DS ENGINEERING JUDGMENT FIRESTOP DETAIL

PROJECT : UNIVERSIDAD DE LIMA


CONTRACTOR : SACOSI
F-RATING = 2-HR. (SEE NOTE NO. 3 BELOW)
FRONT VIEW SECTION A-A

A A

1 3

1
3
2

1. CONCRETE WALL ASSEMBLY (MINIMUM 6" THICK) (2-HR. FIRE-RATING).


2. STEEL DOOR FRAME (2-HR. FIRE-RATING).
3. MINIMUM 5/8" DEPTH HILTI CP 606 FLEXIBLE FIRESTOP SEALANT.
NOTES : 1. MAXIMUM WIDTH OF JOINT = 1/4".
2. T-RATING MAY NOT EQUAL F-RATING IN ACCORDANCE WITH UL 2079.
3. FIRE-RATING OF ASSEMBLY IS DEPENDENT UPON THE PERFORMANCE
OF DOOR FRAME UNDER FIRE CONDITIONS.

(REFERENCE : UL/cUL SYSTEM NO. WW-D-0032)