You are on page 1of 1
@ LARSEN & TOUBRO LIMITED ELECTRICAL & ELECTRONICS DIVISION (EBG) - ELECTRONIC PRODUCTS: ‘Mysore Campus, KIADB Industrial Area, Hebbal-Hootagalli, Mysore - 570 018. Tel : (91)-0821-2402561 ELECTRONIC TRIVECTOR METER ROUTINE TEST REPORT REFERENCE STANDARD DETAILS: Meter No - 13190332 MODEL —: RADIANRD-31 Class: 0.25 For Active Suto ease £455 ForReueve Cal Due Date: 18/07/2013 Model : ER300P Series Configuration : [- 3Wire W 4Wite Voltage: 3635 1 Curent: 1A High Voltage Tests (4KV& 2KV) Insulation resistance (> 50M) Power Supply High (+ 20 %) OK Power Supply Low (- 40% ) —> OK OK Starting Current (At 0.1% of Nominal current) > OK. OK No Load Condition(At 115% of Nominal voltage})——> OK ALLERRORS ARE IN % & MAX LIMITS ARE AS PER IS 14697 & IEC 62053-22 STANDARD. 4: BALANCED LOAD: Current UPF O5LAG | _O.8LEAD PF O.BLEAD 200 0.082 0.012 0.102 0.080 0.081 00 0012 0.036 0.003 “0.011 “0.004 50 0.022 “0.082 0.006 0.013 0.006 10 0.029 0.036 0.036 o.013 0.043, 5 0.087 0146 0077 0.048 0.086 2 0.160 O34 0150 0.075 0.132 0.246 NA NA 0.088 NA ITH POLYPHASE BALANCED VOLTAGE TEST __[R-PHASE.Y-B-0|¥-PHASE,R-B-0|8-PHASE,.A-Y-0 UPF-200% 0.076 0.063 0.079 UPF-50% 0.016 0016 0.015 UPF-10% 0.070 0.066 0.055 UPF-5% 0.166 0136 0.136 D51AG-200% 0.006 0.001 0.008 OSLAG-50% “0.076 076 0.074 O.SLAG-10% 0110) 0.090 Reactive TEST |REPHASE, Y-PHASE.R=B-0 O5LAG-200% 0.056 0.038 O.5LAG-50% -0.046 0047 O.5LAG-20 “0.102 “0.127 ZPF-200% 0.080 071 ZPF-50% 0.026 0.026 ZPF-5% 0.046 0.048 Form Netp120312 REVO! TESTED BY. AUTHORISED BY. SIDDARANGA NAY Ar TRIVECTORMETER PROGUCTION \ xi WARSEN & TOU2RO LIMITE! werd € MYSORE F ; YAN