UPGRADATION OF KHULNA 150 MW PPP TO 225 MW CCPP PROJECT. 3114007/31/08(069) Date: | 2014.04.11 Dat 2014.03.23 351-F248C- S01-04 Rev: [0 Layout of water intake pump house Reference PMC’s Comments 1 | GENERAL 1) The flow capacity for the water intake pump shall be 110% of raw water requirement as per contract document vol2/3,book 3/4Section ~3 clause 3,3.15.Pl revise it taking into account the comments given for Raw Water Balance in Drawing 351-F248C -S01-01 2) 2«100% washable stainer shall be added before the pump. 3)_The pump head is indicated as 20m. EPC has to furnish design calculations forthe pump head EPC comments Agree, ‘The pump take water from river directly , A take pipe. Itcan ensure the safe ‘operation of the pump. Other small Suspended solids can be removed in pre-treatment equipment, ‘The pump head will be 22m(H,0), Please see to “Design calculations for the pump head” Conelusion: 1) Agreed. 2) Agreed, without the strainer before pump, EPC is to consider operational safety of the pumps during river water intake. 3)_Received and to rfeview. dadde: cept Page 1 of