SERVICE MANUAL
TYPE HP-7 GLASS REINFORCED EPOXY BLADE FAN
97” Through 158" Dian:eter 6 Blades
etal
ain
RESILIENT
WASHERS,
RETAINING
FING
wer IA ORAIN HOLE
RR a
BALANGEO NAROWANE
73 gt,
mSaeouned us socne
tow
1 ——S ronaue rngonessvety 4]
sever A srnmcwneoat
Seeeetag tee — f
! ser enc,
x 4 FROM OUADE 1”
sro aN {is document was crealed duting
met The period when Panorpur Cooling
eae sports Leite wos 0 eensee of 19
Mrtsy Cooling Tower Company,
eectve 1992, Narey ond
it Penorpur lerminate thei oensing
BLADE PITCHING ILLUSTRATION Paro mutuo ogee
Shop en, he hwo companes Nave
Deen * ad no business relationship wih
ran PE bonnes
NUMOLH OF ULADES ——
Order No. =
Fan Diameter,
Trial Pitch Angle
rentH canton
—--ponwinaetan | Final Pitch Angle
senec rumnn —_—_—__———_
Speed, (pm
Contract HpFAN ASSEMBLY
1. Install blades with rotation arrow on toy. side anes
pointing In a clockwise direction. All L'ades ars
Interchangeable.
2, Hold each blade level and tighten tne 6 capscrews
sufficiently to hold each blade
8% Do not torque cap screws. Blades must be free te
tutn in retaining ring to adjust pitch,
&
SETTING FAN BLADE PITCH
“1, The tral pitch angie is the calculated setting for de-
load alr density,
Bi ‘ign conditions (water rate, hee
& and brake horsepower). Set the bevol protractor al
the trlal pltch angle supplied by The Marley Cooling
Tower Gompany and pitch ail the blades to the
‘same angle. All blades must be plichod to the same
Angle when each blade is pointing In the same
fection In the fan cylinder.
S61 the pjich angle by using a straight edge and
evel protractor 2" from tho tip of each biade.
Tighton the cap scrows progrossivoly betwoon 36
and 35 Ibs. torque. & crowfool wrench may be
used 10 torque the bolls that cannot to reached
with a sock
Recheck the pitch of each blade, as the pitch might
change while tightening the cap scrows
Segre ee
HUB COVER INSTALLATION
at lristall hub cover using special stainless stecl win
8 peoprane typo washors, and cap scrows
2, Tighten cap screws between 10 and 15 It/bs
torque.
CHECKING LOAD AT MOTOR
1. Operate the fan until motor and Geareducer have
reached operating temperature (approximately 30
minutes of operation). Take oporating voltage and
amperago moasuroinents for.use in calculating
motof HP by the following equation,”
cual volts x actual MPS saya
HP imaplat voll x anole any
2. Tho calcviated horsepower should ex ‘oat not ox
00d tho contract horsepower special ty Ira
ley Coollng Towar Company, Measurern
‘THE MARLEY COOLING TOWER COMPANY
above calculation must be made with hot water
lowing through the tower. Repiich blades as required
{o obiain contract horsepower. Measurements made
with no water or cold water will result in an erroneous
calculated horsepower.
3. Aone degree change in pitch will vary the power re:
quired by approximately 5 HP.
4. If blades are repitched, cap screws must be retight-
‘ened, between 30 and 35 fIJIbs. torque.
FAN REBALANCE
. 1. Each fan hub is statically balanced at the factory.
2, Replacement blades can be installed without (ield
rebalancing. The blades are manufactured with
uniform moment welghts and are completely inter
changeable.
3, Total tip track var
(2 % inch from the ret
Exoeee tip track will oa
tion should not exceed 1% inch
nce plane of fan rotation)
‘dynamic imbalance.
FAN MAINTENANCE
Check and, if necessary, retighten blade clamping hard
ware to prescribed torque afier the first week of opera
tion and subsequently at 6 month intervals. This should
bbe done al the time the Geareducer oll Is changed.
A periodic (monthly) inspaction of the fan should be
made to assure continued trouble-free operation. Any
accumulation of dirt or scale deposits on the fan should
be carafully and compleggly removed it there are any in:
dications of balance bof@p affected. Preventive mainte
‘nance (o control corrosive attack will prolong the use!ul
life of the fan.
Drain holes in blades must be free of obstructions.
MECHANICAL SERVICE
When writing The Marley Cooling Tower Company for
repair or replacement parts, please refer to the order
number and fan serial number; also state dlameter of
fan and number of blades.
“GAUL'ON. Whon chucking and/or changing viode
bitch eyeling Ign in normal operation, do nol exceed
30 trc.shour total motor starting time as motor may bo
ove heated.