Professional Documents
Culture Documents
Installation Instructions: Warning
Installation Instructions: Warning
NOTES:
S Clearance to one of the other three 48 (1219)
30 (762) sides must be 36 inches (914mm).
12 (305)
S Clearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
36 (914) LINE SET
CONNECTIONS
FIGURE 1
7/2012 506945-01
Page 1
*2P72012* *P506945-01*
UNIT DIMENSIONS - INCHES (MM) IMPORTANT !
A This model is designed for use in check / expansion
valve systems only. An indoor expansion valve ap
proved for use with HFC-410A refrigerant must be or
dered separately and installed prior to operating the
system.
B
IMPORTANT !
Exhaust vents from dryers, water heaters and furnaces
should be directed away from the outdoor unit. Pro
longed exposure to exhaust gases and the chemicals
contained within them may cause condensation to
form on the steel cabinet and other metal components
SIDE of the outdoor unit. This will diminish unit performance
VIEW and longevity.
FIGURE 2
TABLE 1 PLACEMENT
UNIT DIMENSIONS
Model Numbers A B INSTALL UNIT AWAY
FROM WINDOWS
13ACX-018-230 24-1/4 (616) 25-1/4 (641)
13ACX-024-230 24-1/4 (616) 25-1/4 (641)
13ACX-030-230 24-1/4 (616) 29-1/4 (743)
13ACX-036-230 24-1/4 (616) 29-1/4 (743)
13ACX-042-230 28-1/4 (718) 29-1/4 (743)
13ACX-048-230 28-1/4 (718) 33-1/4 (845)
13ACX-060-230 28-1/4 (718) 29-1/4 (743)
WARNING FIGURE 3
To prevent personal injury, as well as damage to panels,
unit or structure, observe the following: SLAB MOUNTING
While installing or servicing this unit, carefully stow all
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees
removed panels so that the panels will not cause injury to (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
personnel, objects or nearby structures. Also, take care to BUILDING
DISCHARGE AIR
store panels where they will not be subject to damage STRUCTURE
NOTICE !
Roof Damage! MOUNTING
SLAB
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the GROUND LEVEL
rubber to degrade. Failure to follow this notice could
result in damage to roof surface. FIGURE 4
Page 2
LINE SET INSTALLATION
IMPORTANT — Refrigerant lines must not contact structure.
Line Set Isolation — The following illustrations are REFRIGERANT LINE SET — INSTALLING
examples of proper refrigerant line set isolation: VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE — Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
REFRIGERANT LINE SET — TRANSITION temperature of the liquid line or when pressure drop is equal to or greater
FROM VERTICAL TO HORIZONTAL than 20 psig.
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE AUTOMOTIVE IMPORTANT — Refrigerant lines must not contact wall
MUFFLER‐TYPE HANGER MUFFLER‐TYPE HANGER
OUTSIDE WALL LIQUID LINE
VAPOR LINE
STRAP
STRAP LIQUID LINE TO WOOD BLOCK
BETWEEN STUDS NON-CORROSIVE
VAPOR LINE METAL SLEEVE
WIRE TIE
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE WOOD BLOCK
VAPOR LINE - WRAPPED WIRE TIE
IN ARMAFLEX
STRAP
FLOOR JOIST OR
ROOF RAFTER
FIGURE 5
Page 3
13ACX SERIES
STEP 2 -- REFRIGERANT PIPING -- Flushing Existing Line Set and Indoor Coil
Flush the existing line set per the following
instructions. For more information, refer to the WARNING
Installation and Service Procedures manual available
Polyol ester (POE) oils used with HFC-410A
on DaveNet. CAUTION - DO NOT attempt to flush and refrigerant absorb moisture very quickly. It is very
re-use existing line sets or indoor coil when the system
important that the refrigerant system be kept closed as
contains contaminants (i.e., compressor burn out).
much as possible. DO NOT remove line set caps or
NOTE - When installing refrigerant lines longer than 50 feet, service valve stub caps until you are ready to make
refer to the Refrigerant Piping Design and Fabrication connections.
Guidelines manual available on DaveNet (Corp. 9351-L9),
or contact the Technical Support Department Product
Application group for assistance. IMPORTANT !
Some scroll compressors have an internal vacuum
IMPORTANT ! protector that will unload scrolls when suction pres
If this unit is being matched with an approved line set sure goes below 20 psig. A hissing sound will be
or indoor unit coil that was previously charged with heard when the compressor is running unloaded.
mineral oil, or if it is being matched with a coil which Protector will reset when low pressure in system is
was manufactured before January of 1999, the coil raised above 40 psig. DO NOT REPLACE COMPRES
and line set must be flushed prior to installation. Take SOR.
care to empty all existing traps. Polyol ester (POE)
oils are used in Lennox units charged with HFC-410A LIQUID LINE FILTER DRIER INSTALLATION
refrigerant. Residual mineral oil can act as an insula The filter drier (one is shipped with each 13ACX unit) must
tor, preventing proper heat transfer. It can also clog be field installed in the liquid line between the outdoor unit's
the expansion device and reduce system perfor
mance and capacity. liquid line service valve and the indoor coil's metering device
(fixed orifice or TXV) as illustrated in figure 6. This filter drier
Failure to properly flush the system per this instruc
tion and the detailed Installation and Service Proce must be installed to ensure a clean, moisture-free system.
dures manual will void the warranty. Failure to install the filter drier will void the warranty. A
replacement filter drier is available from Lennox. See
Brazing Connections page 7 for special procedures on
WARNING brazing filter drier connections to the liquid line.
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air Typical Liquid Line Filter Drier Installation
BRAZE CONNECTION POINTS
conditioning system, use a regulator that
can control the pressure down to 1 or 2 psig
(6.9 to 13.8 kPa).
WARNING
LIQUID LINE LIQUID
Refrigerant can be harmful if it is inhaled. Refrigerant SERVICE VALVE
LINE
LINE
must be used and recovered responsibly. LIQUID LINE
OUTDOOR
FILTER DRIER
UNIT
Failure to follow this warning may result in personal injury
or death. FIGURE 6
TABLE 2
REFRIGERANT LINE SET — INCHES (MM)
Valve Size Connections Recommended Line Sets
Model Number (-xx*)
Liquid Line Suction Line L15 Line Set Model Line Set Length Catalog Number
L15-26-20 20 feet (6.1 m) 89J52
13ACX-018-230 L15-26-25 25 feet (9.1 m) 89J53
3/8” (10 mm) 5/8“ (16 mm)
13ACX-024-230 L15-26-35 35 feet (12.2 m) 89J54
L15-26-50 50 feet (15.2 m) 89J55
L15-41-20 20 feet (6.1 m) 89J56
13ACX-030-230 L15-41-30 30 feet (9.1 m) 89J57
13ACX-036-230 3/8” (10 mm) 3/4” (19 mm)
13ACX-042-230 L15-41-40 40 feet (12.2 m) 89J58
L15-41-50 50 feet (15.2 m) 89J59
L15-65-30 30 feet (9.1 m) 89J60
13ACX-048-230 L15-65-40 40 feet (12.2 m) 89J61
3/8” (10 mm) 7/8” (22 mm)
13ACX-060-230
L15-65-50 50 feet (15.2 m) 89J62
* Applicable to all minor revision numbers unless otherwise specified.
** Some applications may required a field-provided 1-1/8” to 7/8” adapter.
Page 4
STEP 2 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device
1A
TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE
(UNCASED COIL SHOWN)
OR
1B TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)
BRASS NUT
TEFLON®
RING SENSING
LINE
DISTRIBUTOR
ASSEMBLY DISTRIBUTOR EQUALIZER
ASSEMBLY LINE
REMOVE AND DISCARD
WHITE TEFLON® SEAL
(IF PRESENT) LIQUID LINE ASSEMBLY
(INCLUDES STRAINER) LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A On fully cased coils, remove the coil access and plumbing panels.
B Remove any shipping clamps from the liquid line and distributor as
sembly. MALE EQUALIZER
C Using two wrenches, disconnect liquid line from liquid line orifice hous LINE FITTING VAPOR
ing. Take care not to twist or damage distributor tubes during this pro LINE LIQUID
SENSING BULB LINE
cess.
D Remove and discard fixed orifice, valve stem assembly (if present) A On fully cased coils, remove the coil access and plumbing panels.
and Teflon® washer as illustrated above.
B Remove any shipping clamps from the liquid line and distributor
E Use a field-provided fitting to temporarily reconnect the liquid line to the assembly.
indoor unit's liquid line orifice housing.
C Disconnect the equalizer line from the expansion valve equalizer
line fitting on the vapor line.
F
Remove the vapor line sensing bulb.
Disconnect the liquid line from the expansion valve at the liquid line
assembly.
Disconnect the expansion valve from the liquid line orifice housing.
CLEAN HCFC-22 TO BE MANIFOLD
USED FOR FLUSHING Take care not to twist or damage distributor tubes during this
(Positioned to deliver liquid process.
A refrigerant) G Remove and discard expansion valve and the two Teflon® rings.
1 LOW HIGH
H Use a field-provided fitting to temporarily reconnect the liquid line
VAPOR LINE NEW to the indoor unit's liquid line orifice housing.
SERVICE VALVE OUTDOOR
UNIT
EXISTING
INDOOR
UNIT B
OPENED CLOSED
3 FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
amount of clean refrigerant that previously charged the system. Check
the charge in the flushing cylinder before proceeding.
LIQUID LINE SERVICE
VALVE A Set the recovery machine for liquid recovery and start the
RECOVERY recovery machine. Open the gauge set valves to allow the
CYLINDER TANK recovery machine to pull a vacuum on the existing system line
RETURN Band indoor unit coil.
set
C
VAPOR
LIQUID
FIGURE 7
Page 5
13ACX SERIES
STEP 2 -- REFRIGERANT PIPING -- Brazing Procedures
3 ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
A Connect gauge set low pressure side to
liquid line service valve (service port). USE REGULATOR TO FLOW
LOW HIGH NITROGEN AT 1 TO 2 PSIG.
B Connect gauge set center port to bottle of
nitrogen with regulator.
C Remove core from valve in suction / vapor
line service port to allow nitrogen to escape. ATTACH
GAUGES
INDOOR OUTDOOR
UNIT UNIT
NITROGEN
LIQUID LINE LIQUID LINE SERVICE
VALVE
A WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
FIGURE 8
CAUTION WARNING
Brazing alloys and flux contain materials which are
hazardous to your health. Danger of fire. Bleeding the refrigerant
Avoid breathing vapors or fumes from brazing operations. charge from only the high side may result
Perform operations only in well-ventilated areas. in pressurization of the low side shell and
Wear gloves and protective goggles or face shield to suction tubing. Application of a brazing
torch to a pressurized system may result in
protect against burns.
ignition of the refrigerant and oil mixture.
Wash hands with soap and water after handling brazing Check the high and low pressures before
alloys and flux. applying heat.
Page 6
4 WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
additional water-saturated cloths underneath the valve body to protect the base paint.
5 FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
WARNING
SUCTION / VAPOR LINE
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE SERVICE VALVE
may result if you do not wrap a water-saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and WHEN BRAZING LINE SET TO
indoor coil have been leak-tested and evacuated. Refer SERVICE VALVES, POINT FLAME
to Installation and Service Procedures manual found on AWAY FROM SERVICE VALVE.
DAVENET.
FIGURE 9
Page 7
13ACX SERIES
STEP 2 -- REFRIGERANT PIPING -- Installing Indoor Expansion Valve
This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or
expansion valve metering device (purchased separately) at the indoor coil. See the 13ACX Product Specifications bulletin
(EHB) for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the
indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a
manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during
installation of expansion valve unit. After installation of the indoor coil metering device, proceed to Step 5.
LIQUID LINE
ASSEMBLY WITH
BRASS NUT SENSING BULB INSTALLATION
A Attach the vapor line sensing bulb in the proper orienta
tion as illustrated below using the clamp and screws
MALE EQUALIZER LINE provided.
VAPOR
FITTING (SEE LINE B NOTE - Though it is preferred to have the sensing bulb
EQUALIZER LINE installed on a horizontal run of the vapor line, installation
INSTALLATION FOR on a vertical run of piping is acceptable if necessary.
DETAILS)
NOTE — Confirm proper thermal contact between vapor line 1/8 Turn
Sensing bulb insulation is required if and expansion bulb before insulating the sensing bulb.
expansion valve is installed external to the
coil casing. See sensing bulb installation for
LIQUID LINE C Connect the equalizer line from the expansion valve to 11 12 1
the equalizer vapor port on the vapor line. Finger tighten 10 2
bulb positioning.
the flare nut, then tighten an additional 1/8 turn (7 ft-lbs) 9 3
as illustrated to the right. 8 4
7 6 5
VAPOR LINE
NOTE — NEVER MOUNT THE SENSING
BULB ON BOTTOM OF LINE.
FIGURE 10
Page 8
STEP 3 -- LEAK TEST AND EVACUATION
LEAK TEST
LOW HIGH
B A
TO VAPOR
SERVICE VALVE
(ANGLE OR BALL
TYPE)
1
CONNECT GAUGE SET
A Connect the high pressure hose of an HFC-410A manifold gauge set to the vapor valve service port.
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set.
NOTE — Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
2 After the line set has been connected to the indoor and outdoor units, check the line set connections and
indoor unit for leaks. Use the following procedure to test for leaks:
A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the
manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).
B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in
a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three
pounds (31 kPa) pressure.] Close the valve on the HFC-410A cylinder and the valve on the high
pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold gauge
set.
D Adjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set
in order to pressurize the line set and the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
F After leak testing, disconnect gauges from service ports.
FIGURE 11
Page 9
13ACX SERIES
STEP 3 -- LEAK TEST AND EVACUATION (CONTINUED)
EVACUATION
3
A
CONNECT GAUGE SET
NOTE — Remove cores from service valves (if not already done).
Connect low side of manifold gauge set with
LOW HIGH
TO LIQUID LINE
HFC-410A
B SERVICE VALVE
VACUUM PUMP
RECOMMEND
MINIMUM 3/8” HOSE
D
FIGURE 12
Page 10
STEP 4 -- ELECTRICAL -- Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes and
the current National Electric Code (NEC). In Canada, wiring
IMPORTANT !
must conform with current local codes and the current If unit is equipped with a crankcase heater, it should
Canadian Electrical Code (CEC). be energized 24 hours before unit start-up to prevent
Refer to the furnace or air handler installation instructions for compressor damage as a result of slugging.
additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
CAUTION
Use the transformer provided with the furnace or air handler Electrostatic discharge can affect
for low‐voltage control power (24VAC - 40 VA minimum) electronic components. Take care during
unit installation and service to protect the
WARNING ELECTROSTATIC
unit's electronic controls. Precautions will
DISCHARGE help to avoid control exposure to
Electric Shock Hazard. Can cause injury or
(ESD) electrostatic discharge by putting the unit,
death. Unit must be grounded in Precautions and the control and the technician at the same
accordance with national and local codes. Procedures
electrostatic potential. Touch hand and all
Line voltage is present at all components
tools on an unpainted unit surface before
when unit is not in operation on units with
performing any service procedure to
single‐pole contactors. Disconnect all
neutralize electrostatic charge.
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
SERVICE
DISCONNECT
SWITCH
5 FEET
(1.5M)
FIGURE 13
Page 11
13ACX SERIES
STEP 4 -- ELECTRICAL (CONTINUED) -- High Voltage and Field Control Wiring
The following illustration provide an example of control wiring connections when using standard thermostat.
FIGURE 14
STEP 5 -- UNIT START-UP 8. Recheck voltage while the unit is running. Power must
be within range shown on the unit nameplate.
IMPORTANT 9. Check system for sufficient refrigerate using the
procedures outlined in under System Refrigerant.
If unit is equipped with a crankcase heater, it should be OPERATING MANIFOLD GAUGE SET AND SERVICE
energized 24 hours before unit start-up to prevent VALVES
compressor damage as a result of slugging. The liquid and vapor line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
1. Rotate fan to check for binding. checking charge and charging.
2. Inspect all factory- and field-installed wiring for loose Each valve is equipped with a service port which has a
connections. factory-installed valve stem. Figure 15 provides information
3. After evacuation is complete, open the liquid line and on how to access and operating both angle and ball service
suction line service valve stems to release the valves.
refrigerant charge (contained in outdoor unit) into the Torque Requirements
system.
When servicing or repairing heating, ventilating, and air
4. Replace the stem caps and tighten to the value listed in conditioning components, ensure the fasteners are
table 3. appropriately tightened. Table 3 lists torque values for
5. Check voltage supply at the disconnect switch. The fasteners.
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted with the power company and the voltage
IMPORTANT
condition has been corrected. To prevent stripping of the various caps used, the
6. Connect manifold gauge set for testing and charging appropriately sized wrench should be used and fitted
using figure NO TAG as a guideline. snugly over the cap before tightening.
7. Set the thermostat for a cooling demand. Turn on power When servicing or repairing HVAC components, ensure the
to the indoor indoor unit and close the outdoor unit fasteners are appropriately tightened. Table 3 provides
disconnect switch to start the unit. torque values for fasteners.
Page 12
TABLE 3. TORQUE REQUIREMENTS gauge set that features low loss anti-blow back fittings.
Parts Recommended Torque Manifold gauge set used with HFC-410A refrigerant
Service valve cap 8 ft.- lb. 11 NM systems must be capable of handling the higher system
Sheet metal screws 16 in.- lb. 2 NM operating pressures. The gauges should be rated for use
with pressures of 0 - 800 psig on the high side and a low side
Machine screws #10 28 in.- lb. 3 NM of 30” vacuum to 250 psig with dampened speed to 500 psi.
Compressor bolts 90 in.- lb. 10 NM Gauge hoses must be rated for use at up to 800 psig of
pressure with a 4000 psig burst rating.
Gauge port seal cap 8 ft.- lb. 11 NM
Using Manifold Gauge Set
When checking the system charge, only use a manifold
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back
the stem out counterclockwise as far as it will go.
TO OUTDOOR UNIT
ANGLE-TYPE SERVICE VALVE
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is When service valve is CLOSED, the service port is open
open to line set, indoor and outdoor unit. to the line set and indoor unit.
11 12
torque cap per table 3.
1
S Without torque wrench: Finger tighten and 10 2
TO OPEN ROTATE STEM
BALL (SHOWN use an appropriately sized wrench to turn 9 3
COUNTERCLOCKWISE 90°.
CLOSED) an additional 1/6 turn clockwise. 8 4
VALVE 7 6 5
TO CLOSE ROTATE STEM
CLOCKWISE 90°.
STEM Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the
SERVICE PORT primary seal. Replace the stem cap and tighten as follows:
1/12 TURN
SERVICE PORT
CORE
S With Torque Wrench: Finger tighten and
11 12 1
then torque cap per table 3.
SERVICE PORT
CAP S Without Torque Wrench: Finger tight 10 2
en and use an appropriately sized 9 3
TO OUTDOOR STEM CAP wrench to turn an additional 1/12 turn 8 4
UNIT clockwise. 7 6 5
NOTE — A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
FIGURE 15
Page 13
13ACX SERIES
CHECKING AND ADDING SYSTEM IMPORTANT !
REFRIGERANT Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
The 13ACX unit is factory-charged with enough HFC-410A outdoor unit by treated water. Prolonged exposure of
refrigerant to accommodate a 15-foot length of refrigerant the unit to treated water (i.e., sprinkler systems, soak
piping. Charge should be checked and adjusted using the ers, waste water, etc.) will corrode the surface of steel
tables provided on the charging procedure sticker located on and aluminum parts, diminish performance and af
the unit access panel. Detailed information is provided in the fect longevity of the unit.
13ACX Installation and Service Procedures manual
(Corp0625-L5), which is available on DaveNet. Routine Maintenance
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
Homeowners Information prevent your unit from operating at its most efficient level.
NOTE — The filter and all access panels must be in place
any time the unit is in operation. If you are unsure about the
CAUTION filter required for your system, call your Lennox dealer for
assistance.
Before attempting to perform any service or mainte 1. Ask your Lennox dealer to show you where your indoor
nance, turn the electrical power to unit OFF at discon unit's filter is located. It will be either at the indoor unit
nect switch. (installed internal or external to the cabinet) or behind a
return air grille in the wall or ceiling. Check the filter
Cleaning of the outdoor unit's coil should be performed by a monthly and clean or replace it as needed.
licensed professional service technician (or equivalent). 2. Disposable filters should be replaced with a filter of the
Contact your dealer and set up a schedule (preferably twice same type and size.
a year, but at least once a year) to inspect and service your 3. The indoor evaporator coil is equipped with a drain pan
outdoor unit. The following maintenance may be performed to collect condensate formed as your system removes
by the homeowner. humidity from the inside air. Have your dealer show you
Outdoor Coil the location of the drain line and how to check for
obstructions. (This would also apply to an auxiliary
The outdoor unit must be properly maintained to ensure its drain, if installed.)
proper operation.
Thermostat Operation
S Please contact your dealer to schedule proper inspection See the ComfortSense® 7000 thermostat homeowner
and maintenance for your equipment. manual for instructions on how to operate your thermostat.
Preservice Check
S Make sure no obstructions restrict airflow to the outdoor
If your system fails to operate, check the following before
unit.
calling for service:
S Grass clippings, leaves, or shrubs crowding the unit can S Verify room thermostat settings are correct.
cause the unit to work harder and use more energy. S Verify that all electrical disconnect switches are ON.
S Keep shrubbery trimmed away from the unit and S Check for any blown fuses or tripped circuit breakers.
periodically check for debris which collects around the S Verify unit access panels are in place.
unit. S Verify air filter is clean.
S Keep snow level below the louvered panels to ensure S If service is needed, locate and write down the unit
proper performance. model number and have it handy before calling.
Page 14
13ACX Start-Up and Performance Checklist
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type:
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required
subcooling and approach temperatures.)
Subcooling: A — B = SUBCOOLING
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach: A — B = APPROACH
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F) A — B = COIL TEMP DROP
Return Air Temperature (A)
minus Supply Air Temperature (B)
Page 15
13ACX SERIES