Elektromotoren und
Geratebau Barleben GmbH
CEPTU®MKAT UCNbITAHUA
Asyxnonnaskopoe razoBoe pene
Tun: 40 (BF 80/Q)
Tun-No: 10-1.20,28.33,34.46.-0243,
Vicnontienwe cuctem KommyTaunu:
SasoncKkoi Homep: 880061
Nepexniovaioumit anemenr: marHutHas Tpy6ka ynpasneHina
Hanpaxenue: AC 12 B-maKc. 2508
Do 12B-maxc. 250 B
Bepxtiaa cuictema Kommyrauvin
4-4 KOHTAKT:
2. koHTaKr:
Hinitiaa cictema Kommyrauan
4 KOHTAKT :
2-H KOHTaKT
Yeraaka knanavHoro sateopa (w/c):
Tow AC 0,01 A-maxc 2A, cos p> 0,5
DC 0,01 A-maxe. 2A UR <40 we
S (sambiKarenb)
S (sampxarenb)
S (sambikarent)
S (sambikatenb)
1,00 mic + 15%
Ha rasoBom pene Byxronbya nposeeHbl M MM BEIAepxaHb! cneaylouMe McnLITAHMA:
1. Vcnbtrative sbicoxnm Hanprreniem no DIN EN 50216-2
2. Menbiranve repmetuutiocrn
3. Mposepxa paGorocnoco6HocTn
3.1. Fiposepxa pa6otocnocoSHocTH cicTeM KOMMYTayIMM KHONKOM KOHTPONA
3.2. TlpoBepka cpaGaTbisaHna BepxHeit cMCTeMBI KOMMyTAUIMM NpH CKonNeHMM raza:
OtxnioveHne npn o6véme rasa oT 200 go 300 cw?
3.3. Mlposepxa napamerpa cpa6arbisakiva KnanaHHoro saTBopa (ucnbiTaHMe noToKoM)
Bapnetex, 17.05.2018
Kontponep: 70 PA cp
Elektromotoren und
Gerditebau Barleben GmbH
‘Otto-on Guoricke-Alog 12
89178 Batleben (Germany)
° %
PEM,
KonTpon kavectea: ho
Tlemat
Ent
Tallon: 4090208700
Fax $40 30203 6330Elektromotoren und | (E M B
Geratebau Barleben GmbH | —wZ
TEST CERTIFICATE
Double-float Buchholz relay
Type: 40 (BF 80/Q) Works-no.: 880061
Type code: 10-1.20.28.33.34.46.-0243
Design of switching systems:
Switching element: magnet contact tube
Voltage: AC. 12 V- max. 250 Current: AC 0.01-max.2.A cos @> 0,5
DG 12V-max. 250 V (DC 0.01 max.2A LR < 40 ms
Upper switching system (alarm):
‘ist contact: S (normally-open)
2nd contact: S (normally-open)
Lower switching system (disconnection):
4st contact: 'S (normally-open)
2nd contact: S (normally-open)
Damper setting 1,00 m/s #15%
The following tests were performed successfully on the Buchholz relay:
4. Dielectric strength test in compliance with DIN EN 50216-2
2. Leakage test
3. Functional test
3.1. Switching system test by means of test key
3.2. Test of switching system operation in case of gas accumulation:
operation at a gas volume of 200 to 300 cm?
3.3. Test of damper operating value (flow test)
Barleben, 17.05.2018