You are on page 1of 7

1

Reactive Power Management in Distributed


Generation
Danial Saleem, Deputy Manager NTDC Lahore, Rehan Majeed, Deputy Manager NTDC Lahore.

motivation to use in DG has been discussed in [3]. The low


Abstract—Distributed Generation offers environmental and voltage problem acts in cascade form i.e., low voltage drives
economic benefits over centralized generation. Renewable energy the load to draw more reactive power and then shortage of
sources are inherently distributed in nature and the most
reactive power further reduces the voltage. This scenario is
important source to meet the future energy demands. Most
generators in distributed generation are asynchronous and are called voltage collapse and technique to avoid it in DG
affected by the problem of reactive power. They cannot produce systems using reactive power resources has been discussed in
reactive power but actually draws it from the power system. It [5]. DG systems are normally operated in micro-grid system.
can cause voltage drop which is not acceptable for the customers Three different strategies for Reactive Power Management in
due to narrow operating range of voltages for appliances. This DG systems operating within micro-grid are discussed in [11].
problem can be overcome by using reactive power management
Most of the renewable energy sources nowadays are either
techniques. Power factor control is most commonly used
technique for reactive power compensation. Many such devices wind or solar. In [12], it only focusses on these sources for the
used for reactive power management are explained in this paper. reactive power compensation.
Moreover, one of the many advantages of FACTS devices, i.e.,
voltage regulation is simulated in MATLAB.
As per above discussion, the performance of reactive power
compensation devices is most needed when the voltage is low
Index Terms—Distributed Generation, Reactive Power, and is near to voltage collapse. However, most devices
Renewable Energy, D-STATCOM, etc. including SVC do not perform well during this situation
because their reactive power generation is proportional to
I. INTRODUCTION square of the voltage. Contrary to this, Static Synchronous

T O meet the ever growing energy demand of the world,


renewable energy sources are the best solution. The
renewable energy sources are distributed by their nature, so in
Compensator’s (STATCOM’s) reactive power varies linearly
with the voltage and it holds a better solution for reactive
power compensation. The basic STATCOM model has been
addition to their everlasting fuel-free and green energy presented in [6]. Further to fine-tune the STATCOM
benefits, they can help reducing heavy power flows on performance for DG systems, PI controller based D-
transmission lines. In result, infrastructure costs to build new STATCOM has been discussed in [8] and [9]. To overcome
transmission facilities and the costs associated with the above discussed problem of poor performance in low
transmission losses can be avoided. So, Distributed Generation voltage, the improvement in Static VAR Compensator (SVC)
(DG), either renewable or non-renewable can be used to obtain technology has been discussed in [10] called SVC-MERS
this economic benefit. (Magnetic Energy Recovery Switch).

Most of the generators in DG are renewable and due to their In this paper, overview regarding DG and their relation with
inherent characteristics, they cannot supply reactive power to renewable energy has been presented. The driving factors for
the load. Reactive power is required along with active power using DG in future power systems has been discussed. The
for majority of the loads like inductive loads. Renewable inherent problem of reactive power with renewable energy
energy generators require reactive power for their excitation to sources are highlighted along with the strategies to overcome
generate active power. Furthermore, without reactive power, this problem. Finally, the most commonly used devices for
active power cannot be transferred to load [3]. If not properly reactive power compensation are explained.
handled, this can cause low voltage problems on the customer
end. II. DISTRIBUTED GENERATION
Distributed Generation (DG) is the electricity generation
This opens a new arena of research and development and a
where the generators are connected to the distribution level
lot of ongoing research has been conducted in this domain to
near the load consumers. The capacity of these generators
overcome this problem efficiently. There is a large number of
normally ranges from several kilowatts (kW) to tens of
devices which can be used to perform reactive power
megawatts (MW) [3]. DG systems use multiple small-scale
compensation. Each of these devices is different from each
generator units instead of few large-scale generator units near
other in its characteristics and each one has its own advantages
to end user with very slight dependence on transmission and
and disadvantages. Many of these devices along with
distribution infrastructure [16]. DG can be of non-renewable
2

or renewable type like wind and photovoltaic, however, due to prices. Since most of the conventional power plants are
recent technology advancements in renewable energy systems, normally based on fossil fuel or nuclear technology, they cause
most DGs are of renewable type. environmental issues [15]. Furthermore, the involvement of
many transmission lines, transformers and other equipment for
III. RENEWABLE ENERGY SOURCES – THE FUTURE the electric power transfer makes the fault vulnerability factor
Renewable energy is a form of energy which is obtained high and in result, decreases the reliability [15]. All of these
from natural processes (e.g. sunlight and wind) that are refilled issues are well addressed and overcome using DG systems.
at a higher rate than they are spent. Solar, wind, geothermal, The main motivation of integrating DG in power system is
hydropower, bioenergy and ocean power are sources of that most renewable energy sources are inherently distributed
renewable energy [17]. The total available potential of and as described in Section III, they are the most suited option
electricity generation from renewable sources is much higher to meet the ever-increasing energy demand of the world.
than that from conventional resources. Only a potential from
solar energy is much greater than the sum of all resources on It is of worth mentioning here that the most expected design
earth. The rate of replenishment of fossil fuel sources is very of future power system involves both conventional power
fast and it is believed that they cannot survive for more than plants as well as DG systems. DG systems actually helps
multiple decades. After the consumption of conventional power transmission network by locally meeting the energy
energy resources, the only way of generating energy would be demand at load centres during peak hours, thus reducing large
from renewable energy sources. At the advent of modern power flows on transmission and distribution network. Further,
renewable technology, it had somehow higher costs. But now, they help to avoid investment costs associated with building
considering levelized cost of electricity (LCOE), the rates of new transmission and distribution infrastructure [6]. However,
renewable are quite comparable to that from some thermal there are some problems like complex operational
power plants. In addition to this, they have an added advantage requirements, reactive power control and power quality which
to environment. need to be focused for the advancement in DG technologies
[3].
European countries are far ahead as compared to the rest of
the world in inducting renewable energy sources into their V. REACTIVE POWER MANAGEMENT FOR DG SYSTEMS
system. They have an agreement to generate 20% of its total
Since most generators in DG systems are asynchronous
energy consumption from renewable energy sources by 2020
type, they draw reactive power for their excitation. If proper
[3]. It is to be appreciated that renewable energy sources are
reactive power compensation will not be applied to DG
becoming the largest power generating type in the world as
systems, it can cause deficit of reactive power and result in
shown in the Fig.1 [4].
voltage drop. This voltage drop is not acceptable for
consumers as most of the devices has very narrow range of
voltage operation [3].

VI. STRATEGIES FOR REACTIVE POWER CONTROL IN DG


SYSTEMS
Reactive power management in DG systems can be
performed using three methods which are discussed below. For
controlling the reactive power, the quadrature axis current iq is
controlled using Proportional Integral (PI) controller
implementation. The controller diagrams for these strategies
are shown in the Fig. 2 [11].

Fig. 1. Electric Power Capacity Addition in the World [4].

IV. MOTIVATIONS FOR DISTRIBUTED GENERATION


The main objectives behind the DG application are
economic, environmental and reliability benefits. For
conventional power plants, huge transmission and distribution
infrastructure is required to transmit power from distant
generators to load centres. In addition to expensive
infrastructure costs, the costs associated with transmission and
distribution losses are also included in end user electricity
3

Fig. 2. Methodologies for Reactive power control in DG. (a) Voltage Droop It is to be noted that mpf is 0 for no compensation and becomes
Characteristic technique. (b) Voltage regulation technique. (c) Power Factor
equal to 1 for full compensation [11].
Correction technique [11].

A. Voltage Droop Characteristics VII. DEVICES FOR REACTIVE POWER MANAGEMENT


Representative Q-V curves for two DG units have been
shown in the Fig. 3. A. Shunt Capacitors
There are two types of shunt capacitors (connected in
parallel) used to supply reactive power, fixed and switched.
Fixed capacitors remain attached to the system irrespective of
the required compensation while switched capacitor can be
switched in and out of the system as per the requirement. This
method of compensation is not very desirable because it does
not provide continuous control of reactive power.
Furthermore, the output from the capacitors fall rapidly as the
voltage of the bus falls. However, they are economical way to
improve the power factor.
B. Synchronous Condensers
Synchronous condenser is a running synchronous motor in
over-excited state connected with the system drawing leading
reactive power. This in result, improves the power factor. It
does not get affected by the variation of voltage and can even
Fig. 3. Voltage Droop Characteristics of two DG units [11]. provide more reactive power during low voltage conditions. It
offers smooth control of reactive power unlike switched shunt
The two DG units have different slopes of Q-V capacitors. However, its dynamic response is not very good
characteristics depending upon the allowed ranges of operation due to inertia constraints.
for the terminal voltage which are characterized by design
specifications. The root mean square (rms) voltage at Point of C. Static VAR Compensator (SVC)
Common Coupling (PCC) of DG along with inherent Q-V SVC is a static device of reactive power generator (can also
characteristics are used to find the reference reactive power absorb reactive power) which can continuously vary its output
output from DG unit as shown in the Fig. 3 [11]. In result, it current to regulate certain parameter of electric power system
can control the bus voltage deviations using reactive power like power factor. There are two types of SVC: Fixed
control. Capacitor-Thyristor Controlled Reactor (FC-TCR) and
Thyristor Switched Capacitor - Thyristor Controlled Reactor
B. Voltage Regulation (TSC-TCR). TSC-TCR is normally used in DG systems
The controller diagram for voltage regulation based because it causes lesser power quality problems and is more
reactive power control is shown in the Fig. 2. Instead of giving flexible in operation range. The typical topology of TSC-TCR
Q-V curve characteristics, the rms reference voltage is is shown in the Fig. 4 [1].
specified to perform a required voltage regulation at PCC by
varying its reactive power. It is normally applied to the buses
where voltage sensitive loads are connected and very little
changes of voltage are allowed for them [11].
C. Power Factor Correction
Renewable energy sources like wind and PV power plants
mostly employ this technique. Capacitive devices are installed
near load bus with in DG module to improve power factor by
meeting the reactive power requirements of load. The
reference value of power factor is assigned to the controller
and the desired reactive power is injected through the DG unit.
The required power factor pfC is calculated using the following
relation [11]:
pf C
pf L (1)
Fig. 4. TSC-TCR Normal Configuration [1].
pf L  (1  m pf )(1  pf L )
2 2

Where, pfC is the desired power factor, pfL corresponds to load By varying the firing angle of TSC and TCR, the
power factor and mpf is the factor for degree of compensation. susceptance ‘BSVC’ can be varied in the control range of SVC.
4

The filters are to suppress the harmonics generated by its


operation. The range of voltage control for SVC will be given
by [1]:
Vref
% VSVC %
Vref (2)
1  X s Bmax 1  X s Bmin
Here in the above equation, Bmin and Bmax are inductive
capacitive susceptance limits respectively. XS is equal to XSVC
for control range. Between these limits, there lies the control
range of operation for SVC. Mechanically switched reactor
and capacitor can be added to above configuration to improve
the working of SVC.
Since its reactive power control depends on firing angle, it
can be used to get very fast response for voltage control.
However, the inherent problem has been caused by using
capacitors in its configuration i.e. it does not provide much Fig. 6. STATCOM Single phase configuration [1].
reactive power injection when it is most needed from it (during
low voltage conditions) [3]. Here, VPN waveform will be positive and negative square
wave for each half of the full cycle. The rms value of the
D. STATCOM fundamental component E1 can be easily found and it will be
STATCOM working principle is based on voltage-source given by [1]:
converter (VSC) and its operation is similar to that of S
2 Vdc 2 (3)
S ³0 2
synchronous condenser, however it does not have any moving E1 sin TdT Vdc
S
part which have inertia. This lack of inertial requirement cause
it to be faster and having superior dynamic response [3]. If E1>V (the source voltage), STATCOM will draw
STATCOM has many advantages over SVC like ease of capacitive current while it will draw inductive current for
connecting to real power systems, faster response, less E1<V. The No load, capacitive and inductive operation of the
requirement of space due to absence of large passive reactor in STATCOM is depicted in the Fig. 7.
the circuitry etc. [1]. The Basic model of STATCOM is
shown in Fig. 5.

Fig. 7. Explanation for Operation of STACOM [3].

E. Distribution STATCOM (D-STATCOM)


The power quality and reliability can be further improved
Fig. 5. Basic STATCOM Model [6].
in DG systems by employing new customized devices like D-
The biggest advantage of STATCOM is its performance STACOM, Dynamic Voltage Regulator (DVR) and Unified
during low voltages. Unlike capacitor dependent devices, the Power Quality Control (UPQC) [9].
reactive power output from STATCOM drops linearly with the The block diagram for DSTATCOM control for WTIG
voltages instead of square of voltage. This factor makes (Wind Turbine Induction Generator) is shown in Fig. 8,
STATCOM more reliable during low voltage conditions as though it applies for any DG system in general other than
compared to other devices [3]. To understand the operation WTIG. D-STATCOM uses STATCOM with Voltage Source
principle, consider single phase STATCOM as shown in Fig. 6 Inverter (VSI) getting feedback of reference reactive power
[1]. through PI Controller. This reference signal is used to
5

generate firing angle command to be compared with phase. MATLAB with distributed generation sources. A conventional
The actual information about the phase at that particular time power source along with Renewable energy sources like Solar
instant is gathered using phase locked loop (PLL). In this way, PV and Doubly Fed Induction Generator (DFIG) Wind
Vdc (the input capacitor voltage) of STATCOM changes Turbines are connected with the network. The micro grid with
according to the firing angle. Therefore, reactive power distributed generation is feeding the community loads having
becomes proportional to the difference of source voltage and fixed active power and reactive power demand as shown in
output voltage [8]. Fig.10.

Fig. 8. Block diagram for D-STATCOM control [8].

F. SVC-MERS
Due to limitations in operation of SVC and high cost of Fig. 10. Simulation in MATLAB – Distributed Renewable Resources with
STATCOM, a new methodology has been proposed for D-STATCOM
voltage control of induction generator [10]. The principle of
phase angle control is used and Magnetic Energy Recovery The variation in voltage at load bus has been monitored in
Switch (MERS) is connected in shunt with induction the load switchings, i.e., sudden load addition and sudden load
generator. The configuration and equivalent circuit of SVC- removal in case of fault. Two cases are analyzed, microgrid
MERS is shown in Fig. 9. The equivalent capacitance of SVC- with D-STATCOM named as Case A and without D-
MERS can be varied from 0 to infinity by controlling the STATCOM termed as Case B.
switching of force commutated switches. In discontinuous
Firstly the cases without D-STATCOM are simulated for
conduction mode, greater reactive power compensation has
large community load switched in and switched out as shown
been obtained using SVC-MERS [10].
in fig. 10 and 11 respectively. For Case A1, the modelled
community load having significant reactive power demand is
switched in at 0.15sec. It can be observed that there is huge
voltage drop to 0.9 p.u. due to deficiency of reactive power
supply from generation sources. Similarly for Case A2, the
load is switched out at 0.15sec. It can be observed that there is
large voltage increase to 1.13 p.u. due to excess of reactive
power from generation sources.

Fig. 9. SVC-MERS – Configuration and Equivalent Circuit [10].

VIII. SIMULATION IN MATLAB


In this simulation, only one of the many advantages of
FACTS devices has been observed, i.e., the function of voltage
regulation by D-STATCOM. A power system is modelled in Fig. 10. Case A1: Large community load switched in at 0.15sec
6

Fig. 11. Case A2: Large community load switched out due to 3-phase
fault at 0.15sec Fig. 13. Case B2: Large community load switched out due to 3-phase fault
at 0.15sec

Now the D-STATCOM is added in the same microgrid and


IX. CONCLUSION
above-mentioned switchings are analyzed named as Case B1
and B2 as shown in fig. 12 and 13 respectively. The voltage Motivations to use Distributed Generation in the power
regulation using reactive power control is monitored. For Case system along with benefits of renewable energy has been
B1, the modelled community load having significant reactive discussed. Reactive power compensation problem in DG is
power demand is switched out at 0.15sec. highlighted and different solutions are discussed for it. Many
reactive power compensation devices are explained in the end
section. Finally, one of the many advantages of FACTS
devices (D-STATCOM here), i.e., voltage regulation is
simulated in MATLAB. In the domain of reactive power
compensation, it can be expected that there are lot of
composite devices to come in near future utilizing advantages
of all above-discussed devices having lesser number of
drawbacks.

Fig. 12. Case B1: Large community load switched in at 0.15sec REFERENCES
[1] K. R. Padiyar, “Facts Controllers in Power Transmission and
As can be observed, initially the system voltage is such that Distribution”, New Age International (P) Limited, Publishers, 2007, pp.
the D-STATCOM is not operative and does not absorb or 55-213.
provide reactive power to the power network. At the instant of [2] K. Enrique Acha, Claudio R. Fuerte-Esquivel, Hugo Ambriz-Pe´rez and
large load switching in at 0.15 sec, there is resulting reactive
Ce´sar Angeles-Camacho, “FACTS Modelling and Simulation in Power
power deficiency, the D-STATCOM responds to this voltage
Networks”, A John Wiley & Sons, 2004, pp. 9-41.
decrease by supplying reactive power to the network, as seen
in fig.12. Similarly, for Case B2, the load is switched out at [3] Therese Uzochukwuamaka Okeke and Ramy Georgious Zaher,
0.15sec and resulting reactive power excess, the D- “Reactive Power Management for Distributed Generation: Motivation
STATCOM responds to this voltage increase by absorbing and Solutions”, IEEE 2013.
reactive power from the network, as seen in fig.13. [4] Dr. Fatih Birol, Executive Director, International Energy Agency, “IEA
Renewable Energy Medium Term Market Report 2015”, G20 Energy
Ministerial, Istanbul, October 2015.
[5] Desmond O. Ampofo, Amer Al-Hinai, M.S. El Moursi, “Utilization of
Reactive Power Resources of Distributed Generation for Voltage
Collapse Prevention in Optimal Power Flow”, IEEE 2015.
7

[6] T. Aziz, M. J. Hossain, T. K. Saha and N. Mithulananthan, “Stability


Evaluation of Distributed Generator Integrated System with Index based
Placement of STATCOM”, IEEE 2011.
[7] Hugo Morais, Tiago Sousa, Pedro Faria, Zita Vale, “Reactive Power
Management Strategies in Future Smart Grids”, IEEE 2013.
[8] S. P. Gawande, Nilesh A. Kubde, Manish S. Joshi and B.S.Sudame,
“Reactive Power Compensation of Wind Energy Distribution System
using Distribution Static Compensator (DSTATCOM)”, IEEE 2012.
[9] Ms. Manju Aggarwal, Prof. S. K. Gupta, Prof. Madhusudan, Dr. Gaurav
Kasal, “D-STATCOM control in Low Voltage Distribution System with
Distributed Generation”, Third International Conference on Emerging
Trends in Engineering and Technology, IEEE 2010.
[10] Miao-miao Cheng, Daisuke Shiojima, Takanori Isobe, and Ryuichi
Shimada, “Voltage Control of Induction Generator Powered Distributed
System Using a New Reactive Power Compensator SVC-MERS”, EPE-
PEMC 2012 ECCE Europe, IEEE 2012.
[11] F. Katiraei and M. R. Iravani, “Power Management Strategies for a
Microgrid with Multiple Distributed Generation Units”, IEEE
Transactions on Power Systems, Vol. 21, No. 4, November 2006.
[12] H A. Ellis, R. Nelson, E. Von Engeln, R. Walling, J. MacDowell, L.
Casey, E. Seymour, W. Peter, C. Barker, B. Kirby, J. R. Williams,
“Reactive Power Performance Requirements for Wind and Solar
Plants”.
[13] D. Gaikwad and S. Mehraeen, “Reactive Power Considerations in
Reliability Analysis of Photovoltaic Systems”, IEEE 2012.
[14] Yong Xue, Jiamei Deng and Shuangbao Ma, “Power Flow Control of a
Distributed Generation Unit in Micro-grid”, IPEMC IEEE 2009.
[15] “how-reactive-power-is-helpful-to-maintain-a-system-healthy”,
Available: http:// electrical-engineering-portal.com/how-reactive-power-
is-helpful-to-maintain-a-system-healthy
[16] “Virginia Tech Education Modules on Distributed Generation”,
Available: http://www.dg.history.vt.edu/ch1/introduction.html
[17] “Renewables topic”, Available: http://www.iea.org/topics/renewables/.

You might also like