Professional Documents
Culture Documents
User Manual 2
GESPSINAF: Active Harmonic Filter
SAFETY PRECAUTIONS
Follow the warnings described in this manual with the symbols shown below.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a specific point.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well
as damage to the unit. In particular, handling with voltages applied may result in
electric shock, which may cause death or serious injury to personnel. Defective
installation or maintenance may also lead to the risk of fire.
Carefully read this manual before connecting the unit. Follow all installation and
maintenance instructions throughout the unit's operating life. Pay special
attention to the installation standards of the National Electrical Code.
DISCLAIMER
INTERNATIONAL CAPACITORS, on its web site, supplies its customers with the
latest versions of the device specificactions and the most updated manuals.
User Manual 3
GESPSINAF: Active Harmonic Filter
Content
SAFETY PRECAUTIONS…………………………………………………………......3
User Manual 5
GESPSINAF: Active Harmonic Filter
• Make sure that the unit has not been damaged during transport.
• Check that the unit received matches that described in your order
and that its electrical features are suitable for the mains where it is
to be connected.
• Make sure that it is equipped with the following accessories:
- Main switch handle.
- 2 keys for locking the door.
- Manual.
• Check the shipping documentation. The dispatch note number must
coincide with the number marked on the outer part of the unit. Unload
and transport the unit following the instructions in section 1.2.-
TRANSPORT AND HANDLING
Inspect the unit externally and internally before connecting.
• Check that all the unit's items on the packing list are present.
User Manual 6
GESPSINAF: Active Harmonic Filter
The transport, loading and unloading and handling of the unit must
be carried out with proper precautions and using the proper manual
or mechanical tools to prevent damage to the unit.
If the unit is not to be immediately installed, it must be stored at a
location with a firm and level floor, and the storage conditions listed in
the section must be observed. 1.3.- STORAGE
In such a case, the unit should be kept in its original protective
packaging.
To move the unit a short distance, the unit's floor support profiles facilitate
handling with a pallet jack or forklift. (Figure 2).
When unloading and moving the unit, use a forklift with forks long enough to
support the entire length of the base. Otherwise, the forks should be long enough
to support at least ¾ of said depth. The forks must be flat and supported firmly by
the base. The cabinet must be raised by placing the forks underneath the profile
that supports the unit. (Figure 3).
User Manual 7
GESPSINAF: Active Harmonic Filter
1.3.- STORAGE
User Manual 8
GESPSINAF: Active Harmonic Filter
Harmonic phase current 50 A (RMS) 100 A (RMS) 150 A (RMS) 200 A (RMS)
Harmonic neutral current 150 A (RMS) 300 A (RMS) 450 A (RMS) 600 A (RMS)
Harmonic peak current 100 A (PEAK) 200 A (PEAK) 300 A (PEAK) 400 A (PEAK)
User Manual 9
GESPSINAF: Active Harmonic Filter
DISPLAY
LOCK
MAIN SWITCH
VENTILATION GRILLES
User Manual 10
GESPSINAF: Active Harmonic Filter
User Manual 11
GESPSINAF: Active Harmonic Filter
Make sure the unit is properly earthed before powering up. Any
fault in the earth connection might cause a risk of electrocution to
the user and damage to the unit itself in the case of lightning or
other transients.
User Manual 12
GESPSINAF: Active Harmonic Filter
Never power or start up the active filter with the front door open or
the side or rear covers removed.
Check that there is a neutral in the place where three-phase active filter
connections are made with neutral.
The active filter must be of the correct size for the harmonic currents it has to
filter and for the installation's electrical features.
The unit must be installed in an environment where the temperature outside the
cabinet is between 0ºC and 40ºC, with a maximum humidity of 90% without
condensation.
Do not install the unit close to a hot spot and keep it out of direct sunlight.
Ventilation spaces must be left on the side and rear to allow for the use of fans.
There must also be sufficient space at the front of the cabinet to be able to open
the door if necessary (Figure 6):
200 mm on the sides of the cabinet.
200 mm between the top of the cabinet and the ceiling.
800 mm at the front of the cabinet.
User Manual 13
GESPSINAF: Active Harmonic Filter
ACTIVE
FILTER
ACTIVE
FILTER
If the unit is not installed after receipt, the following recommendations must be
observed to keep the unit in a good state:
Keep the unit in a dry atmosphere and at a temperature of between 0ºC
and 50ºC.
Avoid exposure to direct sunlight.
Keep the unit in its original packaging.
If the active filter is stored for a long time disconnected from the mains, a
process must be applied to restore the internal dielectric layers of the DC bus
capacitors. Table 2 shows the recommendations for starting the unit depending
on the length of its storage period.
User Manual 14
GESPSINAF: Active Harmonic Filter
The purchased active filter must be sized for the harmonic currents it has to filter.
The nominal current of the GESPSINAF must be at least 20% higher than the
maximum level of harmonics to be filtered. This factor may be higher depending on
the installation features.
The active filters can suffer from overloading when trying to cancel the harmonic
currents in high-impedance, short-circuit mains. The clearest symptom for
detecting such cases is that they originally start from a THD(V) (under voltage) of
over 3%. It has been seen that the higher the initial THD(V), the greater the
chance of filter overload.
The reason for this behaviour is that the load does not behave as a current
source, but rather the larger the harmonic current absorbed by the filter the more
harmonics are produced by the load, which can produce up to more than double
what was initially measured.
To avoid this phenomenon, it is best to oversize the active filter by multiplying the
initial current of harmonics measured in the load by a safety factor (SFh). In
other words:
To calculate this safety factor you must first know the parameter called short-
circuit ratio RSC at the connection point of the PCL transducers (not on the
installation input). The short-circuit ratio is defined as the ratio between the short-
circuit current of a mains (ISC) and the nominal current of the set of non-linear
transducers (INLC) producing the harmonics to be filtered. (Equation 2)
User Manual 15
GESPSINAF: Active Harmonic Filter
I SC
R =
SC
I CNL
Equation 2: Calculating the short-circuit ratio RSC.
In a real installation, the short-circuit current (ISC) in the PCL can be assessed by
having the voltage at the said point for two different load currents. For example,
full load, IA and 10% load, IB. If VOC is the rated voltage in a vacuum, the ISC, can
be calculated using the formula shown in Figure 9.
User Manual 16
GESPSINAF: Active Harmonic Filter
3.5.- CONNECTIONS
All power and current reading cables must enter the electrical
cabinet by the cover on the bottom, guaranteeing the IP
and the user protection against the parts of the cabinet with
high voltages
Perform the drilling and/or milling out of the area for this
(Figura 15) puts at risk the integrity of the equipment and
users, as well as the loss of the warranty.
User Manual 17
GESPSINAF: Active Harmonic Filter
The connections of the three-phase mains to neutral (L1, L2, L3, N and Earth)
are identified in the active filter as in Figure 12.
The minimum cable cross-section will depend on the filter range (Table 3).
GESPSINAF 50A 100A 150A 200A
Cross-section
2 16 35 70 95
(mm )
a ≤ 10 a ≤ 10 a ≤ 10 a ≤ 10
L1 b ≤ 20 b ≤ 20 b ≤ 20 b ≤ 20
Terminal (mm)
L2 c ≤ 21 c ≤ 21 c ≤ 21 c ≤ 21
L3 Ø>8 Ø>8 Ø>8 Ø>8
Torque (Nm) 7.6 7.6 14.4 14.4
Cross-section
2 50 95 2x95 2x95
N (mm )
Terminal (mm) Ø > 10 Ø > 10 Ø > 10 Ø > 10
Torque (Nm) 20 25 30 30
Cross-section
2 50 95 95 95
Earth (mm )
Terminal (mm) Ø>8 Ø > 10 Ø > 10 Ø > 10
Torque (Nm) 20 25 30 30
User Manual 18
GESPSINAF: Active Harmonic Filter
Current transformers TI1, TI2 and TI3, are located on the load side (downstream
of the filter) and are used for measurement and control purposes. In the active
filter, connections S1/L1, S1/L2, S1/L3 S2/L1, S2/L2, S2/L3 have to be made as
shown in (Figure 13).
The use of class 0.2, 0.5s or 0.5 transformers will slightly jeopardise the
behaviour of the active filter although they always provide acceptable harmonic
filtering replies.
User Manual 19
GESPSINAF: Active Harmonic Filter
You can connect up to 8 active filters by connecting the three phases plus the
neutral in parallel. The load current measurement connects in series so that all of
the filters are using the same measuring transformers on the load. (Figure 14).
Section 4.3.4. explains how to configure the active filter to work with several
active filters in parallel.
User Manual 20
GESPSINAF: Active Harmonic Filter
Once the connections specified in the above sections have been checked, the
main switch of the active filter will be switched on. When the unit is started, the
messages “NO CONNECTION” must appear on the display (Figure 13).
Pressing the button Start will make that Active filter starts to operate. If stop
button is pressed active filter will stop working.
Another message may appear if there is some problem in the filter connections
or the power supply. The section APPENDIX A: DISPLAY MESSAGES of this
manual describes all of the causes of malfunction and their corrective measures.
User Manual 21
GESPSINAF: Active Harmonic Filter
3.9.1- CONFIGURATION
Figure 15: Configuration of the transformer ratio and the number of modules in parallel.
Configure the TRANSFORMER RATIO parameter with the ratio between the
primary and secondary of the load current measurement transformer.
GESPSINAF admits the following transformation ratios: 5/5, 10/5, 15/5, 20/5, 25/5,
30/5, 40/5, 50/5, 60/5, 75/5, 100/5, 125/5, 150/5, 200/5, 250/5, 300/5,
400/5, 500/5, 600/5, 700/5, 750/5, 800/5, 1000/5, 1200/5, 1500/5, 1600/5,
2000/5, 2500/5, 3000/5, 4000/5 and 5000/5.
User Manual 22
GESPSINAF: Active Harmonic Filter
User Manual 23
GESPSINAF: Active Harmonic Filter
3.9.2- UNIT VERIFICATION
The load power screen (Figure 19) can be accessed from the home screen by
pressing VIEW:
Figure 19: Verify active and reactive power and load power factor readings.
Make sure the active power measurement of the load equals the power
User Manual 24
GESPSINAF: Active Harmonic Filter
levels of the installation.
Make sure the reactive power measurement of the mains equals the
reactive power levels of the installation.
Check the power factor in the three phases. If there are phases with very
high reactive power and very low active power levels, this might indicate
an error in the phase order. In this case, check the connections of the
three-phase mains power supply cables with neutral and the load current
reading cables, as described in sections 3.5.1 and 3.5.2.
Having checked the active and reactive power and power factor of the
installation, you can return to the main screen to start up the GESPSINAF.
If there is no problem with the connections, the home screen should show the
message “STOP” (Figure 20).
Figure 20: Message displayed when the unit is ready for start-up.
By pressing START, the active filter will take action to neutralise the harmonics,
balance the phases and/or compensate reactive power.
If there is any problem in the connections of the filter or in the configuration, the
“NOT INITIAL CONDITIONS” message will be shown.
The APPENDIX A: DISPLAY MESSAGES of this manual contains all of the causes
of malfunction and their corrective measures.
The RESET ALARM button rearms the unit if the cause of the alarm has
disappeared or been solved.
User Manual 25
GESPSINAF: Active Harmonic Filter
4.- OPERATION
4.1.1.- HARMONICS
Non-linear loads such as: rectifiers, inverters, speed drives, ovens, etc, absorb
periodic non sine-wave currents from the mains.
The result is a deformation of the current and, as a result, of the voltage, causing a
series of associated side effects. These can be machinery overload, electric
cable heating, circuit breaker disconnection, damage to sensitive units, etc.
Mains frequency
Order (n)
Fundamental: 50 Hz Fundamental: 60 Hz
3 150 Hz 180 Hz
5 250 Hz 300 Hz
7 350 Hz 420 Hz
Order of a harmonic (n): A whole number given by the ratio between the
frequency of a harmonic and the fundamental frequency. The order
determines the frequency of the harmonic (E.g.: 5th harmonic → 5•50 Hz =
250 Hz).
User Manual 26
GESPSINAF: Active Harmonic Filter
Individual distortion rate (Un% o In%): A ratio in % between the RMS value
of the voltage or harmonic current (Un o In) and the RMS value of the
fundamental component (U1 o I1).
True root mean square value (TRMS): The square root of the sum of the
squares of all components forming the wave.
Harmonic content: The difference between the total voltage or current and
the corresponding fundamental value.
Harmonic distortion rate (THD): The ratio between the RMS value of the
harmonic content of the voltage and/or current and the value of the
fundamental component.
User Manual 27
GESPSINAF: Active Harmonic Filter
Table 5 lists the most common harmonic generator loads and the wave shape of
the current they consume, as well as their harmonic spectrum.
- Discharge lamps
- Single-phase
transducers
- Lighting lines
- Computer lines
- Sound and image units
Active filters are units responsible for the compensation of harmonic currents.
Compensation is achieved by injecting harmonic currents equal to those in the
installation in counter phase.
This means that upstream of the filter connection point, the signal shows virtually no
harmonic distortion. (Figure 22).
User Manual 28
GESPSINAF: Active Harmonic Filter
In other words, they detect the difference between the required current sine
wave (IMAIN) and the signal deformed by the harmonics (ILOAD). And they inject
the difference between both waves (IFILTER).
Figure 24 show the wave shapes of the currents injected by the active
filters.
These show the required wave, the existing deformed wave and the filter current
(IFILTER).
Figure 23: Current in the load, in the filter and in the mains.
4.2.- DISPLAY
The active filter has a touch display with different screens used for display and
configuration purposes.
User Manual 29
GESPSINAF: Active Harmonic Filter
The main screen contains information regarding the filter status, the start and
stop controls, the alarm rearm process and the accesses to the configuration
and display variables.
User Manual 30
GESPSINAF: Active Harmonic Filter
On pressing VIEW in the home screen (Figure 24), you access the general
display (Figure 25), from where you can access all of the display screens.
• Voltage and current: this option gives us access to the voltage and
current display screen.
• Power: Access to the power display screen.
• THD I: Access to the display screen of the total harmonic distortion of the
load and mains current.
• LOG: Access to the alarm log display screen.
User Manual 31
GESPSINAF: Active Harmonic Filter
User Manual 32
GESPSINAF: Active Harmonic Filter
User Manual 33
GESPSINAF: Active Harmonic Filter
This screen (Figure 29) shows the active, reactive, apparent powers and the
power factor of the three load phases.
This screen (Figure 30) shows the active, reactive, apparent powers and the
power factor of the three mains phases.
User Manual 34
GESPSINAF: Active Harmonic Filter
This shows the instant power used in the three phases L1, L2, L3 of the active
filter as a percentage with respect to the programmed power limit (Figure 31).
User Manual 35
GESPSINAF: Active Harmonic Filter
This screen (Figure 33) will show the THD(I) of the phase 1 load.
This screen (Figure 34) will show the THD(I) of the phase 2 load.
User Manual 36
GESPSINAF: Active Harmonic Filter
4.2.2.4.3.- THD DISPLAY SCREEHN PHASE 3 LOAD CURRENT
This screen (Figure 35) will show the THD(I) of the phase 3 load.
This screen (Figure 36) will show the THD(I) of the phase 1 mains.
User Manual 37
GESPSINAF: Active Harmonic Filter
4.2.2.4.5.- THD DISPLAY SCREEN OF THE PHASE 2 MAINS CURRENT
This screen (Figure 37) will show the THD(I) of the phase 2 mains.
This screen (Figure 38) will show the THD(I) of the phase 3 mains.
User Manual 38
GESPSINAF: Active Harmonic Filter
4.2.2.4.7.-DISPLAY SCREEN OF THE TOTAL THD (I)
This screen (Figure 39) shows the reading of the total THD(I) of the mains and
load phases.
This screen (Figure 40) shows the log of events in the active filter, and indicates
the date and time when each event starts and ends.
User Manual 39
GESPSINAF: Active Harmonic Filter
4.3.- CONFIGURATION
Press SETUP on the GESPSINAF home screen to open the setup menu (Figure 41).
User Manual 40
GESPSINAF: Active Harmonic Filter
User Manual 41
GESPSINAF: Active Harmonic Filter
In this menu (Figure 43), users can access different screens to perform the
following:
User Manual 42
GESPSINAF: Active Harmonic Filter
Use this screen (Figure 44) to select the functions of the GESPSINAF:
Phase balancing +
Harmonic filtering
reactive compensation
Phase balancing +
-
Harmonic filtering
reactive compensation
User Manual 43
GESPSINAF: Active Harmonic Filter
User Manual 44
GESPSINAF: Active Harmonic Filter
Polarity alarm:
With the polarity alarm enabled, the active filter detects the direction of the load
measuring transformer current and if it detects inverse polarity (current towards
the mains) it returns to the initial conditions and restarts with the new conditions in
measuring the current. In the case of regenerative loads temporarily injecting
current into the mains, the polarity alarm will be activated.
With the polarity alarm disabled, if the load is injecting energy into the mains,
GESPSINAF will measure negative active power and will stop neutralising
harmonics, balancing phases and compensating reactive energy. It will only
adjust the bus to the operating voltage.
When the active power is positive again, it will reperform all of the filtering
functions.
Before starting the active filter with the polarity alarm disabled, check
the connection and polarity of the load measuring transformers.
User Manual 45
GESPSINAF: Active Harmonic Filter
This alarm is activated to prevent the unit from starting when the temperature
inside the active filter is below 0ºC or when there is a problem in the connections
of the temperature probes.
Resonance Alarm:
The resonance alarm protects the unit against possible resonating currents
between GESPSINAF and the load. This alarm is tripped when the level of a
harmonic in the load current rises considerably.
User Manual 46
GESPSINAF: Active Harmonic Filter
This menu (Figure 47) contains the parameters that have to be configured during
the installation of the active filter. To be modify these parameters, you have to
unlock the password (refer to 4.3.8.- PASSWORD) and have the filter in “STOP”
mode.
Minimum current:
The minimum load current to start the active filter. GESPSINAF will stop when the
load current is below the entered value and will start when it is higher.
Control algorithm:
Control algorithm selection:
1, Frequency mode: Harmonic filtering based on the selection of the
harmonics to be neutralised from the 3rd to the 25th. (Option enabled by
default.)
User Manual 47
GESPSINAF: Active Harmonic Filter
Do not use the Temporary mode (2) if the supplier has not
recommended this for their installation. This method can cause
resonance in certain installations.
Power limit
This parameter allows the maximum power of the active filter to be limited. The
value is configured as a percentage with respect to the unit's nominal power. The
minimum configurable value is 20%, and the maximum is 100%.
Access to the configuration screen of the number of active filters set out in
parallel with the same load (Figure 48).
All GESPSINAF must use the same load transformer. Refer to the
section 3.6.- PARALLEL CONNECTION OF 2 TO 8 ACTIVE FILTERS
to install more than one active filter in parallel.
User Manual 48
GESPSINAF: Active Harmonic Filter
CTs ratio:
CTs number:
CTs location:
Select the load side option for CTs installed in the load current (downstream from the
Active Filter), or main side for CTs installed in the mains current (upstream from the
Active Filter).
User Manual 49
GESPSINAF: Active Harmonic Filter
This screen (Figure 51) enables all of the screen parameters to be configured.
User Manual 50
GESPSINAF: Active Harmonic Filter
4.3.8.- PASSWORD
All configuration options of the active filter can be password protected. To lock or
unlock the configuration, press on the “LOCK/UNLOCK PARAMETERS” key on
the different screens (Figure 52)
User Manual 51
GESPSINAF: Active Harmonic Filter
The active filters have a RS-485 communications port with the MODBUS RTU
communications protocol.
The RS-485 communication cable is connected to the back of the display, as
shown in (Figure 54):
RS-485
connector
User Manual 52
GESPSINAF: Active Harmonic Filter
Variable Value
Protocol MODBUS RTU slave
Peripheral no. 2
Baud Rate 9600
Parity No
Data bits 8
Stop bits 1
Table 8: Modbus configuration.
User Manual 53
GESPSINAF: Active Harmonic Filter
Variable reading
• Question:
Peripheral Modbus Start CRC 16
No. logs
number function address (Modbus)
02 03 H L H L H L
• Response:
Peripheral Modbus No. bytes Data CRC 16
number function (2 x number of logs) (2 x number of logs) (Modbus)
02 03 1 Byte H L H L
Variable write
• Question:
No. bytes Data
Peripheral Modbus Start CRC 16
No. logs (2 x number of (2 x number
number function address (Modbus)
logs) of logs)
02 10 H L H L 1 Byte H L H L
• Response:
Peripheral Modbus Start CRC 16
No. logs
number function address (Modbus)
02 10 H L H L H L
In Appendix B: In Modbus Map you can see the memory map of the
parameters that can be viewed via RS-485.
4.4.2.- SOFTWARE
PowerStudio is an energy management software package and its main features are
the configuration, communication and monitoring of devices and creation of SCADA
screens and reports. It also has a set of tools such as events, filters, calculated
variables, and an images and styles manager to facilitate the user’s interaction.
The communication protocol between PowerStudio and active filter is Modbus RTU,
with RS-232 cable. The configuration parameters of the communication are shown in
below table.
User Manual 54
GESPSINAF: Active Harmonic Filter
The communications cable RS-232 plugs into the back of the panel, according to
the following scheme.
5.- MAINTENANCE
Table 10 shows the maintenance jobs with their respective time intervals.
Description Interval
Standard maintenance 5,000 to 9,000 hours
Cooling turbines 40,000 h
Cooling fans 100,000 h
DC bus capacitors 200,000 h
Table 11: Active filter maintenance.
Note: The time intervals of the maintenance operations can vary depending on the
unit's operating conditions and environmental factors.
User Manual 55
GESPSINAF: Active Harmonic Filter
When the panel battery is changed, the language, date and time of the unit have to
be reconfigured. (refer to 4.3.7.- SCREEN CONFIGURATION).
User Manual 56
GESPSINAF: Active Harmonic Filter
Table 11 gives the number of fans and/or turbines required to cool the inductors
and the semiconductors according to the active filter model.
The following symptoms in the behaviour of the filter can indicate wear in the
fans or turbines:
1.- Set the GESPSINAF to STOP mode and turn off the main switch (OFF position).
2.- Wait 5 minutes for the energy accumulated in the capacitors to discharge.
3.- Open GESPSINAF cabinet and disconnect the fan's power supply.
User Manual 57
GESPSINAF: Active Harmonic Filter
The power supply terminals are located in the lower left corner of the fan. Grasp
the terminal firmly and pull to disconnect it.
4.- Use a 3 mm Allen key to unscrew the 4 screws fixing the fan to the front
panel. (Figure 58)
5.- Replace the damaged fan, connecting the power supply terminals in the
bottom left corner.
User Manual 58
GESPSINAF: Active Harmonic Filter
6.- Use the 3 mm Allen key to fix the fan to the front panel. (Figure 59)
1.- Set GESPSINAF to STOP mode and turn off the main switch (OFF position).
2.- Wait 5 minutes for the energy accumulated in the capacitors to discharge.
3.- Remove the methacrylate protection in front of fans.
User Manual 59
GESPSINAF: Active Harmonic Filter
5.- Unscrew the compartment cover fasteners with a no. 20 Torx key and remove
the cover (Figure 62).
6.- Disconnect the power supply fans by firmly grasping the terminal and pulling
to disconnect it. (Figure 63)
7.-Take out the fan being changed using a socket spanner or 7 mm spanner to
hold the rear nut and a flat or Phillips screwdriver to loosen the screw.(Figure
64)
User Manual 60
GESPSINAF: Active Harmonic Filter
1.- Place the GESPSINAF in STOP mode and turn off the main switch (OFF
position).
2.- Wait 5 minutes for the energy accumulated in the capacitors to discharge.
3.-Remove the protection board and unfasten the front panel holding the
electronic boards. (Figure 65).
4.- Remove the right side cabinet cover UPPER FANS.
5.- Remove the extractor hood fasteners to be able to reach the top fans.(Figure 65)
6.- Lift the extractor hood, disconnect the power supply from the fans and
remove the hood. (Figure 66).
Figure 66: Disconnect the power supply from the fans and remove the hood.
8.- Replace the damaged fans. Fit the fan, leaving the power supply pins on the
side of the IGBTs
9.- Pass the power supply cable through the drill hole on the hood.
10.- Connect the power supply of the two fans.
11.- Screw back on the extractor hood fasteners.
LOWER FANS
12.- Remove the power supply cable from the bottom heatsink fans. (Figure 68)
User Manual 62
GESPSINAF: Active Harmonic Filter
13.- Reach into the fans from the side and remove the right fan fasteners. It is
best to follow the order of the steps shown in (Figure 69).
1 2 5
3
4
User Manual 63
GESPSINAF: Active Harmonic Filter
1.- Place the GESPSINAF in STOP mode and turn off the main switch
(OFF position).
2.- Wait 5 minutes for the energy accumulated in the capacitors to discharge.
3.- Remove the front panel protection board.
4.- Drop the front panel metal plate. (Figure 71)
5.- Remove the DC bus busbar. (Figur 71)
6.- Disconnect the earth wire from the front panel metal plate. (Figure 71)
7.- Remove the top crossbar. (Figure 71)
10.- Disconnect the IGBT connectors from the gate board. The top board must
first be removed to be able to disconnect the IGBTs from the bottom board.
11.- Disconnect the NTC connectors from the controller board
12.- Take the NTC probe cabling out of the channel.
13.-. Disconnect the turbine power supply.
The location of the power supply depends on the turbine model.
If the turbine is black, the power supply is on the front part (Figure 73).
If the turbine has a steel finish, the power supply is on the rear part
(Figure 74).
User Manual 65
GESPSINAF: Active Harmonic Filter
14.- Unscrew the extractor hood fasteners on the back metal plate (Figure 75).
15.- Remove the screws fastening the heatsink to the hood. (Figure 76)
Figure 76: Remove the screws fastening the heatsink to the hood.
User Manual 66
GESPSINAF: Active Harmonic Filter
16.- Unscrew the bottom fasteners from the pack formed by the heatsink body,
the turbine and the IGBT bridge while the whole pack is held (Figure 77).
17.- Move the pack towards the bottom until the heatsink comes out of the
extractor hood. (Figure 78).
18.- Tilt the pack towards the outside of the cabinet and remove it. (Figure 78).
19.- Place the pack on a flat, stable surface to unscrew the turbine fasteners.
(79).
User Manual 67
GESPSINAF: Active Harmonic Filter
User Manual 68
GESPSINAF: Active Harmonic Filter
The DC bus capacitors have a useful life of 200,000 hours (22 years). The
capacitor life depends on the operation of the active filter and the environmental
conditions and, especially, on the ambient temperature.
The active filter capacitors are maintenance-free, except when the unit is started up
after long storage (Refer to 3.3.- STORAGE FOR LONG PERIODS.)
The complete software update of the unit is divided into two parts:
1.- Controller software update.
2.- Display software update.
The material required for the full update is:
USB memory stick with the Vx.yz_ International Capacitors software (x.yz:
software version no.)
To check the current version of the software, access the filter data screen
(Section 4.3.6.- FILTER DATA).
User Manual 69
GESPSINAF: Active Harmonic Filter
Figure 80: Change the position of the jumpers (A) or micro switches (B).
5.- Connect the memory stick supplied by International Capacitors to port J12
next to the micro-switches or jumpers.
It should be connected with the fat side facing the battery. (Figure 81)
ELECTRICAL FEATURES
Rated voltage 400 V ± 15%
Mains frequency 50 Hz / 60 Hz - 4%
Connection 3 phases with neutral (4 wires)
FILTER SPECIFICATIONS
Harmonic compensation from the 2nd to the 50th harmonic
Specific harmonics selection from the 2nd to the 50th harmonic
Phase balancing Yes
Reactive current compensation Yes
Controller Digital, DSP
Response time < 1ms
Yes, when the nominal current of the filter is
Saturation protection
exceeded
User interface LCD Screen, 5.7” 320x240 pixel
ENVIRONMENTAL FEATURES
Operating temperature 0ºC to +50ºC
Relative humidity 0% to 90% (without condensation)
Maximum altitude < 2000 m
Storage temperature 0ºC to +50ºC
STANDARDS
Harmonic regulation EN61000-3-4, IEEE519-1992
Electrical specifications EN60146
Electrical safety EN50178
EN55011, EN50081-2, EN61000-4-2, EN61000-4-3,
Electromagnetic compatibility EN61000-4-4, EN61000-4-5, EN61000-4-6,
EN61000-6-2
User Manual 71
GESPSINAF: Active Harmonic Filter
In the case of any query in relation to unit operation or malfunction, please contact
INTERNATIONAL CAPACITOR Technical Support Service
Technical Assistance Service
C/Vallès,32- Polígono Industrial Can Bernades
08130 Santa Perpètua de Mogoda (Barcelona) SPAIN
Tel: (+34) 935 747 017 – Fax: (+34) 935 448 433
9.- GUARANTEE
User Manual 72
GESPSINAF: Active Harmonic Filter
The tables below show all of the messages that might appear on the main
screen, along with the description and the corresponding corrective action.
Table 12 shows the messages that might appear on the main screen before
GESPSINAF starts up.
Starting ...
Corrective Check the input voltage of the three phases of GESPSINAF and the
Action circuit breaker 1Q22.
User Manual 73
GESPSINAF: Active Harmonic Filter
Corrective Check the input voltage of the three phases of the GESPSINAF and
Action the circuit breaker 1Q22.
Synchronising
Corrective Check the input voltage and the connections if the message
Action remains on the screen.
Polarity Error
DC Bus imbalance
Corrective
Reduce the number of harmonics to be neutralised.
Action
NTC connector failure
The NTC temperature probe is disconnected or the temperature
Description
inside the unit is below 0ºC.
Make sure the NTC probe is connected to the controller board.
Corrective
If the temperature inside the cabinet is under 0ºC, do not start the
Action
unit.
Table 13: Not Initial Conditions messages.
User Manual 74
GESPSINAF: Active Harmonic Filter
Table 13 shows the messages that might appear on the main screen when
GESPSINAF is in an alarm status.
ALARM
NTC1 temperature
Corrective Make sure that the fans or turbines at the top of the cabinet are
Action operating properly.
NTC2 temperature
Corrective Make sure that the fans or turbines at the top of the cabinet are
Action operating properly.
Inductor Temperature
Corrective Ensure that the fans at the bottom of the cabinet are operating
Action properly.
MAX. DC bus voltage.
Corrective
Check the unit connections and the input voltages.
Action
MAX. Bus positive voltage
Corrective
Check the unit connections and the input voltages.
Action
MAX. Bus negative voltage
Corrective
Check the unit connections and the input voltages.
Action
MAX. Current
User Manual 75
GESPSINAF: Active Harmonic Filter
Corrective
Check the unit connections or reduce the harmonics to be filtered.
Action
MAX. Mains voltage
Corrective
Check GESPSINAF input voltage levels.
Action
Desaturation
Corrective
Check the initial conditions and the configuration.
Action
Resonance Alarm
Description The DC bus voltage is not sufficient for the proper unit operation.
Corrective
Check the connections of the controller boards.
Action
Table 14: Alarm messages.
The RESET ALARM button of the main screen rearms the unit if the cause of
the alarm has disappeared or been solved.
User Manual 76
GESPSINAF: Active Harmonic Filter
Table 14 shows the messages that might appear on the main screen when the
GESPSINAF is operating.
START
Description The load harmonics are higher than the filter nominal current.
GESPSINAF is operating properly but working in saturation. The number
Corrective
of harmonics to be filtered or the unit power should be reduced. Check
Action
section 4.3.- CONFIGURATION.
Table 15 shows the messages that might appear on the main screen when the
GESPSINAF is in configuration status.
CONFIGURATION
Complete configuration
User Manual 77
GESPSINAF: Active Harmonic Filter
User Manual 78
GESPSINAF: Active Harmonic Filter
User Manual 79
GESPSINAF: Active Harmonic Filter
User Manual 80
GESPSINAF: Active Harmonic Filter
User Manual 81
GESPSINAF: Active Harmonic Filter
Name
Mains current harmonics L1
Name Type Function Address (Hexadecimal)
1st Mains current harmonic L1 Word R 003C
3rd Mains current harmonic L1 Word R 003D
5th Mains current harmonic L1 Word R 003E
7th Mains current harmonic L1 Word R 003F
9th Mains current harmonic L1 Word R 0040
11th Mains current harmonic L1 Word R 0041
13th Mains current harmonic L1 Word R 0042
15th Mains current harmonic L1 Word R 0043
17th Mains current harmonic L1 Word R 0044
19th Mains current harmonic L1 Word R 0045
21st Mains current harmonic L1 Word R 0046
23rd Mains current harmonic L1 Word R 0047
25th Mains current harmonic L1 Word R 0048
Response 1st harmonic response in % without decimals.
Name
Mains current harmonics L2
Name Type Function Address (Hexadecimal)
1st Mains current harmonic L2 Word R 0050
3rd Mains current harmonic L2 Word R 0051
5th Mains current harmonic L2 Word R 0052
7th Mains current harmonic L2 Word R 0053
9th Mains current harmonic L2 Word R 0054
11th Mains current harmonic L2 Word R 0055
13th Mains current harmonic L2 Word R 0056
15th Mains current harmonic L2 Word R 0057
17th Mains current harmonic L2 Word R 0058
19th Mains current harmonic L2 Word R 0059
21st Mains current harmonic L2 Word R 005A
94
User Manual
GESPSINAF: Active Harmonic Filter
Name
Mains current harmonics L3
Name Type Function Address (Hexadecimal)
1st Mains current harmonic L3 Word R 0065
3rd Mains current harmonic L3 Word R 0066
5th Mains current harmonic L3 Word R 0067
7th Mains current harmonic L3 Word R 0068
9th Mains current harmonic L3 Word R 0069
11th Mains current harmonic L3 Word R 006A
13th Mains current harmonic L3 Word R 006B
15th Mains current harmonic L3 Word R 006C
17th Mains current harmonic L3 Word R 006D
19th Mains current harmonic L3 Word R 006E
21st Mains current harmonic L3 Word R 006F
23rd Mains current harmonic L3 Word R 0070
25th Mains current harmonic L3 Word R 0071
Response 1st harmonic response in % without decimals.
Name
Load current harmonics L1
Name Type Function Address (Hexadecimal)
1st Load current harmonic L1 Word R 0078
3rd Load current harmonic L1 Word R 0079
5th Load current harmonic L1 Word R 007A
7th Load current harmonic L1 Word R 007B
9th Load current harmonic L1 Word R 007C
11th Load current harmonic L1 Word R 007D
13th Load current harmonic L1 Word R 007E
15th Load current harmonic L1 Word R 007F
17th Load current harmonic L1 Word R 0080
19th Load current harmonic L1 Word R 0081
21st Load current harmonic L1 Word R 0082
23rd Load current harmonic L1 Word R 0083
25th Load current harmonic L1 Word R 0084
Response 1st harmonic response in % without decimals.
Name
Load current harmonics L2
Name Type Function Address (Hexadecimal)
1st Load current harmonic L2 Word R 008C
3rd Load current harmonic L2 Word R 008D
5th Load current harmonic L2 Word R 008E
7th Load current harmonic L2 Word R 008F
9th Load current harmonic L2 Word R 0090
11th Load current harmonic L2 Word R 0091
13th Load current harmonic L2 Word R 0092
15th Load current harmonic L2 Word R 0093
17th Load current harmonic L2 Word R 0094
User Manual
95
GESPSINAF: Active Harmonic Filter
Name
Load current harmonics L3
Name Type Function Address (Hexadecimal)
1st Load current harmonic L3 Word R 00A0
3rd Load current harmonic L3 Word R 00A1
5th Load current harmonic L3 Word R 00A2
7th Load current harmonic L3 Word R 00A3
9th Load current harmonic L3 Word R 00A4
11th Load current harmonic L3 Word R 00A5
13th Load current harmonic L3 Word R 00A6
15th Load current harmonic L3 Word R 00A7
17th Load current harmonic L3 Word R 00A8
19th Load current harmonic L3 Word R 00A9
21st Load current harmonic L3 Word R 00AA
23rd Load current harmonic L3 Word R 00AB
25th Load current harmonic L3 Word R 00AC
Response 1st harmonic response in % without decimals.
Name
Total current THD
Name Type Function Address (Hexadecimal)
Load current total THD L1 Word R 00B4
Load current total THD L2 Word R 00B5
Load current total THD L3 Word R 00B6
Mains current total THD L1 Word R 00B7
Mains current total THD L2 Word R 00B8
Mains current total THD L3 Word R 00B9
Response Response in % without decimals.
Name
Instant measurements
Name Type Function Address (Hexadecimal)
Load current L1 (IL1) Word R 00C8
Load current L2 (IL2) Word R 00C9
Load current L3 (IL3) Word R 00CA
Response Response in Amps without decimals.
Mains current L1 (IR1) Word R 00CB
Mains current L2 (IR2) Word R 00CC
Mains current L3 (IR3) Word R 00CD
Response Response in Amps without decimals.
Mains voltage L1 (VL1) Word R 00CE
Mains voltage L2 (VL2) Word R 00CF
Mains voltage L3 (VL3) Word R 00D0
Response Response in Volts without decimals.
Load active power L1 (P L1) Word R 00D1
Load reactive power L1 (Q L1) Word R 00D2
User Manual
96
GESPSINAF: Active Harmonic Filter
User Manual 97
GESPSINAF: Active Harmonic Filter
GEDAC ELECTRIC
Industrial City; Phase II
P.O.Box # 6838; Jeddah 21452
Tel: +966-2-6364340 – Fax: +966-2-6376742
98
User Manual