Automatic Switch Control Model 5800 Series Product Qualification Test Report
Automatic Switch Control Model 5800 Series Product Qualification Test Report
Revision A
Aug 1999
Proprietary Notice
This document contains information which is proprietary to EnergyLine Systems and is provided under
the terms and conditions of a Purchase Order Terms and Conditions Agreement between EnergyLine and
each of its customers. Disclosure of information contained in this document to third parties without prior
written permission from EnergyLine Systems is strictly forbidden.
Information in this manual is subject to change without notice and does not represent a commitment on
the part of the vendor.
Copyright 1998 EnergyLine Systems, Inc.
All Rights Reserved. Printed in the USA.
EnergyLine and the EnergyLine logo are registered trademarks of EnergyLine Systems, Inc.
All other trademarks are the property of their respective holders.
EnergyLine Systems, 1135 Atlantic Ave, Alameda, CA, USA
Tel (510) 864-9300/ FAX (510) 864-6860
Contents
Testing Certification:______________________________________________________4
Introduction_____________________________________________________________5
General Test Set-Up ______________________________________________________6
Test Points______________________________________________________________7
Definition of Correctly Operating Unit ________________________________________8
Qualification Test Matrix __________________________________________________9
Introduction
This document summarizes the product qualification tests that were performed on the
Model 5801-SC Automatic Switch Control. The units tested were regular production
Switch Control's, without any special modifications. Each unit had a Metricom radio
installed in them.
Two units went through each test.
Document Conventions
The following conventions are used in this document:
BOLD UPPER CASE Labels on faceplates and assemblies; switch positions.
Italic Names of manuals, manual sections, and software
screens.
“Quotes” Names of software setpoints.
Test Points
The following test points were used in the type tests, unless otherwise noted in the test
description.
1. Line
2. External inputs
§ FIC-3 (24V-RET)
§ FIC-6 (24V-RET)
§ FIC-7 (SW-CLOSED STATUS)
§ FIC-8 (SW-OPEN STATUS)
§ FIC-9 (IA+)
§ FIC-10 (IB+)
§ FIC-11 (IC+)
§ FIC-13 (VA+)
§ FIC-14 (VB+)
§ FIC-15 (VC+)
§ FIC-21 (VISUAL DISCONNECT)
3. External inputs
§ FIC-1 (SW-OPEN)
§ FIC-2 (SW-CLOSE)
§ FIC-4 (+24V)
Keying Test:
14 kHz - 10 GHz field strength = 5 V/m
8 EnergyLine Line Voltage Verify operation over Checked operation at the following
Variation Test worst case line voltage voltages: 96 and 144 VAC.
conditions.
9 EnergyLine Momentary Verify resistance to line Twelve tests were conducted, beginning
Power Loss voltage interruptions with a simulated power loss of 0.5 cycle.
and verify safe This power loss was successively
operation when lengthened by 0.5 cycles, up to 6 cycles.
interruptions occur. The start of each successive test was
delayed by 1-minute minimum.