HVA Report IS1-C.

B-Y1 Page 1 of 4

Company Location
Customer PO# Owner
Job# Owner
Representative
Date 1/17/2020 10:41:00 AM Temperature
Tested by Humidity
Substation Position
Circuit ID IS1-C.B-Y1
Device Under Test is Cable
Rated Voltage 33.0 kV Operating Voltage
Manufacturer Model
Insulation Type XLPE Insulation Thickness
Shield Type Grounding
Conductor Size Conductor Material
# of Conductors Length
Installed in Age
Cable Test End Cable Far End
Termination Type Termination Type
# of Splices Splice Locations
Jacket (Y/N) - Jacket Integrity

Equipment
Equipment Used GH5238 Serial No. GH5238.17E018

Test Setup
Type of HV Test Acceptance Test Voltage 19.0 / 44.0 kVrms
Waveform Sine Planned Test 1 / 60 min
Duration
Frequency 0.1 Hz Current Limit Trip out on Arc

Measurements / Results
Breakdown No Breakdown Voltage
Time to Failure
Acceptance Test finished successfully
Step Voltage Current Load Cap. Load Res. Frequency
1 19.0 kVrms 5.25 mArms 440 nF >20 GOhm 0.1 Hz
2 44.0 kVrms 12.2 mArms 440 nF >20 GOhm 0.1 Hz
3
4

Test Result X Acceptable Unacceptable

Comments