4.1 Motor protection

Overload characteristics for 2nd generation current / voltage measuring modules


(e.g. 3UF7110-1AA01-0)
The following figure shows trip classes 5, 7, 10 (d), 15, 20, 25, 30, 35 and 40 for 3-pole
balanced loads:

Fan feeder selected class 20


due to starting current x5In and
starting time 15s

Pump feeder selected class 10


due to starting current x4In and
starting time 8s

Figure 4-2 Trip classes for 3-pole loads, 2nd generation current / voltage measuring modules