Tested To:
10/16/2013
Responsible Engineer: _______________________________Date:_____________
Paul Alt, Senior Project Engineer
10/16/2013
Approved By: ______________________________________Date:______________
Richard Proctor, Operations Manager
This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the
Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to
copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the
tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to
the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification
program.
TABLE OF CONTENTS
Page
LIST OF TABLES
Page
Table 1: History of Revision ................................................................................................................................. 2
Table 2: ANSI/TIA 568 C.0 - Table 7 - Maximum Supportable Distances and Attenuation for Optical Fiber
Applications by Fiber Type ............................................................................................................................ 4
Table 3: Part Numbers and Quantities................................................................................................................... 8
Table 4: Insertion Loss Forward Reading at 850 nm .......................................................................................... 10
Table 5: Insertion Loss Reverse Reading at 850 nm ........................................................................................... 10
Table 6: Insertion Loss Average Reading at 850 nm .......................................................................................... 10
Table 7: Insertion Loss Forward Reading at 1300 nm ........................................................................................ 11
Table 8: Insertion Loss Reverse Reading at 1300 nm ......................................................................................... 11
Table 9: Insertion Loss Average Reading at 1300 nm ........................................................................................ 11
LIST OF FIGURES
Page
Figure 1: Launch Lead Reference and Verification .............................................................................................. 7
Figure 2: Mated Test Jumpers Reference and Verification ................................................................................... 8
Figure 3: Cable Link Channel Testing Configuration ........................................................................................... 8
Figure 4: 6 Channel Link System MM (OM3) Configuration Test Setup .......................................................... 12
Declaration of Compliance
The 6 Channel Link System MM (OM3) Configuration was evaluated and found to be compliant
with the custom criteria supplied by the manufacturer as the criteria for this type of product does not
exist in ANSI/TIA-568-C.0 Table 7: Maximum supportable distances and attenuation for optical fiber
applications by fiber type for the specific application tested.
For this evaluation, the criteria is the Ethernet 10GBASE-S system measured at 850 nm and
1300 nm laser-optimized 50/125 µm TIA 492AAAC (OM3) having a maximum channel
value of 2.6 dB at 300 meters (984 feet).
Table 2: ANSI/TIA 568 C.0 - Table 7 - Maximum Supportable Distances and Attenuation for
Optical Fiber Applications by Fiber Type
5. The basic steps taken to measure and calculate multimode cabling attenuation include:
a. Verifying test jumper quality (once before testing; see clause E.5.1.2)
b. Setting the reference (once before testing; see clause E.5.1.4.2)
c. Measuring link attenuation (each link; see clause E.5.1.4.3)
d. Calculating link attenuation (each link; see clause E.5.1.5).
6. Both ends of the cabling link were disconnected; the ends were interchanged,
reconnected and the measurement was read again.
7. The resulting measurements recorded as the final, or P2, measurements in the reverse
direction.
Failure History
There was no history of failure for the testing in this section.
Disposition of Nonconformance
There was no failure for the testing in this section.
Test Data
Photographs:
References
External Reference Documents
ANSI Z136.2 ANS For Safe Use Of Optical Fiber Communication Systems Utilizing Laser
Diode And LED Sources
ANSI/TIA-568-C.0 General Telecommunications Cabling for Customer Premises
ANSI/TIA/EIA 604-10A-2002 Fiber Optic Connector Intermateability Standard, Type LC
ANSI/TIA 604-10B-2008, FOCIS-10 - Fiber Optic Connector Intermateability Standard, Type
LC (revision and redesignation of ANSI/TIA 604-10A-2002)
IEEE C2-2007, National Electrical Safety Code® (NESC®)
IEEE 802.3-2005, Carrier Sense Multiple Access with Collision Detection (CSMA/CD)
Access Method and Physical Layer Specifications
IEC 61918-2007, Industrial Communication Networks - Installation of Communication
Networks in Industrial Premises
NFPA 70, National Electrical Code®
TIA-492AAAA, Detail Specification For 62.5-μm Core Diameter/125-μm Cladding Diameter
Class IA Graded-Index Multimode Optical Fibers
TIA-492AAAB, Detail Specification For 50-μm Core Diameter/125-μm Cladding Diameter
Class IA Graded-Index Multimode Optical Fibers
TIA-492AAAC, Detail Specification For 850-nm Laser-optimized, 50-μm Core Diameter/125-
μm Cladding Diameter Class IA Graded-Index Multimode Optical Fibers
TIA-492CAAA, Detail Specification For Class IVA Dispersion-Unshifted Single-Mode
Optical Fibers
TIA-492CAAB, Detail Specification For Class IVA Dispersion-Unshifted Single-Mode
Optical Fibers With Low Water Peak
TIA TSB-31-C, Telephone Terminal Equipment Rationale and Measurement Guidelines for
US Network Protection 51
Intertek Documents
LEX-OE-FIB-179, Fiber Training Program Description
LEX-OE-FIB-178, General Fiber Safety Policy
LEX-OE-FIB-185, Fiber Optic Handling Safety Rules and Practices for Optical Fiber
Components and Systems Procedures
LEX-OE-FIB-037, Fiber Optic Insertion Loss and Reflectance Measurements