You are on page 1of 8

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
1

Filter Configuration and PWM Method For Single


Phase Inverters with Reduced Conducted EMI Noise
Mohammad H. Hedayati, Student Member, IEEE, and Vinod John, Senior Member, IEEE

Abstract—Electromagnetic Interference (EMI) noise is one of PWM rectifier as the CM voltage imposed on the load is
the major issues during design of grid-tied power converters. A higher. Combined electrical noise produced by PWM rectifier
novel LCL filter topology for a single-phase PWM rectifier that and inverter, appears at the motor load terminals leading to
makes use of bipolar PWM method is proposed for a single-phase
to three-phase motor drive power converter. The proposed topol- higher CM current. The issue becomes more severe when the
ogy eliminates high dv/dt from the dc-bus common-mode voltage motor is connected to the inverter with long cables [10]–[12].
by making it sinusoidal. Hence, the high frequency common- The EMI noise generated by a power converter has to be
mode current injection to the ground as well as the motor kept within specified limits. Different solutions have been pro-
side common-mode current is minimized. The proposed filter posed [13]–[19] to meet the EMI recommendations. Different
configuration makes the system insensitive to circuit nonidealities
such as mismatch in inductors values, unequal turn on and turn PWM methods and their CM voltage characteristics are stud-
off delays, and dead time mismatch between the inverter legs. ied in [13] with an objective of identifying the method with
Different variants of the filter topology are compared to establish lowest CM voltage for a three-phase Voltage Source Inverters
the effectiveness of the proposed circuit. Experimental results (VSI). In [14], a specific filter to eliminate the high-frequency
based on EMI measurement on the grid side and the common- leakage current due to a grounded heat sink is presented, which
mode current measurement on the motor side are presented for
a 5kW motor drive. It is shown that the proposed filter topology requires RC networks to be connected between the grid star
reduces the EMI noise level by about 35dB. point, the machine neutral point, and the Y filter on the dc
bus. The number of additional components required for this
Index Terms—AC-AC power conversion, AC motor drive, bipo-
lar PWM, conducted emissions (CEs), common mode current, CM filter is high. A clamping filter is employed in [15]–[17]
common mode voltage, single-phase PWM-Rectifier, unipolar to reduce the dv/dt, thus preventing voltage doubling at the
PWM. motor terminals. This also inhibits excitation of the parasitic
capacitances of the cable and motor, hence having lesser EMI
I. I NTRODUCTION noise level. The energy from the clamp capacitors need to be
dissipated, which can be large if the clamp voltage has to be
U SE of grid-tied inverters are increasing dramatically
in applications such as battery chargers, regenerative
drives, front end converters for renewables, PWM-rectifiers,
close to the dc-bus voltage. Filter capacitors are introduced
between dc-bus positive rail to the ground and negative rail to
the ground in [18], which eliminates the CM voltage due to the
and active filters. PWM-rectifier is suitable in motor drive
PWM rectifier. In [19] a CM filter is proposed for three-phase
applications due to regenerative capabilities of the PWM-
PWM rectifier using conventional space vector pulse width
rectifier [1], [2]. Compared to diode bridge rectifiers, PWM
modulation (CSVPWM). In [20] it is shown that adding a CM
rectifiers eliminate lower order harmonics. However, high-
filter can result in oscillations. So, active damping is proposed
frequency electrical noise is injected to the grid by PWM
to damp the these oscillations. However, the implications on
rectifiers. Fast turn on and turn off of the IGBT generate
the design of single phase PWM inverters have not been
high dv/dt, which excites parasitic capacitances in the circuit.
considered in [13]–[19].
This leads to injection of narrow peaky current to ground
A topology to reduce the conducted EMI noise as well as
that contains excitations at high frequencies of the spectrum.
the dc-side leakage current is proposed in [21]. However, the
This causes problems such as shaft induced voltage, bearing
circulating current can be high and the proposed topology
currents, and EMI/EMC [3]–[7]. Standards such as CISPR 11
uses an LLCL-filter that needs additional passive components.
and IEC 61000 specify the limits of voltage disturbance on
In [22] an ac CM choke is added at the output of the inverter to
the mains by power converters for industrial, commercial, and
reduce the dc-side leakage current. However, the value of CM
domestic applications [8], [9]. Inverters with fast switches,
choke inductance itself is much larger than that of the output
such as IGBTs, are the root cause of the aforementioned
filter. In [23] ground current in a single phase grid connected
problems. These problems get worse in the presence of a
inverter is evaluated with different PWM methods and it is
This work is funded by the Department of Heavy Industry (DHI), Govern- shown that the bipolar PWM method results in lower ground
ment of India, under a project titled “Off-line and Real-time Simulators for current when compared with unipolar PWM method. This
Electric Vehicle/ Hybrid Electric Vehicle Systems”.
Mohammad H. Hedayati is with the Department of Electrical Engineer- configuration can be sensitive to nonidealities like switching
ing, Indian Institute of Science (IISc), Bangalore 560012, India (e-mail: delays in the legs of the inverter.
mh49929@gmail.com). In this paper, the grid side CM equivalent circuit is for-
Vinod John is with the Department of Electrical Engineering, In-
dian Institute of Science (IISc), Bangalore 560012, India (e-mail: mulated from the CM voltage and current analysis. This is
vjohn@ee.iisc.ernet.in). used to analyse the implication of the PWM technique that

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
2

MOTOR

Fig. 1. Conventional single phase grid-tied inverter with symmetrical LCL filter [?] connected to a three phase motor drive inverter with LC filter. The dotted
line indicates modification to the topology to make it insensitive to the nonidealities in the switches of the inverter.

is selected. It has been observed in [23] that bipolar PWM It has been shown in [24] that the common mode voltage
method provides lesser leakage current. In this work based on of the single phase grid-connected inverter in Fig. 1 can be
CM equivalent circuit, it is shown that it is the case for ideal derived as:
condition of the inverters. A novel modification is proposed dicom1 dicom2
vcm = 0.5L1 + 0.5L1 (2)
for the LCL filter topology that can overcome the issues dt dt
of inverter nonidealities, such as dead time and switching + 0.5Vdc (1 − Sa+ − Sb+ ) + 0.5eg .
timing mismatch between the legs of the single phase inverter.
Neglecting parasitic capacitances, Cp1 and Cp2 , and for the
Compared to the LCL filter for three phase system in [19],
case when the dotted connections of Fig. 1 are ignored, we
the structure of the proposed LCL filter can avoid a set of Y
have i2 = −i02 and ic = −i0c . Hence (2) can be simplified as,
capacitor on the dc-bus for single phase case. The proposed
method is validated by experimental results carried out on a vcm = 0.5Vdc (1 − Sa+ − Sb+ ) + 0.5eg . (3)
laboratory prototype of a 5kW single phase grid-tied inverter The CM voltage derived, for circuit configuration shown in
connected to a three phase induction motor drive. The effect Fig. 1, given in (3) depends on the dc-bus voltage, switching
of nonidealities are studied by testing the set-up with unequal states, and the grid voltage. It can be observed that for different
dead-time given to the legs of the converter. The ground PWM methods, different CM voltage would appear at the dc-
leakage current for different cases is quantified. The EMI tests bus.
are carried out for different cases and the best case is pointed
out. It is shown that there is a 40dB reduction in the noise III. PWM A NALYSIS
level in the proposed filter topology compared to the base line The high dv/dt in the CM voltage excites the parasitic
condition. capacitances, which results in current injection to ground. In
this section it is shown that use of bipolar PWM method can
eliminate switching dv/dt in the CM dc-bus voltage. The CM
II. G RID S IDE CM VOLTAGE A NALYSIS voltage given in (3) consists of two components, the sinusoidal
The circuit in Fig. 1, without the dotted lines, shows a component which is the half of the grid voltage and the PWM
conventional single phase grid-tied inverter with LCL filter voltage which depends on the switching states. If the switching
as suggested in [?], connected to a three phase motor drive states are such that the coefficient of the Vdc in (3) is constant,
inverter with LC filter. In the shown topology, the filter then the effect of switching is eliminated in the CM voltage.
inductors are split into two and placed in the line and neutral.
A. Unipolar PWM Method
In the proposed filter topology the filter capacitor is also
split into two series connected capacitors. It is shown that in In the case of unipolar PWM method, the modula-
such configuration, when bipolar PWM is used, it is possible tion signals, used to obtain the PWM pulses, are da =
to connect node “M” and “O”, which helps to reduce the M sin(ωt), db = −da . Where, M is the modulation index.
sensitivity of the circuit to the nonidealities of the inverter. da and db are compared with carrier and fed to the switches.
With the help of this filter configuration, it is possible to use From the switching states within a switching cycle, the value
the LCL inductor in CM circuit to reduce the CM current. of (1 − Sa+ − Sb+ ) can be shown to be 1, 0, − 1, 0 and 1.
The dc-bus CM voltage, vcm , of the conventional single phase This is depicted in Fig. 2(a). With this PWM method the CM
inverter shown in Fig. 1 is defined as, voltage would be having a pulsed waveform superimposed on
a sinusoidal. The δv value of the pulsed is 0.5Vdc and the δt
vP g + vng depends on how fast the switching action is taking place in
vcm = vOg = . (1)
2 the IGBT legs.

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
3

(a) (b)

Fig. 2. Switching states of a single phase H-bridge inverter using (a) unipolar PWM method, (b) bipolar PWM method.

B. Bipolar PWM Method and (9) the CM equivalent circuit is as shown in Fig. 3. where,

In bipolar PWM method, the modulation signal is d = vAO + vBO


vcon = = 0.5Vdc (1 − Sa+ − Sb+ ). (4)
M sin(ωt). Sa+ is calculated by comparing the modulation 2
signal with the carrier. The Sb+ is equal to (1 − Sa+ ). Hence, With bipolar PWM the vcon = 0. Hence, there is no high dv/dt
the term (1 − Sa+ − Sb+ ) is always equal to zero in (3) which to excite the parasitic capacitances Cp . However finite vcon is
makes the coefficient of the Vdc equal to zero. This is shown generated in practice due to mismatch in dead-time, mismatch
in Fig. 2(b). So, the high dv/dt due to switching actions are of the two inductors, of nominal value L1 , that are placed in
eliminated in the dc-bus CM voltage based on (3) and it phase and neutral, and delays in the circuit. If the dead-time
consists of only sinusoidal waveform with amplitude of half circuit is made of analog components, due to tolerances of
of the ac voltage. the capacitances and resistances, different values of dead-time
Use of bipolar PWM method for single phase grid- can be offered to the legs. This causes glitches to appear in
connected converters is suggested in [?] to reduce the ground the CM voltage. To make sure these glitches do not excite
leakage current. However, the circuit is sensitive to the nonide- the parasitic capacitances, a path is provided within the filter
alities. In the case of nonidealities like, dead time mismatch, circuit. This path is recognized by connecting the points “O”
mismatch in inverter side inductors, unequal turn on and turn and “M” together, as shown by the dotted line in Fig. 1. With
off of the switches, and propagation delays, high frequency this connection, if there are any glitches in the CM voltage
pulses, with high dv/dt, are generated in CM voltage. due to factors such as dead time, switching timing delay, or
To obtain the same effective switching frequency, the bipolar mismatch between the legs of the inverter, etc. the CM current
PWM switching frequency should be twice of the unipo- will circulate inside the filter and will not pollute the grid. A
lar PWM switching frequency. This causes higher switching capacitor CM g is connected to ground which reduces the high
losses and lower efficiency in the power converter using frequency voltage on the dc side of the inverter.
bipolar PWM. However, it is expected that in this case a The CM g design is based on the guidelines suggested
smaller EMI filter is needed, which has lesser losses. The in [19]. The capacitor CM g is small, of the order of tens
efficiency and loss evaluation of the overall system including of nanofarad. So, at the low frequency it acts as an open
the EMI filter is out of scope of this work. circuit. The grid side CM circuit at low frequency can be
approximated as shown in Fig. 4(a). The resonance frequency
of the filter, for low frequency approximation circuit, is given
IV. CM C IRCUIT D ESIGN by fres = 2π√1L C . As said before the vcon = 0 for bipolar
1
PWM method. Hence, the resonance frequency is not excited.
The condition derived in Section III.B shows that it is High frequency equivalent circuit of CM circuit shown in
possible to connect the mid point of the dc-bus to the mid Fig. 3 is depicted in Fig. 4(b). The capacitor CM g will reduce
point of ac filter capacitor without any circulating current in the high frequency voltage between point “M” and “g”. The
the connection. The CM equations of the circuit are derived voltage is divided between Cp1 , Cp2 and CM g as given in (5).
in [24] and summarized in Appendix A. Based on (6), (7), (8) Cp1 and Cp2 represent the parasitic capacitances of semicon-

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
4

Fig. 3. CM equivalent circuit of the single phase to three phase motor drive shown in Fig. 1.

TABLE I
S INGLE P HASE G RID - TIED INVERTER PARAMETER VALUES

SL.NO. PARAMETER PER UNIT ACTUAL


1 DC bus voltage Vdc 2.92 700V
2 Filter Inductance L1 = L2 24.5e − 3 900µH
3 Filter Inductance Lf 49e − 3 1.8mH
4 Filter Capacitance C 72e − 3 20µF
5 Filter Capacitance Cf 72e − 3 20µF
6 Filter Capacitance Cy 36e − 3 10µF
(a) 7 Filter Capacitor CM g 272e − 6 75nF

voltage at high frequencies.


vM g Cp2
= (5)
vcon Cp1 + Cp2 + CM g
Addition of capacitor CM g can cause resonance oscillations
in the CM circuit. Due to the value of the CM g , which is small,
the resonance frequency is much higher than the switching
frequency. These oscillations need to be damped passively. A
RC branch is used in parallel with the capacitor CM g to damp
the resonance oscillations.
In the case of unipolar PWM, vcon is non zero. The
pulsed shaped would be as shown in Fig. 2(a). This pulsed
voltage will cause high current to circulate in the set-up and
(b) it also excites the resonance frequency of the filter. Also, the
benefits of reduced output ripple in the filter inductors, due to
Fig. 4. Grid side CM equivalent circuit of the filter with, (a) Low-frequency unipolar PWM, is lost. Hence, the use of unipolar PWM is not
approximation, (b) high-frequency approximation.
beneficial for the proposed circuit topology, where as bipolar
PWM has the advantage of reduced CM voltage and ground
leakage current. The LCL filter components are selected using
ductor chips to baseplate of the switch modules packages. By method suggested in [25].
keeping the value of CM g reasonably high in comparison to
Cp1 and Cp2 , the voltage vM g is reduced. However, a very V. E XPERIMENTAL R ESULTS
large value of CM g will lead to higher fundamental ground A 5kW single-phase active rectifier connected to a three
leakage currents. CM g that gives an attenuation of 95% based phase motor drive prototype is built in the laboratory to
on (5) is used for the design. The use of CM g ensures that demonstrate the effectiveness of the proposed method. The
any subsystem connected to the dc-bus will see a reduced CM IGBT based converter has a switching frequency of 10kHz for

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
5

Voltage
Current

C1 C1
C2

C1 DC1M C2 DC1M Timebase 0.0 ms C1 DC1M Timebase 0.0 ms


100V/div 10.0A/div 5.0ms/div 200V/div 5.0ms/div
0.0V offset 0.0V offset 100kS 2.0MS/s 0.0V offset 100kS 2.0MS/s

(a)
Fig. 5. Grid voltage and grid current of the power converter operating at
3kW as a UPF, 200V/div, 20A/div, 5ms/div.

the active rectifier when using bipolar PWM and 5kHz for the
case of unipolar PWM. The switching frequency of the motor
C1
side inverter is 10kHz. The base values are Pbase =5kVA,
Vbase =240V, and fbase =50Hz. The base capacitance, and
inductance are derived as,
2
Pbase Vbase
Cbase = 2 ; Lbase = .
2πfbase Vbase 2πfbase Pbase C1 DC1M Timebase 10.0 ms
200V/div 5.0ms/div
0.0V offset 100kS 2.0MS/s
The values are calculated to be, Cbase = 276µF and Lbase =
(b)
36.7mH, the designed parameter values are given in Table I.
A three phase, 415V, 5kW, 50Hz induction motor is connected Fig. 6. CM voltage vcm (i.e. dc-bus midpoint to ground voltage) in the single
to the inverter. The motor is controlled using V/F scheme. For phase inverter, 200V/div, 5ms/div. (a) case “a” no CM filter with unipolar
PWM, (b) case “b” no CM filter with bipolar PWM.
loading purpose the shaft of the induction motor is coupled
with an doubly fed induction generator. This configuration
for testing the motor drive [26], allows circulation of power
Fig.6(b) lesser high frequency CM voltage is observed with
and draws only losses from the grid. The PWM rectifier
the bipolar PWM method.
is controlled using an outer voltage control loop, using PI
In unipolar PWM method the effective switching frequency
controller, and inner current controller loop using PR con-
is double the switching frequency. In the case of bipolar PWM
troller. An Altera Cyclone II FPGA platform is used for the
method the current ripple frequency is same as the switching
implementation of the control algorithm. The power converter
frequency. Hence, with unipolar PWM the ripple current in L1
is tested at 3kW to validate its normal operation as a grid-
is effectively reduced by half. Comparing bipolar with unipolar
tied converters. The results are depicted in Fig. 5. It can be
PWM method, the bipolar PWM needs to operate its legs at
seen that the current is in-phase with the voltage, indicating
twice of the switching frequency to obtain the same level of
the unity power factor (UPF) operation. The grid current is
ripple current in inductor L1 as in the case of unipolar PWM.
almost free of high frequency switching ripple indicating the
The setup has been tested in a large number of configura-
effectiveness of the LCL filter. However, it can be observed
tions, out of which the following four cases are of interest.
that finite amount of lower order harmonics are presented in
the grid current. This is due to the presence of the lower order Case a) no CM filter with unipolar PWM.
harmonics in the grid voltage. This can be verified by looking Case b) no CM filter with bipolar PWM [?].
at the grid voltage; a flat peak is an indication for presence Case c) with “OM” connection and with bipolar PWM.
of harmonics at the fifth, seventh, eleventh, etc, in the grid Case d) with “OM” connection and the capacitor CM g
voltage. and with bipolar PWM.
The rectifier was tested with both unipolar and bipolar Case “d” corresponds to the proposed filter configuration
PWM method and the CM voltage, dc-bus midpoint to ground including all the dotted connections shown in Fig. 1.
voltage, is captured. For the case of unipolar PWM shown in The set-up has been tested at 70% loaded, with unipolar
Fig. 6(a), it can be seen that a high frequency pulsed voltage PWM, and bipolar PWM with and without the proposed filter
at 5kHz is superimposed on a 50Hz sinusoidal voltage. These circuit configuration. Power losses and the efficiency have
pulses have a high dv/dt of the order of 1kV/µs depending on been measured by the help of YOKOGAWA WT1600 and the
IGBT characteristics. This high dv/dt, which occur at every results are tabulated in Table II. The switching frequency of
instance of switching, excites the parasitic capacitances and bipolar PWM is twice of unipolar PWM. This cause higher
injects a peaky current to ground. On the other hand, CM volt- switching losses and lower efficiency. It can be seen that the
age of the bipolar PWM shown in Fig.6(b) is sinusoidal with efficiency is reduced by 2.88% while using bipolar PWM
magnitude of half of the grid voltage. Comparing Fig. 6(a) and method. The losses and the efficiency of the set-up using

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
6

F1

F1 F2

F1 FFT(C1) Timebase 0.0 ms F1 FFT(C1) F2 FFT(C2) Timebase 0.0 ms


20dB/div 1.0ms/div 20dB/div 20dB/div 1.0ms/div
1.00MHz/div 1MS 100MS/s 1.00MHz/div 1.00MHz/div 1MS 100MS/s

(a)
Fig. 8. EMI noise level comparison with different filter configuration and with
bipolar PWM. Top, case “c” with “OM” connection (F1 ). Bottom (F2 ), case
“d” with “OM” connection and with capacitor CM g . 20dBV/div, 1MHz/div.

TABLE II
P OWER LOSSES AND EFFICIENCY WITH BIPOLAR AND UNIPOLAR PWM.
F1 Case Losses (W) Efficiency
a 204 93.86%
b 309.5 90.98%
c&d 308.7 90.99%
Measurement made at 3.5kW load.

F1 FFT(C1) Timebase 0.0 ms


20dB/div 1.0ms/div
1.00MHz/div 1MS 100MS/s
about 5dB.
(b)
To see the effectiveness of the proposed CM filter, the setup
Fig. 7. EMI noise level comparison, (a) case “a” no CM filter with unipolar has been tested with unequal dead times. In the ideal case both
PWM, (b) case “b” no CM filter with bipolar PWM. 20dBV/div, 1MHz/div. legs of the active rectifier uses dead-time of 3µs. Mismatch in
the dead time and different delays in the circuit is simulated
by reducing the dead-time in one of the legs by 1µs. The
bipolar PWM with proposed filter configuration has been results are shown in Fig. 9. Fig. 9(a) shows the CM voltage, as
measured. It is seen that addition of the proposed circuit suggested in [?]. It can be seen that the high frequency pulses
topology does not further reduce the efficiency of the power with magnitude of Vdc /2 are super imposed on the sinusoidal
converter. voltage. This can inject high peaky current to ground. Fig. 9(b)
To estimate the effectiveness of the proposed filter, con- shows the CM voltage with proposed CM filter. It can be seen
ducted noise emission test has been carried out by connecting that with the proposed filter the CM voltage stays sinusoidal
a single-phase line impedance stabilization network (LISN). even when the dead times are not equal. Fig. 10 shows the
The LISN prevents noise from the mains to converter set- EMI noise level, when unequal dead time is introduced to the
up, which can affect the test results. It also provides a 50Ω system. By comparing Fig. 10(a) and Fig. 10(b) it can be seen
match connectors for the receiver. The LISN is used with a that, the amount of current injected to the ground is reduced
high-frequency oscilloscope (500 MHz, 5 GSa/s, Lecroy 6050) and the EMI noise level is reduced by about 20dB at 200kHz
as a receiver [27]. The data captured are processed by the and 10dB at 900kHz with the proposed filter,.
oscilloscope and the FFT of the waveforms are shown in Fig. 7 The grid side and the motor side CM currents have been
for the frequency range up to 10MHz. measured in all the tests and the results are tabulated in
Fig. 7(a) shows the EMI noise level with the unipolar Table III. Comparing case “d” with case “a” it can be seen
PWM and switching frequency of Fsw =5kHz (case “a”). that the CM current is reduced by more than four times
The EMI noise level with the bipolar PWM and Fsw =10kHz at the grid side and about 21 times at the motor side in
is shown in Fig.7(b) (case “b”). It can be seen that just case “d”. However, the grid side CM current in case “d”
by using the bipolar PWM method with double switching is slightly higher than the cases “b”. This is not a problem
frequency we can reduce the EMI peak around 0.2MHz by as long as the difference is small and the value is within
about 20dB. However, due to switching nonidealities this the acceptable standard limits. For instance, standard VDE
situation is altered. The results for cases “c”, and “d” are V 0126-1-1 indicates that the PV system leakage currents
shown in Fig. 8. It can be seen that the least EMI noise should not be higher than 300mA and in the case of violations
level corresponds to the case “d” (with “OM” connection and the system must be disconnected within 0.3 seconds [28].
the capacitor CM g ). Comparing case “c” and “d”, the peak The motor side ground leakage current with the proposed
at 0.2MHz is eliminated and the peak at 3.4MHz is reduced filter configuration is the least among all the cases. It can be
about 10dB. Comparing cases “a” and “d” it can be seen that observed that with the proposed filter configuration, given in
in case “d” the peak 0.2MHz is reduced about 40dB, peak at case “d” and shown in Fig. 1, the system is insensitive to the
0.9MHz is eliminated and peak around 3MHz is reduced by dead-time mismatch. The grid side and the motor side ground

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
7

C1 F1

C1 DC1M Timebase 10.0 ms F1 FFT(C1) Timebase 0.0 ms


200V/div 5.0ms/div 20dB/div 1.0ms/div
0.0V offset 100kS 2.0MS/s 1.00MHz/div 1MS 100MS/s

(a) (a)

C1 F1

C1 DC1M Timebase 10.0 ms F1 FFT(C1) Timebase 0.0 ms

200V/div 5.0ms/div 20dB/div 1.0ms/div


0.0V offset 100kS 2.0MS/s 1.00MHz/div 1MS 100MS/s

(b) (b)

Fig. 9. CM voltage with unequal dead time (a) without the CM filter, (b) Fig. 10. EMI noise level with unequal dead time (a) without the CM filter,
with the CM filter. 200V/div, 5ms/div. (b) with the CM filter. 20dBV/div, 1MHz/div.

TABLE III
C ASE STUDIES OF GRID SIDE AND MOTOR SIDE CM CURRENT VALUES
WITH EQUAL DEAD TIME OF 3µs AND WITH UNEQUAL DEAD TIME OF 3µs frequency CM voltage. The experiments on the laboratory
AND 2µs. prototype show that the CM voltage with bipolar PWM is
Case Grid Side CM Current (mA) Motor Side CM Current (mA) sinusoidal. The conducted noise emission test has been carried
Equal DT Unequal DT Equal DT Unequal DT out, which confirms the effectiveness of the proposed method,
a 231.2 —— 97.4 —— by which the peak noise in the EMI spectrum was reduced
b 45.8 82.5 25.7 37.2
c 56.2 56.3 13.8 13.9 by 35dB. CM current measurement on a 5kW laboratory
d 49.5 49.7 4.5 4.6 prototype indicates that the proposed CM filter configuration
using bipolar PWM method will reduce the grid side CM
current by more than four times and the motor side CM current
is reduced by 21 times when compared with a baseline case
leakage current remain almost the same with and without the
that utilizes unipolar PWM method and without such a filter.
nonidealities.

A PPENDIX A
VI. C ONCLUSION
An LCL filter configuration that can be used with a single The CM equations of the circuit are derived in [24] and
phase inverter that leads to reduced CM current EMI is given here.
proposed. The CM voltage for the topology is derived and Vdc + dicom1 vcaM + vcbM
it is shown that the CM voltage depends on the circuit config- (Sa + Sb+ − 1) = 0.5L1 + (6)
2 dt 2
uration and also depends on the PWM method. Unipolar and
bipolar PWM methods have been analysed. Using switching vcaM + vcbM dicom2
function analysis it is shown for the proposed filter configu- = 0.5L2 + 0.5eg − vM g (7)
2 dt
ration that the CM voltage at the dc-bus will be sinusoidal if
bipolar PWM is used. The modification of connecting LCL
d vcaM + dvcbM
filter midpoint to the dc-bus midpoint ensures that there is imid = 2C ( ) (8)
no high frequency common mode excitation of the power dt 2
dvM g
converter parasitics even under non ideal conditions of the iM g = CM g (9)
inverter. The circuit is modified to make the system insensitive dt
to the nonidealities of the inverter. The capacitor CM g ensures With the help of (6), (7), (8) and (9) the CM equivalent circuit
that subsystems connected to the dc-bus experience low high is drawn and is depicted in Fig. 3.

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI
10.1109/TIA.2014.2387483, IEEE Transactions on Industry Applications
8

R EFERENCES [20] ——, “Common-mode and differential-mode active damping for PWM
rectifiers,” IEEE Trans. Power Electron., vol. 29, no. 6, pp. 3188–3200,
[1] J. Rodriguez, J. Dixon, J. Espinoza, J. Pontt, and P. Lezana, “PWM June 2014.
regenerative rectifiers: state of the art,” IEEE Trans. Ind. Electron., [21] W. Wu, Y. Sun, Z. Lin, Y. He, M. Huang, F. Blaabjerg, and H.-H.
vol. 52, no. 1, pp. 5–22, Feb. 2005. Chung, “A modified llcl filter with the reduced conducted emi noise,”
[2] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL- IEEE Trans. Power Electron., vol. 29, no. 7, pp. 3393–3402, July 2014.
filter-based three-phase active rectifier,” IEEE Trans. Ind. Appl., vol. 41, [22] D. Dong, F. Luo, D. Boroyevich, and P. Mattavelli, “Leakage current
no. 5, pp. 1281–1291, Sept.-Oct. 2005. reduction in a single-phase bidirectional ac-dc full-bridge inverter,” IEEE
[3] E. Persson, “Transient effects in application of PWM inverters to Trans. Power Electron., vol. 27, no. 10, pp. 4281–4291, Oct 2012.
induction motors,” IEEE Trans. Ind. Appl., vol. 28, no. 5, pp. 1095– [23] O. Lopez, F. Freijedo, A. Yepes, P. Fernandez-Comesaa, J. Malvar,
1101, Sep.-Oct. 1992. R. Teodorescu, and J. Doval-Gandoy, “Eliminating ground current in a
[4] A. Bonnett, “Analysis of the impact of pulse-width modulated inverter transformerless photovoltaic application,” IEEE Trans. Energy Convers.,
voltage waveforms on AC induction motors,” IEEE Trans. Ind. Appl., vol. 25, no. 1, pp. 140–147, March 2010.
vol. 32, no. 2, pp. 386–392, Mar.-Apr. 1996.
[5] C. Melhorn and L. Tang, “Transient effects of PWM drives on induction [24] M. Hedayati and V. John, “Filter configuration and pwm method for
motors,” IEEE Trans. Ind. Appl., vol. 33, no. 4, pp. 1065–1072, Jul.-Aug. single phase inverters with reduced conducted emi noise,” in IEEE
1997. Transportation Electrification Conference and Expo, Beijing, China,
[6] G. Skibinski, R. Kerkman, and D. Schlegel, “EMI emissions of modern Sep. 2014.
PWM ac drives,” IEEE Ind. Appl. Mag., vol. 5, no. 6, pp. 47–80, Nov.- [25] P. Channegowda and V. John, “Filter optimization for grid interactive
Dec. 1999. voltage source inverters,” IEEE Trans. Ind. Electron., vol. 57, no. 12,
[7] P. L. Alger and H. W. Samson, “Shaft currents in electric machines,” pp. 4106–4114, Dec. 2010.
Trans. Amer. Inst. of Elect. Engineers, vol. XLIII, pp. 235–245, Jan. [26] M. Hedayati and V. John, “Circulating power test setup for a PWM
1924. rectifier motor drive,” in Power Electronics, Drives and Energy Systems
[8] “Industrial, scientific and medical radio-frequency equipment electro- Conf., Bangalore, India, 2012, pp. 1–5.
magnetic disturbance characteristics limits and methods of measure- [27] ——, “Design of a 3-phase line impedance stabilization network for
ment, CISPR11 Edition 5.0, 2009-05.” conducted emission test,” in Sixth National Power Electronics Conf.
[9] “Electromagnetic compatibility (emc) - part 4-6: Testing and measure- 2013, IIT Kanpur, India, Dec. 2013.
ment techniques - immunity to conducted disturbances, induced by [28] “Automatic Disconnection Device between a Generator and the Public
radio-frequency fields, IEC 61000 Edition 3.0, 2008-10.” Low-Voltage Grid, Din Electrotechnical Standard DIN VDE 0126-1-1,
[10] S. Amarir and K. Al-Haddad, “A new design tool to protect industrial 2005.”
long-cable pwm asd systems against high-frequency overvoltage prob-
lems,” Canadian J. of Elect. and Comput. Eng., vol. 33, no. 3/4, pp.
125–132, Summer 2008.
[11] L. Wang, C.-m. Ho, F. Canales, and J. Jatskevich, “High-frequency
modeling of the long-cable-fed induction motor drive system using
tlm approach for predicting overvoltage transients,” IEEE Trans. Power Mohammad H. Hedayati (S’14)was born in Kaze-
Electro., vol. 25, no. 10, pp. 2653–2664, Oct 2010. roon, Iran, in 1984. He received his B.Tech. degree
[12] H. Akagi and I. Matsumura, “Overvoltage mitigation of inverter-driven in electrical engineering from the Islamic Azad
motors with long cables of different lengths,” IEEE Trans. Ind. Appl., University, Kazeroon, Iran, in 2006, the ME. degree
vol. 47, no. 4, pp. 1741–1748, July 2011. from the Indian Institute of Science (IISc) Banga-
[13] A. Hava and E. Un, “Performance analysis of reduced common-mode lore, India in 2010. He is currently a PhD. student at
voltage PWM methods and comparison with standard PWM methods the Indian Institute of Science Bangalore, India. His
for three-phase voltage-source inverters,” IEEE Trans. Power Electron., primary areas of interests are in power electronics,
vol. 24, no. 1, pp. 241–252, Jan. 2009. motor drives, active damping, common mode filters
[14] H. Akagi and T. Oe, “A specific filter for eliminating high-frequency and high-power converters.
leakage current from the grounded heat sink in a motor drive with an
active front end,” IEEE Trans. Power Electron., vol. 23, no. 2, pp. 763–
770, Mar. 2008.
[15] S.-J. Kim and S.-K. Sul, “A novel filter design for suppression of
high voltage gradient in voltage-fed PWM inverter,” in Applied Power
Electronics Conf. and Expo., vol. 1, Feb. 1997, pp. 122–127. Vinod John (S’92-M’00-SM’09) received the
[16] B. Acharya and V. John, “Design of output dv/dt filter for motor drives,” B.Tech. degree in electrical engineering from the
in Proc. of Industrial and Information Systems Conf., Mangalore, India, Indian Institute of Technology, Madras, India, the
Aug. 2010, pp. 562–567. M.S.E.E. degree from the University of Minnesota,
[17] T. Habetler, R. Naik, and T. Nondahl, “Design and implementation of an Minneapolis, and the PhD. degree from the Univer-
inverter output LC filter used for dv/dt reduction,” IEEE Trans. Power sity of WisconsinMadison, Madison. He has worked
Electron., vol. 17, no. 3, pp. 327–331, May 2002. in research and development positions at GE Global
[18] E. Zhong and T. Lipo, “Improvements in EMC performance of inverter- Research, Niskayuna, NY, and Northern Power, VT.
fed motor drives,” IEEE Trans. Ind. Appl., vol. 31, no. 6, pp. 1247–1256, He is currently working as an Assistant Professor
Nov.-Dec. 1995. with the Indian Institute of Science, Bangalore,
[19] M. Hedayati, A. Acharya B, and V. John, “Common mode filter design India. His primary areas of interests are in power
for PWM rectifier based motor drives,” IEEE Trans. Power Electron., electronics and distributed generation, power quality, high-power converters,
vol. 28, no. 11, pp. 5364–5371, 2013. and motor drives.

0093-9994 (c) 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See
http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like