Heat loss from the storage tank exhibits a mild dependence on
ambient temperature, e.g. a 108C increase in ambient temperature causes a heat loss increase of 7.1%. Copyright
# 2007 John Wiley & Sons, Ltd.
KEY WORDS: energy; exergy; efficiency; cooling; glycol; thermal energy storage; performance
*Correspondence to: I. Dincer, Faculty of Engineering and Applied Science, University of Ontario Institute of Technology (UOIT),
2000 Simcoe Street North, Oshawa, ON, Canada L1H 7K4.
y
E-mail: Ibrahim.Dincer@uoit.ca
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
GLYCOL COLD THERMAL ENERGY STORAGE SYSTEMS 217
0
Propylene Glycol
-10
Ethylene Glycol
10 11 -30
-40
3 2
Condenser
-50
Expansion Compressor
-60
valve
0 20 40 60 80 100
Concentration of antifreeze [Vol. %]
Chiller
Figure 2. Freezing point of water solutions based on
4 1 propylene glycol and ethylene glycol at different
concentrations.
7
3.8
6 5 9 3.6 T=4.5 °C
T=-18 °C
3.4
pump
Cp [kJ/kg.K]
3.2
3
Heat
2.8
exchanger
2.6
Storage tank 8
2.4
Figure 1. Glycol CTES system.
2.2
20 30 40 50 60 70 80 90 100
Concentration of Antifreeze [Vol. %]
water flows through the evaporator from the Figure 3. Specific heat at constant pressure of water
storage tank forming a closed recirculating loop. solutions based on ethylene glycol at different concen-
In a chilled water system, the glycol solution is trations.
first cooled in the chiller, which is the evaporator
of a screw or centrifugal refrigeration system
located in a centralized plant. The glycol solution ethylene glycol concentration is used here as the
is then pumped to the cooling-load heat exchan- storage medium because it has a low freezing point
ger, where the temperature of the fluid is increased. that enables the temperature to decrease to –308C
Then, it returns to the storage tank through the without any freezing, as seen in Figure 2. This low
evaporator. temperature allows the storage of very cold energy,
A water–glycol mixture is employed as the reducing the size of storage needed. Furthermore,
storage medium and working fluid in glycol TES ethylene glycol is a clear, odourless, and slightly
systems. The most common antifreeze fluids are viscous liquid and has a low vapour pressure.
ethylene glycol and propylene glycol. Figure 2 Figure 3 illustrates the variation of specific heat of
shows the freezing point of water solutions based such antifreeze fluids as a function of concentra-
on propylene glycol and ethylene glycol at tion. The specific heat of the fluid is seen to
different concentrations. A 45% (by volume) decrease with increasing antifreeze concentration.
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
218 K. BAKAN, I. DINCER AND M. A. ROSEN
Glycol CTES systems are relatively simple. Few the storage medium temperature is decreased. The
accessories are needed and a conventional water maximum value of the cooling load is 1000 kW:
chiller is used. Glycol CTES systems cool water by An energy balance for the overall system in Figure
circulating ethylene or propylene glycol solution 1 can be written as
through storage tanks. Glycol storage systems Q’s ¼Q’ load þ Q
’ loss Q
’ chill ð1Þ
present the system designer with numerous bene-
fits: the ability to use a standard packaged chiller, where
the opportunity to reduce pump horsepower, and ’ s ¼ MCp DT
Q ð2Þ
the need for few accessories [12]. t
Glycol CTES systems are closed recirculated
water systems. Air or nitrogen has a negative effect ’ loss ¼ UAðTamb Tst Þ
Q ð3Þ
within the system. Air can exist in the system as
free air or gas bubbles, or as packets of air/gas, or ’ chill ¼ m
Q ’ r ðh4 h1 Þ ð4Þ
it can be dissolved in water. Potential problems
where Q’ s denotes the rate energy is stored in the
due to the presence of air or gas include unstable
’ loss and Q
tank, Q ’ chill denote the heat loss rates
system pressure, poor pump performance due to
gas bubbles, water logging in plain closed expan-
sion tanks, reduction of heat transfer surface, and
excessive noise. The latent heat of condensation is 1000
removed from the refrigerant in the condenser by
condenser cooling water. This condenser cooling 800
water is supplied from a cooling tower [13].
Qload [kW]
600
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
GLYCOL COLD THERMAL ENERGY STORAGE SYSTEMS 219
from the tank and chiller, respectively, Cp and M The exergy efficiency of the storage tank Ct is
denote the value of the specific heat for a 45% ’ t;out
X
ethylene glycol-based water solution and the mass Ct ¼ ð12Þ
’ t;in
X
of water in the storage tank, respectively, and UA
and t are the overall heat transfer coefficient of the The pump is an energy-consuming device in the
storage tank and time, respectively. glycol TES system. The electrical power used by
The refrigerant mass flow rate m ’ r can be the pump can be determined as follows:
expressed as follows: ’ p;in
’ p ¼ DPn m
W ð13Þ
V’ r Zp
m’r ¼ ð5Þ
vr where v; DP; Zp and m ’ p;in denote the specific
where V’ r is the volume flow rate of refrigerant volume at the inlet of the pump, the pressure
(which is taken to be 0:51 m3 s1 ), and vr is the difference between the inlet and the exit of the
specific volume of the refrigerant. In addition, pump, the energy efficiency of the pump, which is
’ chill ¼ aðTst T1 Þ taken to be 80%, and the mass flow rate of fluid
Q ð6Þ
entering the pump, respectively. Several exergy
’ con ¼ bðT3 Tct Þ
Q ð7Þ quantities for the pump are as follows:
’ p;in ¼ m
X ’ p;in ½ðhp;in h0 Þ T0 ðsp;in s0 Þ ð14Þ
’ con ¼ m
Q ’ r ðh2 h3 Þ ð8Þ
where Q’ con denotes the capacity of condenser, and ’ p;out ¼ m
X ’ p;out ½ðhp;out h0 Þ T0 ðsp;out s0 Þ ð15Þ
a and b are evaporator and condenser heat
exchanger effectiveness–capacitance rate products,
’ p;dest ¼ W
X ’ p;out X
’ p X ’ p;in ð16Þ
respectively. Also, T1 ; T3 ; and Tst denote tempera-
tures at the evaporator outlet, the condenser inlet,
where X ’ p;dest ; X’ p;in ; and X ’ p;out denote the
and the storage, respectively, and Tct is the cooling
tower working temperature. exergy destruction rate, the exergy input rate,
The energy recovery rate from the tank during and the exergy output rate for the pump,
discharging is respectively.
’d ¼m The compressor work rates and outlet enthalpy
Q ’ d Cp ðT9 T8 Þ ð9Þ
can be expressed as
where Q ’ d and m ’ d are discharge energy rate and the ’ c;i ¼ m
W ’ r ðh2;i h1 Þ ð17Þ
discharge mass flow rate, respectively, and numer-
ical subscripts refer to points in Figure 1. ’
The exergy inlet X ’ t;in and outlet X’ t;out rates ’ c ¼ W c;i
W ð18Þ
associated with the fluid entering and exiting the Zc
storage tank are
’c
W
’ t;in ¼ m Tin h2 ¼ h1 ð19Þ
X ’ c Cp ðTin T0 Þ T0 ln ð10Þ ’r
m
T0
where W ’ c are the compressor work rates
’ c;i and W
Tout for ideal and real processes, and h2;i and h2 are the
’ t;out
X ’ c Cp ðTout T0 Þ T0 ln
¼m
T0 enthalpies at the condenser inlet for ideal and real
processes, respectively. Also, Zc is the isentropic
ð11Þ efficiency of the compressor.
A heat exchanger is used to discharge cold
where m ’ c and the subscript t refer to discharge energy from the storage. This heat exchanger
mass flow rate and storage tank, respectively. The is positioned in the storage tank. An exergy
reference temperature T0 is taken as 208C: analysis of the discharge heat exchanger yields
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
220 K. BAKAN, I. DINCER AND M. A. ROSEN
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
GLYCOL COLD THERMAL ENERGY STORAGE SYSTEMS 221
1600
30 T = 45 °C
Qload T = 35 °C
1200 Qchill
20 T = 25 °C
10
Q [kW]
Ts [°C]
800
0
400 -10
-20
0
0 4 8 12 16 20 24 0 4 8 12 16 20 24 4 8
t [hour] t [hour]
Figure 5. Comparison of chiller capacity and cooling Figure 6. Variation of storage temperature Ts with
load for the storage system. time t:
maximum value is 1000 kW at 13:00. Discharging midnight, the temperature of the storage is
of cold energy from the storage occurs from 8:00 observed to decrease gradually with time until
to 18:00, respectively. The load increases steadily discharging begins at 8:00. Then, the temperature
to its maximum value of 1000 kW at 13:00 O’clock increases between 8:00 and 18 O’clock as cold
and then decreases to 0 at 18:00. energy is extracted from the storage to meet the
Figure 5 shows the cooling load and the load. The chiller unit is switched off from 18:00 to
capacity of the chiller unit, as a function of time 02:00 on the following day; during this period, due
of day. The solid line represents a typical cooling to a lower storage temperature, heat transfer
load for a commercial building, while the dashed occurs from the surrounding environment to the
line represents the cooling capacity of a chiller. As storage medium. Therefore, the storage tempera-
seen in this figure, during first two hours of ture increases to its maximum value at 02:00 and
operation the chiller capacity is much higher than the chiller unit is switched on at 02:00 and run
at other times; this is the case only for the start-up until 18:00. During the second and subsequent
period of the first day. For this reason, the storage operating days, the storage medium temperature
medium temperature is the same as the ambient remains below the ambient temperature, and
temperature, and the evaporator therefore dissi- varies between 13 and 218C; depending on the
pates more cold energy to the storage medium, environment temperature.
yielding a higher chiller capacity during this start- Figure 7 illustrates the variation of both energy-
up period. The storage temperature does not reach and exergy-based COP values of the chiller for the
the ambient temperature for any subsequent 32-h operating period. The energy-based COP
cycles. It is also evident that the storage system varies between 2 and 6, while the exergy-based
enables the use of lower capacity: instead of COP varies between 0.6 and 0.7. The figure
employing a 1000 kW chiller to meet the load, a indicates that the exergy-based COP for the chiller
600 kW chiller unit is sufficient. is much less than the energy-based COP, and that
Figure 6 shows the variation in the temperature energy-based COP values decrease during char-
of the storage medium under the specified load, for ging from midnight to 08:00 while storage
three different ambient temperatures, for a period temperature decreases. The increase in storage
of 32 h: The initial temperature of the storage temperature during the discharging period from
medium is taken to be equal to ambient tempera- 08:00 to 21:00 makes the evaporator dissipate cold
ture in order to show a start-up period during the energy more easily and this yields a higher energy
first 24 h of operation. Once charging begins at COP. The COPs depend mainly on the storage
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
222 K. BAKAN, I. DINCER AND M. A. ROSEN
9 0.8 80
8
70
7 0.6
60
Qloss [kW]
6
50
COPex
COPen
5 0.4
40
4
30
3 0.2
Tamb=45 °C Tamb =45 °C
=45[˚C
COPex Tamb=35 °C 20 Tamb =35 °C
=35[˚C
2
COPeenn Tamb=25 °C Tamb =25 °C
=25[˚C
1 0 10
0 4 8 12 16 20 24 4 8 0 4 8 12 16 20 24 4 8
t [hour]
t [hour]
Figure 7. Variation of energy- and exergy-based chiller Figure 8. Variation of energy loss rate from storage
COP with time for several ambient temperatures. tank with time.
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
GLYCOL COLD THERMAL ENERGY STORAGE SYSTEMS 223
Ξ chill,dest [kW]
60 50
Efficiency [%]
50
40
45
30
20
40
10
0
35
-10 Charging Discharging Storing Charging
30
0 4 8 12 16 20 24 4 8 4 8 12 16 20 24 4 8
t [hour] t [hour]
Figure 10. Variation of energy and exergy efficiencies Figure 11. Variation of exergy destruction rate for the
for the system with time. chiller unit with time.
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
224 K. BAKAN, I. DINCER AND M. A. ROSEN
0.00235
exergy efficiency around 40%, for a 258C
ambient air temperature. Also, the chiller COP
is observed to be strongly related to storage
0.0023 temperature and to vary approximately between
Rsys [kW/$]
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er
GLYCOL COLD THERMAL ENERGY STORAGE SYSTEMS 225
Greek letters
ACKNOWLEDGEMENTS
a ¼ evaporator heat exchanger
effectiveness–capacitance rate The authors acknowledge the support provided by the
products ðW K1 Þ Natural Sciences and Engineering Research Council of
b ¼ condenser heat exchanger ef- Canada.
fectiveness–capacitance rate
REFERENCES
products
ðW K1 Þ 1. Rosen MA, Dincer I. Exergoeconomic analysis of power
plants operating on various fuels. Applied Thermal
Z ¼ energy efficiency Engineering 2002; 23(6):643–658.
’
X ¼ exergy rate (kW) 2. CEC. Source energy and environmental impacts of thermal
t ¼ exergetic temperature factor energy storage. Report, California Energy Commission, 1996.
3. Bejan A. Fundamentals of exergy analysis, entropy
C ¼ exergy efficiency generation, minimization and the generation of flow
architecture. International Journal of Energy Research
2002; 26(6):545–565.
Subscripts
4. Rosen MA, Pedinelli N, Dincer I. Energy and exergy
analysis of cold thermal energy storage systems. Interna-
amb ¼ ambient tional Journal of Energy Research 1999; 23(12):1029–1038.
c ¼ compressor 5. Rosen MA, Dincer I. Effect of varying dead-state properties
on energy and exergy analyses of thermal systems. Interna-
ch ¼ charging tional Journal of Thermal Sciences 2004; 43(2):121–133.
chill ¼ chiller 6. Silveira JL, Tuna CE. Thermoeconomic analysis method
con ¼ condenser for optimization of combined heat and power systems:
part I. Progress in Energy and Combustion Science 2003;
ct ¼ cooling tower 29(6):479–485.
d ¼ discharge 7. Kwak HY, Kim DJ, Jeon JS. Exergetic and thermoeco-
dest ¼ destruction nomic analyses of power plants. Energy 2003; 28(4):
343–360.
e ¼ evaporator 8. Guoxi Z, Ben H, Qinglin C. Exergoeconomic methodology
en ¼ energy for analysis and optimization of process systems. Compu-
ex ¼ exergy ters and Chemical Engineering 2000; 24(2–7):613–618.
9. Rosen MA, Dincer I. Exergy methods for assessing and
hx ¼ heat exchanger comparing thermal energy storage systems. International
i ¼ ideal Journal of Energy Research 2003; 27(4):415–430.
in ¼ inlet 10. Si-Moon K, Si-Doek O, Yong-Ho K, Ho-Young K.
Exergoeconomic analysis of thermal systems. Energy
load ¼ cooling load 1998; 23(5):393–406.
out ¼ outlet 11. Chih W, Lingen C, Fengrui S. Effect ZOF heat transfer law
p ¼ pump on finite-time exergoeconomic performance of CARNOT
heat pump. Energy Conversion and Management 1998;
r ¼ refrigerant 39(7):579–588.
st ¼ storage 12. Dincer I, Rosen MA. Thermal Energy Storage Systems and
s ¼ system Applications. Wiley: New York, 2001.
13. Rosen MA, Dincer I. Exergy-cost-energy-mass analysis of
t ¼ tank thermal systems and processes. Energy Conversion and
w ¼ water Management 2003; 44(10):1633–1651.
Copyright # 2007 John Wiley & Sons, Ltd. Int. J. Energy Res. 2008; 32:215–225
DOI: 10.1002/er