Specialized firmware for
InteliGenNT/C and
InteliSysNT/C
SW version 1.8.0
1 General information 2
2 Changes in the version 1.8.0 3
3 Changes in the version 1.7.0 4
4 Changes in the version 1.6.3 5
5 Changes in the version 1.6.2 6
6 Changes in the version 1.6.1 7
7 Changes in the version 1.6 8
8 Related information 12
9 Notes 14
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or unproper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
2.2 Repairs
Number of PLC blocks
Numbers of PLC blocks are the same for all types of controllers now
All types of controllers contain the same types of PLC blocks
7.2 Repairs
WebSupervisor is now supported properly
BusParams OK and AuxParams OK LBOs reaction repaired
In the previous version the Aux and Bus measurement were considered together (i.e. if Aux voltage was
out of range the Bus voltage was immediately also considered out of range and vice versa)
Wrong rounding of negative values in Math Fc and Ext Math Fc set to AVG fixed
Reset of the controller during Modbus reading of the history records longer than 18 characters prevented.
Modbus reading of history records longer than 18 characters caused reset of the controller.
Archives (*.ant)
For InteliGenNT/C GC For InteliGenNT/C BaseBox For InteliSysNT/C BaseBox
IG-GC-PSC-1.8.0.3.ant IG-BB-PSC-1.8.0.3.ant IS-PSC-1.8.0.3.ant
Note: 1) Terminals are switchable. When RS232 is switched on, RS485 serves as display terminal. When
RS485 is switched on terminal RS232 deactivated.
Note: 2) Terminal RS485 is available only for display connection (display terminal only).