You are on page 1of 1

5220FL Non-Paired - Fire Alarm Cable

Total # Cond.
2
AWG Stranding Type Insulation Insulation Shield
Thickness (in.)
16 Solid BC - Bare PVC - Polyvinyl .01000 Aluminum Foil-
Copper Chloride Polyester Tape
Jacket Jacket Thickness Nom. OD (in.) Nom. Cond. DCR Nom. Cap. (pF/ft)
(in.) (Ohms/M')
PVC - Polyvinyl .0150 .1780 3.900 77.000
Chloride

For technical data, click the button below For available colors, click the button below

or call 1-800-BELDEN-1 or call 1-800-BELDEN-1

Description
Multi-Conductor, 2 conductors, twisted, 16 AWG, Solid BC - Bare Copper conductors, PVC - Polyvinyl Chloride
insulation, overall Aluminum Foil-Polyester Tape (Beldfoil) shield with a 20 AWG stranded tinned copper drain
wire, 100% shield coverage, PVC - Polyvinyl Chloride jacket, Sequential Footage Marked. Applicable
Specifications: UL Type FPLR. Flame Resistance: Ul 1666 Vertical Shaft. New Generation. Overall Shielded
Riser. Approved by California State Fire Marshall. Applications: Fire Protective, Alarm, Signal,
Monitor/Detection. NEC Article 760. NEW GENERATION is a Belden registered trademark. BELDFOIL is a
Belden registered trademark.