condition if all the measured (or calculated) physical quantities describing the operating condition of the system can be considered constant for purposes of analysis.
When operating in a steady state condition if a
sudden change or sequence of changes occurs in one or more of the parameters of the system, or in one or more of its operating quantities, we say that the system has undergone a disturbance from its steady state operating condition.
Power System Analysis
Granger & Stevenson Chap 16 Disturbances can be large or small depending on their origin. A large disturbance is one for which the nonlinear equations describing the dynamics of the power system cannot be validly linearized for purposes of analysis. ❑ Transmission system faults ❑ Sudden load changes ❑ Loss of generating units ❑ Line switching are examples of large disturbances Power System Analysis Granger & Stevenson, Chap 16 A change in the gain of the automatic voltage regulator in the excitation system of a large generating unit could be an example of a small disturbance.
Small load changes can also be considered as
small disturbances
Power System Analysis
Granger & Stevenson, Chap 16 For a small disturbance, the system returns to its original steady state operating condition.
For a large disturbance, the system returns to
a new steady state operating condition
Power System Analysis
Granger & Stevenson, Chap 16 Steady state
Transient or rotor angle
Voltage
Frequency
Power System Analysis
Granger & Stevenson, Chap 16 Steady state stability studies examine the stability of the system under small incremental variations in parameters or operating conditions about a steady state equilibrium point.
The nonlinear differential and algebraic
equations of the system are replaced by a set of linear equations which are then solved by methods of linear analysis to determine if the system is steady state stable.
Power System Analysis
Granger & Stevenson, Chap 16 Transient stability studies involve large disturbances and linearization of the system equations is not permitted.
Transient stability is sometimes studied on a first
swing (first cycle) rather than a multi-swing basis.
First swing transient stability studies use a reasonably
simple generator model consisting of the transient internal voltage E behind transient reactance X’d.
In such studies the excitation systems and turbine
governing control systems of the generating units are not represented
Power System Analysis
Granger & Stevenson Chap 16 Usually, the time period under study is the first second following a system fault or other large disturbance.
If the machines of the system are found to remain
essentially in synchronism within the first second, the system is regarded as being transiently stable.
Multiswing stability studies extend over a longer
study period, and therefore the effects of the generating units' control systems must be considered since they can affect the dynamic performance of the units during the extended period.
Power System Analysis
Grangr & Stevenson, Chap 16 Machine models of greater sophistication are then needed to properly reflect the behavior of the system.
Thus, excitation systems and turbine-governing
control systems may or may not be represented in steady-state and transient stability studies depending on the objectives.
In all stability studies the objective is to determine
whether or not the rotors of the machines being disturbed return to constant speed operation. Obviously, this means that the rotor speeds have departed at least temporarily from synchronous speed.
Power System Analysis
Granger & Stevenson, Chap 16 To facilitate computation, three fundamental assumptions therefore are made in all stability studies: 1. Only synchronous frequency currents and voltages are considered in the stator windings and the power system. Consequently, dc offset currents and harmonic components are neglected. 2. Symmetrical components are used in the representation of unbalanced faults. 3. Generated voltage is considered unaffected by machine speed variations.
Power System Analysis
Granger & Stevenson, Chap 16 These assumptions permit the use of phasor algebra for the transmission network and solution by power- flow techniques using 60-Hz parameters.
Also, negative- and zero-sequence networks can be
incorporated into the positive sequence network at the fault point.
As we shall see, three-phase balanced faults are
generally considered. However, in some special studies circuit-breaker clearing operation may be such that consideration of unbalanced conditions is unavoidable.
Power System Analysis
Granger & Stevenson, Chap 16 The equation governing rotor motion of a synchronous machine is based on the elementary principle in dynamics which states that accelerating torque is the product of the moment of inertia of the rotor times its angular acceleration.
In the MKS (meter-kilogram-second) system
of units this equation can be written for the synchronous generator in the form
Power System Analysis
Granger & Stevenson, Chap 16 Power System Analysis Granger & Stevenson, Chap 16 Power System Analysis Granger & Stevenson, Chap 16 Tm and Te are positive for generator operation. In steady-state Tm equals Te, the accelerating torque Ta is zero, and, from (11.1.1), the rotor acceleration αm is zero, resulting in a constant rotor velocity called synchronous speed.
When Tm is greater than Te, Ta is positive and αm
is therefore positive, resulting in increasing rotor speed.
Similarly, when Tm is less than Te, the rotor speed
is decreasing.
Power System Analysis & Design,
Granger & Stevenson, Chap 16 It is convenient to measure the rotor angular position with respect to a synchronously rotating reference axis instead of a stationary axis. Accordingly, we define
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 It is also convenient to work with power rather than torque, and to work in per-unit rather than in actual units. Accordingly, we multiply (11.1.5) by ωm(t) and divide by Srated, the three-phase voltampere rating of the generator:
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Finally, it is convenient to work with a normalized inertia constant, called the H constant, which is defined as
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 The H constant has the advantage that it falls within a fairly narrow range, normally between 1 and 10 p.u.-s, whereas J varies widely, depending on generating unit size and type. Solving (11.1.7) for J and using in (11.1.6),
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 However in most cases ωp.u(t) =1
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Armature resistance is small and can be neglected Va is reference phasor
Ea leads Va by angle δ
Ia lags Va by Ɵ
Ea = Eacos δ +jEasin δ
Ia = Iacos Ɵ – jIasin Ɵ Po = 3VaIacosƟ
which is known as the power angle equation
For a given field current and terminal voltage
the maximum power output Pom or Pdm Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Figure 11.2 shows a simplified model of a synchronous machine, called the classical model, that can be used in transient stability studies. As shown, the synchronous machine is represented by a constant internal voltage E’ behind its direct axis transient reactance Xd’. This model is based on the following assumptions: 1. The machine is operating under balanced three- phase positive sequence conditions. 2. Machine excitation is constant. 3. Machine losses, saturation, and saliency are neglected. Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 In transient stability programs, more detailed models can be used to represent exciters, losses, saturation, and saliency. However, the simplified model reduces model complexity while maintaining reasonable accuracy in stability calculations.
Each generator in the model is connected to a system
consisting of transmission lines, transformers, loads, and other machines. To a first approximation the system can be represented by an ‘‘infinite bus’’ behind a system reactance.
An infinite bus is an ideal voltage source that
maintains constant voltage magnitude, constant phase, and constant frequency.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Figure 11.3 shows a synchronous generator connected to a system equivalent. The voltage magnitude Vbus and 00 phase of the infinite bus are constant. The phase angle δ of the internal machine voltage is the machine power angle with respect to the infinite bus.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Figure 11.4 shows a single-line diagram of a three-phase, 60-Hz synchronous generator, connected through a transformer and parallel transmission lines to an infinite bus. All reactances are given in per-unit on a common system base. If the infinite bus receives 1.0 per unit real power at 0.95 p.f. lagging, determine (a) the internal voltage of the generator and (b) the equation for the electrical power delivered by the generator versus its power angle δ.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 When a machine receives a disturbance that changes its operating point, it does not immediately settle to the new point, but oscillates until damping finally causes it to settle.
The energy gained during the disturbance
must be dissipated on an equal amount and this leads to the concept of Equal Area Criteria
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 The swing equations that have been developed are nonlinear in nature. Formal solutions of such equations cannot be explicitly found. Even in the case of a single machine swinging with respect to an infinite bus, it is very difficult to obtain literal- form solutions, and computer methods are therefore normally used .
Consider a synchronous generating unit
connected through a reactance to an infinite bus. Plots of electrical power pe and mechanical power pm versus power angle δ are shown in Figure 11.6. pe is a sinusoidal function of δ, as given by (11.2.1).
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Initial electrical and mechanical powers are equal and operating angle is δ0 Mechanical input changes from pm0 to pm1 Increase in mechanical power changes operating angle to δ1
Because of rotor inertia change does not happen
from one position and stops at the next but rotor swings (oscillates) before finally settling to point δ1
Areas A1 and A2 are equal
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Rotor swings to δ2 and then swings back toward δ1. If there is no damping, δ would continually oscillate around δ1.
However, damping due to mechanical and
electrical losses causes δ to stabilize at its final steady-state operating point δ1.
Note that if the power angle exceeded δ3, then
pm would exceed pe and the rotor would accelerate again, causing a further increase in δ and loss of stability.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 One method for determining stability and maximum power angle is to solve the nonlinear swing equation via numerical integration techniques using a digital computer. This method, which is applicable to multimachine systems, is described later.
However, there is also a direct method for
determining stability that does not involve solving the swing equation; this method is applicable for one machine connected to an infinite bus or for two machines.
This method is called the equal-area criterion.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 To derive the equal-area criterion for one machine connected to an infinite bus, assume ωp.u(t) =1, giving
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 The above equation begins at δ0 where dδ/dt = 0 (steady state) and ends with δ2 where dδ/dt also = 0 (point at which energy gained is exhausted) .
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 In practice, sudden changes in mechanical power usually do not occur, since the time constants associated with prime mover dynamics are on the order of seconds.
However, stability phenomena similar to that
described above can also occur from sudden changes in electrical power, due to system faults and line switching.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Example 11.4 shows how to use the equal area criteria to determine stability
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 The synchronous generator shown in Figure 11.4 is initially operating in the steady-state condition given in Example 11.3, when a temporary three-phase to-ground bolted short circuit occurs on line 1–3 at bus 1, shown as point F in Figure 11.4. Three cycles later the fault extinguishes by itself. Due to a relay misoperation, all circuit breakers remain closed
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Determine whether stability is or is not maintained and determine the maximum power angle.
The inertia constant (H) of the generating unit
is 3.0 per unit-seconds on the system base. Assume pm remains constant throughout the disturbance. Also assume ωp.u. =1.0 in the swing equation.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Assuming the temporary short circuit in Example 11.4 lasts longer than 3 cycles, calculate the critical clearing time.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 The critical clearing angle is such that δ3 does not go beyond Intersection with pm else rotor begins accelerating again
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 The p–δ plot is shown above. At the critical clearing angle, denoted δcr, the fault is extinguished.
The power angle then increases to a
maximum value δ3 = 1800 - δ0 = 156.050 = 2.7236 radians, which gives the maximum decelerating area. Equating the accelerating and decelerating areas,
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 If the fault is cleared before t = tcr = 11:38 cycles, stability is maintained.
Otherwise, the generator goes out of
synchronism with the infinite bus; that is, stability is lost.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 The figure above is a single line diagram of a three phase, 60Hz, synchronous generator, connected through transformers and parallel transmission lines to an infinite bus. All reactances are shown on the diagram in per unit on the same base. The infinite bus is receiving 0.8 per unit real power at 1.0 per unit voltage and 0.8 power factor lagging. The inertia constant (H) of the generating unit is 4.0 per unit- seconds on the system base. Determine the following: the internal voltage of the generator
the power angle equation for the system .
Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 The generator is operating as above when a three phase to ground fault occurs at P, at point at the source end one of the transmission lines reducing the power output to zero. After some time the fault is cleared and the system returns to normal. Sketch the p-δ plot of the power angle curve for before, during and after the fault demonstrating the equal area criterion for the critical clearing angle. Calculate the critical clearing angle and the critical clearing time.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 The synchronous generator in Figure 11.4 is initially operating in the steady state condition given in Example 11.3 when a permanent three-phase-to ground bolted short circuit occurs on line 1–3 at bus 3. The fault is cleared by opening the circuit breakers at the ends of line 1–3 and line 2–3. These circuit breakers then remain open. Calculate the critical clearing angle. As in previous examples, H = 3.0 p.u.-s, pm = 1.0 per unit and ωp.u. =1.0 in the swing equation.
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Looking in from the generator source (i) Short out infinite bus and find Thevenin impedance (ii) Replace infinite bus and find Thevenin voltage
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 tcr = 0.2331 sec
Power System Analysis & Design,
Glover, Sarma & Overbye, Chap 4 Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 The figure above is a single line diagram of a three phase, 60Hz, synchronous generator, connected through transformers and parallel transmission lines to an infinite bus. All reactances are shown on the diagram in per unit on the same base. The infinite bus is receiving 0.8 per unit real power at 1.0 per unit voltage and 0.8 power factor lagging. The inertia constant (H) of the generating unit is 4.0 per unit- seconds on the system base. Determine the following: the internal voltage of the generator
the power angle equation for the system .
Power System Analysis & Design, Glover, Sarma & Overbye, Chap 4 The generator is operating as above when a three phase to ground fault occurs at P, in the middle of one of the transmission lines. The fault is cleared by the breakers and the transmission line remains open. The system now operates with only one transmission line. Sketch the p-δ plot of the power angle curves for before, during and after the fault demonstrating the equal area criterion for the critical clearing angle. Calculate the critical clearing angle and the critical clearing time.