Connecting S7-400H to PC Station (WinCC)
Contents
1 Automation problem...
2 Solution description ..
24 S7-400H woe - seven 8
22 S7-RedConnect. 4
224 Important notes on S7-RedConnect. 5
2.2.2 Two-path or Four-path Redundancy... 6
3 Configuration...
34 Configuring $7-400H 9
32 Configuring PC-station 15
33 Configuring fault-tolerant connections. 17
34 Setting the PGIPC-Interface of the WinCC-Station seme 20
35 Configuring WinCC-Station 22
4 Reference.
5 Contact, 25
6 Warranty and Support...
Evaluation / Feedbact
Rev. A- Entwurt 13.08.2002 226SIEMENS
Connecting S7-400H to PC Station (WinCC)
1 Automation problem
Connecting $7-400H to WinCC Station with S7-RedConnect has always
been a problem, not because the system is difficult to handle, but rather
due to lack of information provided on the manuals. This solution will show
you the necessary steps that you have to do in order to establish a fault-
tolerant connection between $7-400H and WinCC Station.
2 Solution description
This solution is valid for:
CPU ‘Order Number Hardware [Firmware |Hoptional | STEP 7 Vor-
version | Version _| package Ver- | sion’
sion
CPU 414-4H [6ES7 414-410-0880 [1 v2i2 [V5.4 V5.1 + SP
CPU4I7-4H _|6ES7417-4HL01-0AB0 [1 v2i2 [Vea 5A
CPU4IT-4H [6ES7417-4HLO0-0ABO [3 v2i2 |V54 V5.4
+) If STEP7 V5.1+SP2 is installed, then H optional package V5.1+SP2 must be used!
If you have H-CPU that is different from the above specification, then you
can still use this solution as your guide because the idea behind is the
same, but please make sure that you have the components (hardware and
software) that can be used for the version of H-CPU you used.
Before starting the commissioning you have to take-care of the following
24 ‘$7-400H
The following ethernet GPs (CP 443-1) can be used for fault-tolerant com-
munications:
(Order Number Hardware Version _| Firmware Version
OGKT 443-1EX02-0XE0 1 V5.2
6GKT 443-1EX10-0XE0 1 Vi1.04
6GK7 443-1X11-0XE0 1 Vi4.0
Please always refer to the product information of CPU 417-4H / CPU 414-
4H, because with the new firmware version of the H-CPU, some modules
must be upgraded
The product information should be considered as a separate document
and, in case of doubt, takes precedence over information contained in
manuals and catalogs.
Rev. A- Entwurt 13.08.2002 w26oh sowed
PrRNNINN-NIA
SIEMENS
Connecting S7-400H to PC Station (WinCC)
22
Please note that only /SO transport protocol can be used for fault-tolerant
communications.
In contrast to the description on the H manual, the Profibus network can not
be used for fault-tolerant communication between S7-400H and WinCC sta-
tion, because the latest version of S7-RedConnect V1.4 does not support
the Profibus CPs (CP 5613 and CP 5614).
For fault-tolerant communication between S7-400H and WinCC station, an
“$7 connection redundant’ must be configured in NetPro.
$7-RedConnect
In order to be able to use fault-tolerant connections between $7-400H and
PC (for example, WinCC), the “S7-RedConnect” software package is re-
quired on the PC.
The $7-RedConnect software package has the following characteristics:
+ Fault detection, switching over, monitoring of the communication and
synchronization are handled in the background invisible to the applica-
tion.
+ No additional programming required for PC and fault-tolerant system.
+ The application, for example WinCC, communicates with both parts of
the fault-tolerant system in the same way as with one S7-CPU
* $7-RedConnect provides the same S7 user interfaces (PG/OP func-
tions, $7 Communication) as other SIMATIC NET $7 software products
for PCs,
+ Existing Windows applications can continue to be used.
+ An application can monitor the status of the redundant connections us-
ing status queries.
+ The status of the connection can be displayed with the aid of the diag-
nostic tool.
* Configurable two-path and four-path redundancy
Rev. A- Entwurt 13.08.2002 W726SIEMENS
Connecting S7-400H to PC Station (WinCC)
224 Important notes on S7-RedConnect
‘S7-RedConnect Version Operating Network Card | Redundancy
System sup- | supported
ported
vis" 6GK1716-0HB13-3AA0 [NT 4.0 CP 1413 or GP | Only two-path
5412 (A2)
via 6GK1716-0HB14-3AA0 [NT4.00r [Only CP 1613 | Two-path or Four-
V1.4 Upgrade _| 6GK1716-0HB14-3AA4 2000 Pro path
4) Please also install the Service Pack 3 for S7-RedConnect V1.3
2) Four-path redundancy connections can only be configured with STEP 7 V5.1 + SP1 or
her
S7-RedConnect supports only $7 communication, since the fault-tolerant
connections are possible only using the $7 protocol. The transport protocol,
that can be used is /SO transport protocol or additionally Profibus in case of
V1.3.
‘The $7-RedConnect can be used along with other SIMATIC NET products
on the same CP.
Operating other protocols (for example, TCP/IP, Novell, etc., as used in of-
fice networks) on the same network card and on the same network can
lead to problems in fault-tolerant communication. It is therefore recom-
mended that you use a separate network card and a separate network.
Rev. A- Entwurt 13.08.2002 3126SIEMENS
Connecting S7-400H to PC Station (WinCC)
2.2.2 Two-path or Four-path Redundancy
‘Two-path Redundancy (Redundant bus)
Communication path 1
Communication path 2
SIMATIC PC station
cP 1|| cp2
1613 || 1613
SIMATIC H station
Rack 0 Rack 1 4
Icpu| cP 4 Icpu| cP 4 1
1
ai7 |443-4 ai7 1443-1 1
1
1
1
‘Two-path communication can, for example, be set up with the following
components:
* SIMATIC H station, two CPUs each with a CP
* Two networks
* PC station with two CPs
A fault-tolerant S7 connection therefore has two communication paths. The
failure of one component leads to an automatic failover to the other redun-
dant communication path.
Rev. A- Entwurt 13.08.2002 e126SIEMENS
Connecting S7-400H to PC Station (WinCC)
‘Two-path Redundancy (Single bus)
‘mmnnees Communication path 1
= Communication path 2
SIMATIC PC station
SIMATIC H station
Rack 0 Rack 1
cpu cP 4 cpu cpa
47 1443-1 47 |443-
Two-path communication can also be set up with a line topology (single bus, PC station
with one CP)
Rev. A- Entwurt 13.08.2002 7726SIEMENS
Connecting S7-400H to PC Station (WinCC)
Four-path Redundancy
= Communication path 4
SIMATIC PC station
== === Communication path 2
« Communication path 3 cp 1 |[cp2
++ Communication path 4 1613 || 1613
SIMATIC H station
Rack 0 Rack 4
cpu) [cr s|cp2| |cpu| cr 1)cp 2
417. 417] |443-4]
PrRNNINN-NIA
Fault-tolerant communication on four-paths with inereased redundaney can
be set up, for example, with the following components:
* SIMATIC H station, two CPUs each with two CPs
* Two networks
* PC station with two CPs
A fault-tolerant S7 connection therefore has four communication paths.
Now, for example, rack 0 can fail and network 2 can be down. Since four
paths are available, rack 1 and network 1 continue to function automati-
cally.
Rev. A- Entwurt 13.08.2002 26PrRNNINN-NIA
SIEMENS
Connecting S7-400H to PC Station (WinCC)
3 Configuration
The following steps show you how to configure a two-path redundancy sys-
tem as showed in page 6.
34 Configuring $7-400H
The following steps show you how to configure the hardware of the S7-
400H.
Procedure
4. Open SIMATIC Manager, and create a new project. Then insert a new H station: Insert >
Station > SIMATIC H Station
2. Open the hardware configuration (HWConfig) of the SIMATIC H Station(1) created (you can
change the name) by double-clicking the hardware object (or right-click the Open Object pop-
up menu command)
3. First place a mounting rack from the RACK-400 catalog. You can use one UR2-H rack or
alternatively two UR1 or two UR2 racks.
Rev. A- Entwurt 13.08.2002 O26