Abstract-- The inter-turn short circuits fault of field simulation method can obtain accurately the distribution
windings is one common fault in generators. It will cause and the value of fault current in the loops [4] by
serious damages if such faults are not handled properly in simulating different operations of different structure
time。For this reason, according to the multi-loop method machines with less cost [5][6][7][8].
of AC machines this paper proposes multi-loop This paper researches the model and simulation of
mathematical model of turbine generators with inter-turn
generator according to the multi-loop method of AC
short circuits fault of field windings. The inductance
parameters are calculated by air-gap permeance method machines [6]. Combining with the actual structure and
and the calculated wave-form of inductance parameters the fault feature of a 300MW turbine generator, this paper
shows reasonable. Combining with the actual structure of a calculates the inductance parameters by air-gap
300MW turbine generator, the normal rated load operation permeance method and proposes multi-loop mathematical
and the short circuits fault operation of generator have been model of turbine generators with inter-turn short circuits
simulated based on the model. The normal stator winding fault of field windings. The calculated results wave-form
currents and the fault currents difference in stator winding of inductance parameters shows reasonable. Based on the
parallel branches of same phase were obtained. The model, the normal rated load operation and the short
currents of normal and fault field winding are calculated.
circuits fault operation of generator have been simulated.
The model considers the different structure and the
The normal stator winding currents and the fault currents
harmonics in air gap magnetic field, which provides the
basis for further fault analysis for turbine generator with
difference in stator winding parallel branches of same
inter-turn short circuits of field winding. phase were obtained. The currents of normal and fault
field winding are calculated. The model considers the
Index Terms—Inter-turn short circuit fault of field different structure and the harmonics in air gap magnetic
windings, Inductance parameters, Multi-loop method, field, which provides the basis for further fault analysis
Turbine generator for turbine generator with inter-turn short circuits of field
winding.
concentric field coil. q is the slot number of each pole in The mutual inductance between field loop and
damper loops
a phase, β is the short pitch ratio, β fdi is the short pitch
4 w fd w1d τ l nfd _ rotor 1 k β fdi π k β1d π
ratio of i-th concentric field coil, a fd is the number of M 1dfd = λ0 ∑ ∑ sin sin
2 2
a fd π i =1 k =1,3,5..... k 2 2
parallel field winding, γ is electric angle between d axis
(12)
k βπ
and the stator 1-th coil axis , sin( ) is the short pitch Where nfd _ rotor is the turn number of each pole
2
concentric field coils.
coefficient of stator coil, θ is the electrical angle per slot
in the stator.
The mutual inductances between stator branch and D. The verification of Multi-loop parameters [ M ]
equivalent direct-axis damper winding loop. In this paper, the calculation values of traditional
formula are the reference values. The amplitude results
of time variant parameters show as TABLEⅠ,the 0.08
mutual inductance(H)
0.04
TABLE I 0.02
-0.04
(abbreviation) loop method Traditional -0.06
method -0.08
0 0.05 0.1 0.15 0.2
ma1 fd 0.0611 0.0676 t(s)
(b) the mutual inductance between a2 stator branch and field loop
Fig.3. the mutual inductances between stator branch and field loop
ma1d 0.0044 0.0048 -3
x 10
8
6
ma1q 0.0025 0.0028
mutual inductance(H)
4
2
TABLEⅡ 0
The parameter The values of The values of -2
name Multi-loop Traditional -4
-8
L11d 0.0055 0.0051 0 0.05 0.1
t(s)
0.15 0.2
mutual inductance(H)
4
-4
4 4 -2
U N = 2.0 × 10 , I N = 1.7664 × 10 , p = 1 , f N = 50 ,
-4
The wave-form of time variant inductance parameters (a) the mutual inductances between stator branch a1 equivalent
quadrature-axis damper winding
as Fig.3, Fig.4 and Fig.5 -3
x 10
The amplitude of mutual inductances between stator
6
0.08 -6
0 0.05 0.1 0.15 0.2
0.06 t(s)
(b) the mutual inductances between stator branch a2 equivalent
mutual inductance(H)
0.04
0.02
quadrature-axis damper winding
0
Fig.5. the mutual inductances between stator branch equivalent
-0.02
quadrature-axis damper winding
-0.04 The stator currents have been obtained in normal
-0.06 rated load operating conditions. The phase a current
-0.08
0 0.05 0.1
t(s)
0.15 0.2 shows model reasonable as Fig.6
(a)The mutual inductance between a1 stator branch and field
winding
are obtained. The currents of normal and fault field
5
x 10
1.5
1
winding are calculated. The paper provides the basis for
further fault analysis of turbine generator with inter-turn
0.5
0
current(A)
-1.5
REFERENCES
-2
-2.5
0 0.05 0.1 0.15 0.2
[1] Li Wei-qing, Analysis And Prevention Of Fault Of
t(s)
Turbine-Generator. Beijing: China Electric Power Press,
Fig.6. the phase a current
2002, pp. 80-81.
The simulation current of stator and rotor after [2] Wan Shu ting, Li He ming, Li Yong gang, etal. Analysis
generator short circuits fault (10%) happens under the of generator excitation current harmonics on rotor winding
rated load operating conditions show Fig.7 Fig.8. Fig.9. inter turn
the unbalanced currents emerge because of unbalance short circuit fault. [J] Automation of Electric Power
magnetic field caused by the fault current in Fig.7 Fig.8 Systems 2003,27 (22) :64 267
Fig.9. the unbalance magnetic field cause some [3] Li Yong-gang, Li He-ming, Zhao hua, Wan shu-ting
harmonics currents. Fault identification method of rotor inter turn short circuit
1.5
x 10
5
using stator winding detection [J] Proc.CSEE ,2004,24
1
r:i1
b:i2 (2) :107 2112
[4] Sun yu-guang, simulation research on inter-turn short
circuits of field windings in synchronous machines.
0.5
current(A)
0
Advanced Technology of Electrical Engineering
-0.5
andenergy.April 2008,vol.27,No.2,pp,5-10
-1 [5] Wang Xiangheng, Chen Songlin,Wang Weijian, Sun
-1.5
0 0.05 0.1 0.15 0.2
Yuguang . A Study of Armature Winding Internal Faults
t(s)
and Protection Schemes for Turbogenerators. Industry
Fig.7.the currents i1 , i2 of stator branchs a1,a2 Applications Conference, 2000. Conference Record of the
2000 IEEE ,vol.1:402 – 408
5
x 10
3
0
Beijing, 1993. (Chinese Book )
[7] Peter P. Reichmeider, Charles A. Gross, Dale Querrey,
-1
Damir Novosel, et al. Internal Faults in Synchronous
-2
Machines Part I: The Machine Model. IEEE Transactions
-3
0 0.05 0.1 0.15 0.2 on Energy Conversion, 2000, 15(4): 376-379.
t(s)
Fig.8.the current difference of stator branch a1,a2 [8] Peter P. Reichmeider, Charles A. Gross, Dale Querrey,
4
x 10
4
Damir Novosel, et al. Internal Faults in Synchronous
Machines Part II: Model Performance. IEEE Transactions
r:ifd
3 b:ifk
2
on Energy Conversion, 2000, 15(4): 380-383.
[9] Wang Xiangheng, Sun yu-guang, Gui Lin, Wang Weijian.
current(A)
0
Reasonable Simplification of Multi-loop Model of the
-1
Hydro Generators. [J] Proc.CSEE,2007,27(3):63-67.
-2
-3
0 0.05 0.1 0.15 0.2
t(s)
IV. CONCLUSIONS
The self-inductance and inductance parameters of
stator and rotor loops are calculated by air-gap permeance
method in this paper, in which the harmonics in air gap
magnetic field were considered. The time variant
waveforms of the inductance are obtained by numerical
simulation which consists with the actual structure of
generator winding. The paper proposes multi-loop
mathematical model of turbine generators with inter-turn
short circuits fault of field windings. Based on the model,
the stator phase currents which verify the correctness of
the model have been obtained in normal rated load
operating conditions. After generator short circuits fault
happens under the rated load operating conditions, the
currents in stator winding parallel branches of same phase