ECE 476 - Power System Analysis Fall 2017: Homework 3
ECE 476 - Power System Analysis Fall 2017: Homework 3
Homework 3
Problem 1. A 60-Hz single-phase, two-wire overhead line has solid cylindrical copper conductors with 1.5 cm di-
ameter. The conductors are arranged in a horizontal configuration with 0.5 m spacing. Calculate in mH/km:
a) The inductance of each conductor due to internal flux linkages only.
b) The inductance of each conductor due to both internal and external flux linkages.
The inductance for each conductor due to both internal and external flux linkages is given by (4.4.21):
D
Lx = Ly = 2 × 10−7 ln
r0
!
−7 0.5 H 1000 mH 1000 m
= 2 × 10 ln .
e−1/4 0.015
2
m 1H 1 km
= 0.8899 mH/km per conductor
−7 D
Lx = Ly = 2 × 10 ln
r0
!
−7 0.5 H 1000 mH 1000 m
= 2 × 10 ln 0.018
e−1/4 2
m 1H 1 km
= 0.8535 mH/km per conductor.
1
b) Decreased by 20% to 1.2 cm, without changing the phase spacing.
1 −7 1000 mH 1000 m
Lint = × 10 H/m = 0.05 mH/km per conductor.
2 1H 1 km
D
Lx = Ly = 2 × 10−7 ln
r0
!
−7 0.5 H 1000 mH 1000 m
= 2 × 10 ln 0.012
e−1/4 2
m 1H 1 km
= 0.9346 mH/km per conductor.
• A 20% increase in phase spacing results in a 3.4% decrease in shunt capacitance and admittance.
• A 20% decrease in phase spacing results in a 4.4% increase in shunt capacitance and admittance.