You are on page 1of 348

<?xml version="1.0" encoding="utf-8"?

>
<SCL xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance"
xmlns:xsd="http://www.w3.org/2001/XMLSchema"
xsi:schemaLocation="http://www.iec.ch/61850/2003/SCL SCL.xsd"
xmlns="http://www.iec.ch/61850/2003/SCL">
<Header id="P746" version="2.32" revision="" toolID="ALSTOM IEC61850 Px40
Modelling Tool" nameStructure="IEDName">
<Text source="">IED Capability Description for Centralized Busbar
protection</Text>
</Header>
<Communication>
<SubNetwork name="NONE" type="8-MMS">
<ConnectedAP iedName="F87BB11T" apName="AP1">
<Address>
<P type="IP">10.22.91.105</P>
<P type="IP-SUBNET">255.255.255.0</P>
<P type="IP-GATEWAY">0.0.0.0</P>
<P type="OSI-PSEL">00000001</P>
<P type="OSI-SSEL">0001</P>
<P type="OSI-TSEL">0001</P>
</Address>
<GSE ldInst="System" cbName="gcb01">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0100</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb02">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb03">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb04">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb05">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb06">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb07">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<GSE ldInst="System" cbName="gcb08">
<Address>
<P type="MAC-Address">01-0C-CD-01-00-00</P>
<P type="APPID">0000</P>
<P type="VLAN-ID">000</P>
<P type="VLAN-PRIORITY">4</P>
</Address>
<MinTime unit="s" multiplier="m">10</MinTime>
<MaxTime unit="s" multiplier="m">1000</MaxTime>
</GSE>
<PhysConn type="Plug">
<P type="Type">FOC</P>
<P type="Plug">ST</P>
</PhysConn>
</ConnectedAP>
</SubNetwork>
</Communication>
<IED name="F87BB11T" desc="Centralized Busbar protection" type="P746"
manufacturer="ALSTOM" configVersion="P746v12G">
<Private type="MiCOM-ModellingToolID">ALSTOM IEC61850 Px40 Modelling
Tool</Private>
<Private type="MiCOM-ModellingToolVersion">2.32</Private>
<Private type="MiCOM-ModelNumber">P746???????120* (G-J)</Private>
<Private type="MiCOM-SNTPServers">2</Private>
<Private type="MiCOM-TimeServer" />
<Private type="MiCOM-MCLVersion">V2.1</Private>
<Private type="MiCOM-UniqueID">37000462-551871315.309-20226</Private>
<Services>
<DynAssociation />
<SettingGroups />
<GetDirectory />
<GetDataObjectDefinition />
<DataObjectDirectory />
<GetDataSetValue />
<DataSetDirectory />
<ConfDataSet max="100" modify="true" />
<ReadWrite />
<ConfReportControl max="24" />
<GetCBValues />
<ReportSettings cbName="Fix" datSet="Conf" rptID="Dyn" optFields="Dyn"
bufTime="Dyn" trgOps="Dyn" intgPd="Dyn" />
<GSESettings cbName="Fix" datSet="Conf" appID="Conf" />
<GOOSE max="8" />
<FileHandling />
<ConfLNs fixPrefix="true" fixLnInst="true" />
</Services>
<AccessPoint name="AP1" desc="IEC61850 Interface" router="false" clock="false">
<Server desc="IEC61850 Compliant data model" timeout="900">
<Authentication none="true" />
<LDevice desc="P746 Measurements" inst="Measurements">
<LN0 desc="Measurements Logical Device" lnType="LLN0_STANDARD" inst=""
lnClass="LLN0">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="Returns the Configuration Revision of the Physical
Device." name="configRev" valKind="RO" />
<DAI name="d" valKind="RO">
<Val>Measurements Logical Device</Val>
</DAI>
<DAI name="ldNs" valKind="RO">
<Val>IEC61850-7-4:2003</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN0>
<LN desc="Physical Device Information" lnType="LPHD_STANDARD"
lnClass="LPHD" inst="1">
<DOI name="PhyHealth">
<DAI desc="Returns the Health of the Physical Device." name="stVal"
valKind="RO" />
</DOI>
<DOI name="PhyNam">
<DAI desc="Returns the Hardware Revision of the Physical Device."
name="hwRev" valKind="RO" />
<DAI desc="[00 05] - Plant Reference" name="location" valKind="RO" />
<DAI desc="[00 06] - Model Number" name="model" valKind="RO" />
<DAI desc="[00 08] - Serial Number" name="serNum" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Proxy">
<DAI name="d" valKind="RO">
<Val>Logical Device is a Proxy</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="PwrUp">
<DAI name="d" valKind="RO">
<Val>Px40 Power-Up Detected</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>true</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary Busbar Differential Measurements - Zone 1"
lnType="MMXU_IDIFF" lnClass="MMXU" inst="1" prefix="PriBbp">
<Private type="MiCOM-
ConfigurableAttributes">ABias.phsA.units.multiplier,ABias.phsA.db,ABias.phsA.rangeC
.min.f,ABias.phsA.rangeC.max.f,ABias.phsB.units.multiplier,ABias.phsB.db,ABias.phsB
.rangeC.min.f,ABias.phsB.rangeC.max.f,ABias.phsC.units.multiplier,ABias.phsC.db,ABi
as.phsC.rangeC.min.f,ABias.phsC.rangeC.max.f,ADiff.phsA.units.multiplier,ADiff.phsA
.db,ADiff.phsA.rangeC.min.f,ADiff.phsA.rangeC.max.f,ADiff.phsB.units.multiplier,ADi
ff.phsB.db,ADiff.phsB.rangeC.min.f,ADiff.phsB.rangeC.max.f,ADiff.phsC.units.multipl
ier,ADiff.phsC.db,ADiff.phsC.rangeC.min.f,ADiff.phsC.rangeC.max.f,</Private>
<DOI name="ABias">
<DAI name="d" valKind="RO">
<Val>Differential Bias Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 04] - IA Z1 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 04] - IA Z1 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 05] - IB Z1 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 05] - IB Z1 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 06] - IC Z1 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 06] - IC Z1 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="ADiff">
<DAI name="d" valKind="RO">
<Val>Differential Base Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 01] - IA Z1 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 01] - IA Z1 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 02] - IB Z1 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 02] - IB Z1 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 03] - IC Z1 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 03] - IC Z1 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Differential Zone1 Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary Busbar Differential Measurements - Zone 2"
lnType="MMXU_IDIFF" lnClass="MMXU" inst="2" prefix="PriBbp">
<Private type="MiCOM-
ConfigurableAttributes">ADiff.phsC.rangeC.min.f,ADiff.phsC.rangeC.max.f,ABias.phsA.
units.multiplier,ABias.phsA.db,ABias.phsA.rangeC.min.f,ABias.phsA.rangeC.max.f,ABia
s.phsB.units.multiplier,ABias.phsB.db,ABias.phsB.rangeC.min.f,ABias.phsB.rangeC.max
.f,ABias.phsC.units.multiplier,ABias.phsC.db,ABias.phsC.rangeC.min.f,ABias.phsC.ran
geC.max.f,ADiff.phsA.units.multiplier,ADiff.phsA.db,ADiff.phsA.rangeC.min.f,ADiff.p
hsA.rangeC.max.f,ADiff.phsB.units.multiplier,ADiff.phsB.db,ADiff.phsB.rangeC.min.f,
ADiff.phsB.rangeC.max.f,ADiff.phsC.units.multiplier,ADiff.phsC.db,</Private>
<DOI name="ABias">
<DAI name="d" valKind="RO">
<Val>Differential Bias Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0D] - IA Z2 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0D] - IA Z2 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0E] - IB Z2 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0E] - IB Z2 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0F] - IC Z2 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0F] - IC Z2 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="ADiff">
<DAI name="d" valKind="RO">
<Val>Differential Base Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0A] - IA Z2 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0A] - IA Z2 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0B] - IB Z2 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0B] - IB Z2 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0C] - IC Z2 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0C] - IC Z2 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Differential Zone2 Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary Check Zone Differential Measurements - Fundamentals"
lnType="MMXU_IDIFF" lnClass="MMXU" inst="1" prefix="PriCzn">
<Private type="MiCOM-
ConfigurableAttributes">ABias.phsA.units.multiplier,ABias.phsA.db,ABias.phsA.rangeC
.min.f,ABias.phsA.rangeC.max.f,ADiff.phsA.rangeC.min.f,ADiff.phsA.rangeC.max.f,ADif
f.phsB.units.multiplier,ADiff.phsB.db,ADiff.phsB.rangeC.min.f,ADiff.phsB.rangeC.max
.f,ADiff.phsC.units.multiplier,ADiff.phsC.db,ADiff.phsC.rangeC.min.f,ADiff.phsC.ran
geC.max.f,ABias.phsB.units.multiplier,ABias.phsB.db,ABias.phsB.rangeC.min.f,ABias.p
hsB.rangeC.max.f,ABias.phsC.units.multiplier,ABias.phsC.db,ABias.phsC.rangeC.min.f,
ABias.phsC.rangeC.max.f,ADiff.phsA.units.multiplier,ADiff.phsA.db,</Private>
<DOI name="ABias">
<DAI name="d" valKind="RO">
<Val>Differential Bias Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 16] - IA CZ Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 16] - IA CZ Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 17] - IB CZ Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 17] - IB CZ Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 18] - IC CZ Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 18] - IC CZ Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="ADiff">
<DAI name="d" valKind="RO">
<Val>Differential Base Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 13] - IA CZ Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 13] - IA CZ Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 14] - IB CZ Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 14] - IB CZ Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 15] - IC CZ Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 15] - IC CZ Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Checkzone differential measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary Derived One-box Measurements" lnType="MMXU_A_6"
lnClass="MMXU" inst="1" prefix="PriDvd">
<Private type="MiCOM-
ConfigurableAttributes">A1.neut.db,A2.neut.db,A3.neut.db,A4.neut.db,A5.neut.db,A6.n
eut.db,A1.neut.rangeC.min.f,A1.neut.rangeC.max.f,A2.neut.rangeC.min.f,A2.neut.range
C.max.f,A3.neut.rangeC.min.f,A3.neut.rangeC.max.f,A4.neut.rangeC.min.f,A4.neut.rang
eC.max.f,A5.neut.rangeC.min.f,A5.neut.rangeC.max.f,A6.neut.rangeC.min.f,A6.neut.ran
geC.max.f,A1.neut.units.multiplier,A2.neut.units.multiplier,A3.neut.units.multiplie
r,A4.neut.units.multiplier,A5.neut.units.multiplier,A6.neut.units.multiplier,</Priv
ate>
<DOI name="A1">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 68] - IN-T1 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 67] - IN-T1 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 67] - IN-T1 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A2">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 6F] - IN-T2 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 6E] - IN-T2 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 6E] - IN-T2 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A3">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 76] - IN-T3 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 75] - IN-T3 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 75] - IN-T3 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A4">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 7B] - IN-T4 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 7A] - IN-T4 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7A] - IN-T4 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A5">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 80] - IN-T5 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 7F] - IN-T5 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7F] - IN-T5 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A6">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 85] - IN-T6 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 84] - IN-T6 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 84] - IN-T6 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>IN Derived Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary Fourier Based Measurements" lnType="MMXU_FOURIER"
lnClass="MMXU" inst="1" prefix="PriFou">
<Private type="MiCOM-
ConfigurableAttributes">Hz.db,PPV.phsAB.db,PPV.phsBC.db,PPV.phsCA.db,PhV.phsA.db,Ph
V.phsB.db,PhV.phsC.db,VNd.res.db,PhV.phsC.rangeC.min.f,PhV.phsC.rangeC.max.f,VNd.re
s.rangeC.min.f,VNd.res.rangeC.max.f,PPV.phsAB.rangeC.min.f,PPV.phsAB.rangeC.max.f,P
PV.phsBC.rangeC.min.f,PPV.phsBC.rangeC.max.f,PPV.phsCA.rangeC.min.f,PPV.phsCA.range
C.max.f,PhV.phsA.rangeC.min.f,PhV.phsA.rangeC.max.f,PhV.phsB.rangeC.min.f,PhV.phsB.
rangeC.max.f,Hz.rangeC.min.f,Hz.rangeC.max.f,PhV.phsB.units.multiplier,PhV.phsC.uni
ts.multiplier,VNd.res.units.multiplier,Hz.units.multiplier,PPV.phsAB.units.multipli
er,PPV.phsBC.units.multiplier,PPV.phsCA.units.multiplier,PhV.phsA.units.multiplier,
V0.units.multiplier,V0.db,V0.rangeC.min.f,V0.rangeC.max.f,V1.units.multiplier,V1.db
,V1.rangeC.min.f,V1.rangeC.max.f,V2.units.multiplier,V2.db,V2.rangeC.min.f,V2.range
C.max.f,</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Hz">
<DAI desc="[02 AA] - Frequency" name="d" valKind="Set" />
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 AA] - Frequency" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>66</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>45</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 AA] - Frequency" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Fourier Based Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="PhV">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 90] - VAN Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 8F] - VAN Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 8F] - VAN Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 92] - VBN Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 91] - VBN Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 91] - VBN Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 94] - VCN Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 93] - VCN Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 93] - VCN Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="PPV">
<SDI name="phsAB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 9D] - VAB Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 9C] - VAB Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 9C] - VAB Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsBC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 9F] - VBC Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 9E] - VBC Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 9E] - VBC Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsCA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 A1] - VCA Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 A0] - VCA Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A0] - VCA Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="V0">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 99] - V0 Magnitude" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 99] - V0 Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="V1">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 97] - V1 Magnitude" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 97] - V1 Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="V2">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 98] - V2 Magnitude" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 98] - V2 Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="VNd">
<DAI name="d" valKind="RO">
<Val>Derived Voltage Earth</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="res">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 9B] - VN Derived Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 9A] - VN Derived Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>381.0624</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>9.5266</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 9A] - VN Derived Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
</LN>
<LN desc="Primary Measured Values for One-box Measurements"
lnType="MMXU_DERIVED_A_6" lnClass="MMXU" inst="1" prefix="PriMsi">
<Private type="MiCOM-
ConfigurableAttributes">A1.phsA.db,A1.phsB.db,A1.phsC.db,A2.phsA.db,A2.phsB.db,A2.p
hsC.db,A3.phsA.db,A3.phsB.db,A3.phsC.db,A4.phsA.db,A4.phsB.db,A4.phsC.db,A5.phsA.db
,A5.phsB.db,A5.phsC.db,A6.phsA.db,A6.phsB.db,A6.phsC.db,A1.phsA.rangeC.min.f,A1.phs
A.rangeC.max.f,A1.phsB.rangeC.min.f,A1.phsB.rangeC.max.f,A1.phsC.rangeC.min.f,A1.ph
sC.rangeC.max.f,A2.phsA.rangeC.min.f,A2.phsA.rangeC.max.f,A2.phsB.rangeC.min.f,A2.p
hsB.rangeC.max.f,A2.phsC.rangeC.min.f,A2.phsC.rangeC.max.f,A3.phsA.rangeC.min.f,A3.
phsA.rangeC.max.f,A3.phsB.rangeC.min.f,A3.phsB.rangeC.max.f,A3.phsC.rangeC.min.f,A3
.phsC.rangeC.max.f,A4.phsA.rangeC.min.f,A4.phsA.rangeC.max.f,A4.phsB.rangeC.min.f,A
4.phsB.rangeC.max.f,A4.phsC.rangeC.min.f,A4.phsC.rangeC.max.f,A5.phsA.rangeC.min.f,
A5.phsA.rangeC.max.f,A5.phsB.rangeC.min.f,A5.phsB.rangeC.max.f,A5.phsC.rangeC.min.f
,A5.phsC.rangeC.max.f,A6.phsA.rangeC.min.f,A6.phsA.rangeC.max.f,A6.phsB.rangeC.min.
f,A6.phsB.rangeC.max.f,A6.phsC.rangeC.min.f,A6.phsC.rangeC.max.f,A1.phsA.units.mult
iplier,A1.phsB.units.multiplier,A1.phsC.units.multiplier,A2.phsA.units.multiplier,A
2.phsB.units.multiplier,A2.phsC.units.multiplier,A3.phsA.units.multiplier,A3.phsB.u
nits.multiplier,A3.phsC.units.multiplier,A4.phsA.units.multiplier,A4.phsB.units.mul
tiplier,A4.phsC.units.multiplier,A5.phsA.units.multiplier,A5.phsB.units.multiplier,
A5.phsC.units.multiplier,A6.phsA.units.multiplier,A6.phsB.units.multiplier,A6.phsC.
units.multiplier,</Private>
<DOI name="A1">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 02] - IA-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 01] - IA-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 01] - IA-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 04] - IB-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 03] - IB-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 03] - IB-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 06] - IC-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 05] - IC-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 05] - IC-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A2">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 08] - IA-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 07] - IA-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 07] - IA-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 0A] - IB-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 09] - IB-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 09] - IB-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 0C] - IC-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 0B] - IC-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 0B] - IC-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A3">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 0E] - IA-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 0D] - IA-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 0D] - IA-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 10] - IB-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 0F] - IB-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 0F] - IB-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 12] - IC-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 11] - IC-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 11] - IC-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A4">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 14] - IA-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 13] - IA-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 13] - IA-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 16] - IB-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 15] - IB-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 15] - IB-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 18] - IC-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 17] - IC-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 17] - IC-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A5">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 1A] - IA-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 19] - IA-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 19] - IA-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 1C] - IB-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 1B] - IB-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 1B] - IB-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 1E] - IC-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 1D] - IC-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 1D] - IC-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A6">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 20] - IA-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 1F] - IA-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 1F] - IA-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 22] - IB-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 21] - IB-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 21] - IB-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 24] - IC-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 23] - IC-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 23] - IC-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="[FE 23] - One_Box Measurement Beh" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 22] - One_Box Measurement Mod" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>One Box measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary Measured Values for Three-box Measurements"
lnType="MMXU_A_18" lnClass="MMXU" inst="2" prefix="PriMsi">
<Private type="MiCOM-
ConfigurableAttributes">A1.neut.db,A2.neut.db,A3.neut.db,A4.neut.db,A5.neut.db,A6.n
eut.db,A7.neut.db,A8.neut.db,A9.neut.db,A10.neut.db,A11.neut.db,A12.neut.db,A13.neu
t.db,A14.neut.db,A15.neut.db,A16.neut.db,A17.neut.db,A18.neut.db,A1.neut.rangeC.min
.f,A1.neut.rangeC.max.f,A2.neut.rangeC.min.f,A2.neut.rangeC.max.f,A3.neut.rangeC.mi
n.f,A3.neut.rangeC.max.f,A4.neut.rangeC.min.f,A4.neut.rangeC.max.f,A5.neut.rangeC.m
in.f,A5.neut.rangeC.max.f,A6.neut.rangeC.min.f,A6.neut.rangeC.max.f,A7.neut.rangeC.
min.f,A7.neut.rangeC.max.f,A8.neut.rangeC.min.f,A8.neut.rangeC.max.f,A9.neut.rangeC
.min.f,A9.neut.rangeC.max.f,A10.neut.rangeC.min.f,A10.neut.rangeC.max.f,A11.neut.ra
ngeC.min.f,A11.neut.rangeC.max.f,A12.neut.rangeC.min.f,A12.neut.rangeC.max.f,A13.ne
ut.rangeC.min.f,A13.neut.rangeC.max.f,A14.neut.rangeC.min.f,A14.neut.rangeC.max.f,A
15.neut.rangeC.min.f,A15.neut.rangeC.max.f,A16.neut.rangeC.min.f,A16.neut.rangeC.ma
x.f,A17.neut.rangeC.min.f,A17.neut.rangeC.max.f,A18.neut.rangeC.min.f,A18.neut.rang
eC.max.f,A1.neut.units.multiplier,A2.neut.units.multiplier,A3.neut.units.multiplier
,A4.neut.units.multiplier,A5.neut.units.multiplier,A6.neut.units.multiplier,A7.neut
.units.multiplier,A8.neut.units.multiplier,A9.neut.units.multiplier,A10.neut.units.
multiplier,A11.neut.units.multiplier,A12.neut.units.multiplier,A13.neut.units.multi
plier,A14.neut.units.multiplier,A15.neut.units.multiplier,A16.neut.units.multiplier
,A17.neut.units.multiplier,A18.neut.units.multiplier,</Private>
<DOI name="A1">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 26] - IA-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 25] - IA-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 25] - IA-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A10">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 38] - IA-10 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 37] - IA-10 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 37] - IA-10 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A11">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 3A] - IA-11 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 39] - IA-11 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 39] - IA-11 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A12">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 3C] - IA-12 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 3B] - IA-12 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 3B] - IA-12 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A13">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 3E] - IA-13 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 3D] - IA-13 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 3D] - IA-13 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A14">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 40] - IA-14 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 3F] - IA-14 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 3F] - IA-14 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A15">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 42] - IA-15 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 41] - IA-15 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 41] - IA-15 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A16">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 44] - IA-16 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 43] - IA-16 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 43] - IA-16 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A17">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 46] - IA-17 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 45] - IA-17 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 45] - IA-17 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A18">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 48] - IA-18 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 47] - IA-18 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 47] - IA-18 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A2">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 28] - IA-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 27] - IA-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 27] - IA-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A3">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 2A] - IA-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 29] - IA-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 29] - IA-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A4">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 2C] - IA-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 2B] - IA-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 2B] - IA-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A5">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 2E] - IA-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 2D] - IA-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 2D] - IA-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A6">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 30] - IA-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 2F] - IA-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 2F] - IA-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A7">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 32] - IA-7 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 31] - IA-7 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 31] - IA-7 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A8">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 34] - IA-8 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 33] - IA-8 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 33] - IA-8 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A9">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 36] - IA-9 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 35] - IA-9 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 35] - IA-9 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="[FE 25] - Three_Box Measurement Beh" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 24] - Three_Box Measurement Mod" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Three Box Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Primary RMS Measurements" lnType="MMXU_RMS" lnClass="MMXU"
inst="1" prefix="PriRms">
<Private type="MiCOM-
ConfigurableAttributes">PhV.phsA.db,PhV.phsB.db,PhV.phsC.db,PhV.phsA.rangeC.min.f,P
hV.phsA.rangeC.max.f,PhV.phsB.rangeC.min.f,PhV.phsB.rangeC.max.f,PhV.phsC.rangeC.mi
n.f,PhV.phsC.rangeC.max.f,PhV.phsA.units.multiplier,PhV.phsB.units.multiplier,PhV.p
hsC.units.multiplier,</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>RMS Measurements phase-to-ground</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="PhV">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 A2] - VAN RMS" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A2] - VAN RMS" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 A3] - VBN RMS" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A3] - VBN RMS" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 A4] - VCN RMS" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A4] - VCN RMS" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
</LN>
<LN desc="Primary One-box Sequence Measurements" lnType="MSQI_SEQ_6"
lnClass="MSQI" inst="1" prefix="PriSeq">
<Private type="MiCOM-
ConfigurableAttributes">SeqA1.c1.db,SeqA1.c2.db,SeqA1.c3.db,SeqA2.c1.db,SeqA2.c2.db
,SeqA2.c3.db,SeqA3.c1.db,SeqA3.c2.db,SeqA3.c3.db,SeqA4.c1.db,SeqA4.c2.db,SeqA4.c3.d
b,SeqA5.c1.db,SeqA5.c2.db,SeqA5.c3.db,SeqA6.c1.db,SeqA6.c2.db,SeqA6.c3.db,SeqA1.c1.
rangeC.min.f,SeqA1.c1.rangeC.max.f,SeqA1.c2.rangeC.min.f,SeqA1.c2.rangeC.max.f,SeqA
1.c3.rangeC.min.f,SeqA1.c3.rangeC.max.f,SeqA2.c1.rangeC.min.f,SeqA2.c1.rangeC.max.f
,SeqA2.c2.rangeC.min.f,SeqA2.c2.rangeC.max.f,SeqA2.c3.rangeC.min.f,SeqA2.c3.rangeC.
max.f,SeqA3.c1.rangeC.min.f,SeqA3.c1.rangeC.max.f,SeqA3.c2.rangeC.min.f,SeqA3.c2.ra
ngeC.max.f,SeqA3.c3.rangeC.min.f,SeqA3.c3.rangeC.max.f,SeqA4.c1.rangeC.min.f,SeqA4.
c1.rangeC.max.f,SeqA4.c2.rangeC.min.f,SeqA4.c2.rangeC.max.f,SeqA4.c3.rangeC.min.f,S
eqA4.c3.rangeC.max.f,SeqA5.c1.rangeC.min.f,SeqA5.c1.rangeC.max.f,SeqA5.c2.rangeC.mi
n.f,SeqA5.c2.rangeC.max.f,SeqA5.c3.rangeC.min.f,SeqA5.c3.rangeC.max.f,SeqA6.c1.rang
eC.min.f,SeqA6.c1.rangeC.max.f,SeqA6.c2.rangeC.min.f,SeqA6.c2.rangeC.max.f,SeqA6.c3
.rangeC.min.f,SeqA6.c3.rangeC.max.f,SeqA1.c1.units.multiplier,SeqA1.c2.units.multip
lier,SeqA1.c3.units.multiplier,SeqA2.c1.units.multiplier,SeqA2.c2.units.multiplier,
SeqA2.c3.units.multiplier,SeqA3.c1.units.multiplier,SeqA3.c2.units.multiplier,SeqA3
.c3.units.multiplier,SeqA4.c1.units.multiplier,SeqA4.c2.units.multiplier,SeqA4.c3.u
nits.multiplier,SeqA5.c1.units.multiplier,SeqA5.c2.units.multiplier,SeqA5.c3.units.
multiplier,SeqA6.c1.units.multiplier,SeqA6.c2.units.multiplier,SeqA6.c3.units.multi
plier,</Private>
<DOI name="Beh">
<DAI desc="[FE 23] - One_Box Measurement Beh" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 22] - One_Box Measurement Mod" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>One box mode sequence measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="SeqA1">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 63] - I1-T1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 63] - I1-T1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 64] - I2-T1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 64] - I2-T1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 62] - I0-T1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 62] - I0-T1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA2">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 6A] - I1-T2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 6A] - I1-T2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 6B] - I2-T2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 6B] - I2-T2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 69] - I0-T2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 69] - I0-T2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA3">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 71] - I1-T3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 71] - I1-T3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 72] - I2-T3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 72] - I2-T3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 70] - I0-T3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 70] - I0-T3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA4">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 78] - I1-T4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 78] - I1-T4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 79] - I2-T4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 79] - I2-T4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 77] - I0-T4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 77] - I0-T4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA5">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 7D] - I1-T5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7D] - I1-T5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 7E] - I2-T5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7E] - I2-T5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 7C] - I0-T5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7C] - I0-T5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA6">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 82] - I1-T6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 82] - I1-T6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 83] - I2-T6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 83] - I2-T6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 81] - I0-T6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>900</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>15</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 81] - I0-T6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary Busbar Differential Measurements - Zone 1"
lnType="MMXU_IDIFF" lnClass="MMXU" inst="1" prefix="SecBbp">
<Private type="MiCOM-
ConfigurableAttributes">ABias.phsA.units.multiplier,ABias.phsA.db,ABias.phsA.rangeC
.min.f,ABias.phsA.rangeC.max.f,ABias.phsB.units.multiplier,ABias.phsB.db,ABias.phsB
.rangeC.min.f,ABias.phsB.rangeC.max.f,ABias.phsC.units.multiplier,ABias.phsC.db,ABi
as.phsC.rangeC.min.f,ABias.phsC.rangeC.max.f,ADiff.phsA.units.multiplier,ADiff.phsA
.db,ADiff.phsA.rangeC.min.f,ADiff.phsA.rangeC.max.f,ADiff.phsB.units.multiplier,ADi
ff.phsB.db,ADiff.phsB.rangeC.min.f,ADiff.phsB.rangeC.max.f,ADiff.phsC.units.multipl
ier,ADiff.phsC.db,ADiff.phsC.rangeC.min.f,ADiff.phsC.rangeC.max.f,</Private>
<DOI name="ABias">
<DAI name="d" valKind="RO">
<Val>Differential Bias Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 04] - IA Z1 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 04] - IA Z1 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 05] - IB Z1 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 05] - IB Z1 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 06] - IC Z1 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 06] - IC Z1 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="ADiff">
<DAI name="d" valKind="RO">
<Val>Differential Base Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 01] - IA Z1 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 01] - IA Z1 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 02] - IB Z1 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 02] - IB Z1 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 03] - IC Z1 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 03] - IC Z1 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Differential Zone1 Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary Busbar Differential Measurements - Zone 2"
lnType="MMXU_IDIFF" lnClass="MMXU" inst="2" prefix="SecBbp">
<Private type="MiCOM-
ConfigurableAttributes">ABias.phsA.units.multiplier,ABias.phsA.db,ABias.phsA.rangeC
.min.f,ABias.phsA.rangeC.max.f,ABias.phsB.units.multiplier,ABias.phsB.db,ABias.phsB
.rangeC.min.f,ABias.phsB.rangeC.max.f,ABias.phsC.units.multiplier,ABias.phsC.db,ABi
as.phsC.rangeC.min.f,ABias.phsC.rangeC.max.f,ADiff.phsA.units.multiplier,ADiff.phsA
.db,ADiff.phsA.rangeC.min.f,ADiff.phsA.rangeC.max.f,ADiff.phsB.units.multiplier,ADi
ff.phsB.db,ADiff.phsB.rangeC.min.f,ADiff.phsB.rangeC.max.f,ADiff.phsC.units.multipl
ier,ADiff.phsC.db,ADiff.phsC.rangeC.min.f,ADiff.phsC.rangeC.max.f,</Private>
<DOI name="ABias">
<DAI name="d" valKind="RO">
<Val>Differential Bias Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0D] - IA Z2 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0D] - IA Z2 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0E] - IB Z2 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0E] - IB Z2 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0F] - IC Z2 Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0F] - IC Z2 Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="ADiff">
<DAI name="d" valKind="RO">
<Val>Differential Base Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0A] - IA Z2 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0A] - IA Z2 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0B] - IB Z2 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0B] - IB Z2 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 0C] - IC Z2 Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 0C] - IC Z2 Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Differential Zone2 Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary Check Zone Differential Measurements - Fundamentals"
lnType="MMXU_IDIFF" lnClass="MMXU" inst="1" prefix="SecCzn">
<Private type="MiCOM-
ConfigurableAttributes">ABias.phsA.units.multiplier,ABias.phsA.db,ABias.phsA.rangeC
.min.f,ABias.phsA.rangeC.max.f,ABias.phsB.units.multiplier,ABias.phsB.db,ABias.phsB
.rangeC.min.f,ABias.phsB.rangeC.max.f,ABias.phsC.units.multiplier,ABias.phsC.db,ABi
as.phsC.rangeC.min.f,ABias.phsC.rangeC.max.f,ADiff.phsA.units.multiplier,ADiff.phsA
.db,ADiff.phsA.rangeC.min.f,ADiff.phsA.rangeC.max.f,ADiff.phsB.units.multiplier,ADi
ff.phsB.db,ADiff.phsB.rangeC.min.f,ADiff.phsB.rangeC.max.f,ADiff.phsC.units.multipl
ier,ADiff.phsC.db,ADiff.phsC.rangeC.min.f,ADiff.phsC.rangeC.max.f,</Private>
<DOI name="ABias">
<DAI name="d" valKind="RO">
<Val>Differential Bias Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 16] - IA CZ Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 16] - IA CZ Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 17] - IB CZ Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 17] - IB CZ Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 18] - IC CZ Bias" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 18] - IC CZ Bias" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="ADiff">
<DAI name="d" valKind="RO">
<Val>Differential Base Measurements</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 13] - IA CZ Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 13] - IA CZ Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 14] - IB CZ Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 14] - IB CZ Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[04 15] - IC CZ Diff" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[04 15] - IC CZ Diff" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Checkzone differential measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary Derived One-box Measurements" lnType="MMXU_A_6"
lnClass="MMXU" inst="1" prefix="SecDvd">
<Private type="MiCOM-
ConfigurableAttributes">A1.neut.db,A2.neut.db,A3.neut.db,A4.neut.db,A5.neut.db,A6.n
eut.db,A1.neut.rangeC.min.f,A1.neut.rangeC.max.f,A2.neut.rangeC.min.f,A2.neut.range
C.max.f,A3.neut.rangeC.min.f,A3.neut.rangeC.max.f,A4.neut.rangeC.min.f,A4.neut.rang
eC.max.f,A5.neut.rangeC.min.f,A5.neut.rangeC.max.f,A6.neut.rangeC.min.f,A6.neut.ran
geC.max.f,A1.neut.units.multiplier,A2.neut.units.multiplier,A3.neut.units.multiplie
r,A4.neut.units.multiplier,A5.neut.units.multiplier,A6.neut.units.multiplier,</Priv
ate>
<DOI name="A1">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 68] - IN-T1 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 67] - IN-T1 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 67] - IN-T1 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A2">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 6F] - IN-T2 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 6E] - IN-T2 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 6E] - IN-T2 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A3">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 76] - IN-T3 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 75] - IN-T3 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 75] - IN-T3 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A4">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 7B] - IN-T4 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 7A] - IN-T4 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7A] - IN-T4 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A5">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 80] - IN-T5 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 7F] - IN-T5 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7F] - IN-T5 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A6">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 85] - IN-T6 Deriv Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 84] - IN-T6 Deriv Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 84] - IN-T6 Deriv Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>IN Derived Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary Fourier Based Measurements" lnType="MMXU_FOURIER"
lnClass="MMXU" inst="1" prefix="SecFou">
<Private type="MiCOM-
ConfigurableAttributes">Hz.db,VNd.res.db,PPV.phsAB.db,PPV.phsBC.db,PPV.phsCA.db,PhV
.phsA.db,PhV.phsB.db,PhV.phsC.db,VNd.res.rangeC.min.f,VNd.res.rangeC.max.f,PPV.phsA
B.rangeC.min.f,PPV.phsAB.rangeC.max.f,PPV.phsBC.rangeC.min.f,PPV.phsBC.rangeC.max.f
,PPV.phsCA.rangeC.min.f,PPV.phsCA.rangeC.max.f,PhV.phsA.rangeC.min.f,PhV.phsA.range
C.max.f,PhV.phsB.rangeC.min.f,PhV.phsB.rangeC.max.f,PhV.phsC.rangeC.min.f,PhV.phsC.
rangeC.max.f,Hz.rangeC.min.f,Hz.rangeC.max.f,Hz.units.multiplier,VNd.res.units.mult
iplier,PPV.phsAB.units.multiplier,PPV.phsBC.units.multiplier,PPV.phsCA.units.multip
lier,PhV.phsA.units.multiplier,PhV.phsB.units.multiplier,PhV.phsC.units.multiplier,
V0.units.multiplier,V0.db,V0.rangeC.min.f,V0.rangeC.max.f,V1.units.multiplier,V1.db
,V1.rangeC.min.f,V1.rangeC.max.f,V2.units.multiplier,V2.db,V2.rangeC.min.f,V2.range
C.max.f,</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Hz">
<DAI desc="[02 AA] - Frequency" name="d" valKind="Set" />
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 AA] - Frequency" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>66</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>45</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 AA] - Frequency" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Fourier Based Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="PhV">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 90] - VAN Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 8F] - VAN Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 8F] - VAN Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 92] - VBN Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 91] - VBN Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 91] - VBN Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 94] - VCN Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 93] - VCN Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 93] - VCN Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="PPV">
<SDI name="phsAB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 9D] - VAB Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 9C] - VAB Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 9C] - VAB Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsBC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 9F] - VBC Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 9E] - VBC Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 9E] - VBC Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsCA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 A1] - VCA Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 A0] - VCA Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A0] - VCA Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="V0">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 99] - V0 Magnitude" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 99] - V0 Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="V1">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 97] - V1 Magnitude" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 97] - V1 Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="V2">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="mag">
<DAI desc="[02 98] - V2 Magnitude" name="f" valKind="RO" />
</SDI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>127.0207</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>3.1755</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 98] - V2 Magnitude" name="SIUnit" valKind="RO" />
</SDI>
</DOI>
<DOI name="VNd">
<DAI name="d" valKind="RO">
<Val>Derived Voltage Earth</Val>
</DAI>
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="res">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 9B] - VN Derived Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 9A] - VN Derived Mag" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>381.0624</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>9.5266</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 9A] - VN Derived Mag" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
</LN>
<LN desc="Secondary Measured Values for One-box Measurements"
lnType="MMXU_DERIVED_A_6" lnClass="MMXU" inst="1" prefix="SecMsi">
<Private type="MiCOM-
ConfigurableAttributes">A1.phsA.db,A1.phsB.db,A1.phsC.db,A2.phsA.db,A2.phsB.db,A2.p
hsC.db,A3.phsA.db,A3.phsB.db,A3.phsC.db,A4.phsA.db,A4.phsB.db,A4.phsC.db,A5.phsA.db
,A5.phsB.db,A5.phsC.db,A6.phsA.db,A6.phsB.db,A6.phsC.db,A1.phsA.rangeC.min.f,A1.phs
A.rangeC.max.f,A1.phsB.rangeC.min.f,A1.phsB.rangeC.max.f,A1.phsC.rangeC.min.f,A1.ph
sC.rangeC.max.f,A2.phsA.rangeC.min.f,A2.phsA.rangeC.max.f,A2.phsB.rangeC.min.f,A2.p
hsB.rangeC.max.f,A2.phsC.rangeC.min.f,A2.phsC.rangeC.max.f,A3.phsA.rangeC.min.f,A3.
phsA.rangeC.max.f,A3.phsB.rangeC.min.f,A3.phsB.rangeC.max.f,A3.phsC.rangeC.min.f,A3
.phsC.rangeC.max.f,A4.phsA.rangeC.min.f,A4.phsA.rangeC.max.f,A4.phsB.rangeC.min.f,A
4.phsB.rangeC.max.f,A4.phsC.rangeC.min.f,A4.phsC.rangeC.max.f,A5.phsA.rangeC.min.f,
A5.phsA.rangeC.max.f,A5.phsB.rangeC.min.f,A5.phsB.rangeC.max.f,A5.phsC.rangeC.min.f
,A5.phsC.rangeC.max.f,A6.phsA.rangeC.min.f,A6.phsA.rangeC.max.f,A6.phsB.rangeC.min.
f,A6.phsB.rangeC.max.f,A6.phsC.rangeC.min.f,A6.phsC.rangeC.max.f,A1.phsA.units.mult
iplier,A1.phsB.units.multiplier,A1.phsC.units.multiplier,A2.phsA.units.multiplier,A
2.phsB.units.multiplier,A2.phsC.units.multiplier,A3.phsA.units.multiplier,A3.phsB.u
nits.multiplier,A3.phsC.units.multiplier,A4.phsA.units.multiplier,A4.phsB.units.mul
tiplier,A4.phsC.units.multiplier,A5.phsA.units.multiplier,A5.phsB.units.multiplier,
A5.phsC.units.multiplier,A6.phsA.units.multiplier,A6.phsB.units.multiplier,A6.phsC.
units.multiplier,</Private>
<DOI name="A1">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 02] - IA-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 01] - IA-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 01] - IA-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 04] - IB-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 03] - IB-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 03] - IB-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 06] - IC-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 05] - IC-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 05] - IC-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A2">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 08] - IA-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 07] - IA-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 07] - IA-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 0A] - IB-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 09] - IB-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 09] - IB-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 0C] - IC-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 0B] - IC-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 0B] - IC-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A3">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 0E] - IA-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 0D] - IA-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 0D] - IA-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 10] - IB-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 0F] - IB-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 0F] - IB-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 12] - IC-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 11] - IC-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 11] - IC-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A4">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 14] - IA-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 13] - IA-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 13] - IA-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 16] - IB-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 15] - IB-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 15] - IB-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 18] - IC-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 17] - IC-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 17] - IC-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A5">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 1A] - IA-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 19] - IA-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 19] - IA-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 1C] - IB-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 1B] - IB-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 1B] - IB-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 1E] - IC-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 1D] - IC-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 1D] - IC-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A6">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 20] - IA-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 1F] - IA-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 1F] - IA-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 22] - IB-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 21] - IB-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 21] - IB-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 24] - IC-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 23] - IC-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 23] - IC-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="[FE 23] - One_Box Measurement Beh" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 22] - One_Box Measurement Mod" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>One Box measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary Measured Values for Three-box Measurements"
lnType="MMXU_A_18" lnClass="MMXU" inst="2" prefix="SecMsi">
<Private type="MiCOM-
ConfigurableAttributes">A1.neut.db,A2.neut.db,A3.neut.db,A4.neut.db,A5.neut.db,A6.n
eut.db,A7.neut.db,A8.neut.db,A9.neut.db,A10.neut.db,A11.neut.db,A12.neut.db,A13.neu
t.db,A14.neut.db,A15.neut.db,A16.neut.db,A17.neut.db,A18.neut.db,A1.neut.rangeC.min
.f,A1.neut.rangeC.max.f,A2.neut.rangeC.min.f,A2.neut.rangeC.max.f,A3.neut.rangeC.mi
n.f,A3.neut.rangeC.max.f,A4.neut.rangeC.min.f,A4.neut.rangeC.max.f,A5.neut.rangeC.m
in.f,A5.neut.rangeC.max.f,A6.neut.rangeC.min.f,A6.neut.rangeC.max.f,A7.neut.rangeC.
min.f,A7.neut.rangeC.max.f,A8.neut.rangeC.min.f,A8.neut.rangeC.max.f,A9.neut.rangeC
.min.f,A9.neut.rangeC.max.f,A10.neut.rangeC.min.f,A10.neut.rangeC.max.f,A11.neut.ra
ngeC.min.f,A11.neut.rangeC.max.f,A12.neut.rangeC.min.f,A12.neut.rangeC.max.f,A13.ne
ut.rangeC.min.f,A13.neut.rangeC.max.f,A14.neut.rangeC.min.f,A14.neut.rangeC.max.f,A
15.neut.rangeC.min.f,A15.neut.rangeC.max.f,A16.neut.rangeC.min.f,A16.neut.rangeC.ma
x.f,A17.neut.rangeC.min.f,A17.neut.rangeC.max.f,A18.neut.rangeC.min.f,A18.neut.rang
eC.max.f,A1.neut.units.multiplier,A2.neut.units.multiplier,A3.neut.units.multiplier
,A4.neut.units.multiplier,A5.neut.units.multiplier,A6.neut.units.multiplier,A7.neut
.units.multiplier,A8.neut.units.multiplier,A9.neut.units.multiplier,A10.neut.units.
multiplier,A11.neut.units.multiplier,A12.neut.units.multiplier,A13.neut.units.multi
plier,A14.neut.units.multiplier,A15.neut.units.multiplier,A16.neut.units.multiplier
,A17.neut.units.multiplier,A18.neut.units.multiplier,</Private>
<DOI name="A1">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 26] - IA-1 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 25] - IA-1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 25] - IA-1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A10">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 38] - IA-10 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 37] - IA-10 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 37] - IA-10 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A11">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 3A] - IA-11 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 39] - IA-11 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 39] - IA-11 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A12">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 3C] - IA-12 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 3B] - IA-12 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 3B] - IA-12 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A13">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 3E] - IA-13 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 3D] - IA-13 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 3D] - IA-13 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A14">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 40] - IA-14 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 3F] - IA-14 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 3F] - IA-14 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A15">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 42] - IA-15 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 41] - IA-15 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 41] - IA-15 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A16">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 44] - IA-16 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 43] - IA-16 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 43] - IA-16 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A17">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 46] - IA-17 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 45] - IA-17 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 45] - IA-17 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A18">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 48] - IA-18 Phase Ang" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 47] - IA-18 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 47] - IA-18 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A2">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 28] - IA-2 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 27] - IA-2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 27] - IA-2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A3">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 2A] - IA-3 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 29] - IA-3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 29] - IA-3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A4">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 2C] - IA-4 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 2B] - IA-4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 2B] - IA-4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A5">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 2E] - IA-5 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 2D] - IA-5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 2D] - IA-5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A6">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 30] - IA-6 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 2F] - IA-6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 2F] - IA-6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A7">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 32] - IA-7 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 31] - IA-7 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 31] - IA-7 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A8">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 34] - IA-8 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 33] - IA-8 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 33] - IA-8 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="A9">
<SDI name="neut">
<SDI name="cVal">
<SDI name="ang">
<DAI desc="[02 36] - IA-9 Phase Angle" name="f" valKind="RO" />
</SDI>
<SDI name="mag">
<DAI desc="[02 35] - IA-9 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 35] - IA-9 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
</DOI>
<DOI name="Beh">
<DAI desc="[FE 25] - Three_Box Measurement Beh" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 24] - Three_Box Measurement Mod" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Three Box Measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Secondary RMS Measurements" lnType="MMXU_RMS" lnClass="MMXU"
inst="1" prefix="SecRms">
<Private type="MiCOM-
ConfigurableAttributes">PhV.phsA.db,PhV.phsB.db,PhV.phsC.db,PhV.phsA.rangeC.min.f,P
hV.phsA.rangeC.max.f,PhV.phsB.rangeC.min.f,PhV.phsB.rangeC.max.f,PhV.phsC.rangeC.mi
n.f,PhV.phsC.rangeC.max.f,PhV.phsA.units.multiplier,PhV.phsB.units.multiplier,PhV.p
hsC.units.multiplier,</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>RMS Measurements phase-to-ground</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="PhV">
<SDI name="phsA">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 A2] - VAN RMS" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A2] - VAN RMS" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsB">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 A3] - VBN RMS" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A3] - VBN RMS" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
<SDI name="phsC">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 A4] - VCN RMS" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>220</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>5.5</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 A4] - VCN RMS" name="SIUnit" valKind="RO" />
</SDI>
</SDI>
</DOI>
</LN>
<LN desc="Secondary One-box Sequence Measurements" lnType="MSQI_SEQ_6"
lnClass="MSQI" inst="1" prefix="SecSeq">
<Private type="MiCOM-
ConfigurableAttributes">SeqA1.c1.db,SeqA1.c2.db,SeqA1.c3.db,SeqA2.c1.db,SeqA2.c2.db
,SeqA2.c3.db,SeqA4.c1.db,SeqA4.c2.db,SeqA4.c3.db,SeqA5.c1.db,SeqA5.c2.db,SeqA5.c3.d
b,SeqA6.c1.db,SeqA6.c2.db,SeqA6.c3.db,SeqA3.c1.db,SeqA3.c2.db,SeqA3.c3.db,SeqA1.c1.
rangeC.min.f,SeqA1.c1.rangeC.max.f,SeqA1.c2.rangeC.min.f,SeqA1.c2.rangeC.max.f,SeqA
1.c3.rangeC.min.f,SeqA1.c3.rangeC.max.f,SeqA2.c1.rangeC.min.f,SeqA2.c1.rangeC.max.f
,SeqA2.c2.rangeC.min.f,SeqA2.c2.rangeC.max.f,SeqA2.c3.rangeC.min.f,SeqA2.c3.rangeC.
max.f,SeqA4.c1.rangeC.min.f,SeqA4.c1.rangeC.max.f,SeqA4.c2.rangeC.min.f,SeqA4.c2.ra
ngeC.max.f,SeqA4.c3.rangeC.min.f,SeqA4.c3.rangeC.max.f,SeqA5.c1.rangeC.min.f,SeqA5.
c1.rangeC.max.f,SeqA5.c2.rangeC.min.f,SeqA5.c2.rangeC.max.f,SeqA5.c3.rangeC.min.f,S
eqA5.c3.rangeC.max.f,SeqA6.c1.rangeC.min.f,SeqA6.c1.rangeC.max.f,SeqA6.c2.rangeC.mi
n.f,SeqA6.c2.rangeC.max.f,SeqA6.c3.rangeC.min.f,SeqA6.c3.rangeC.max.f,SeqA3.c1.rang
eC.min.f,SeqA3.c1.rangeC.max.f,SeqA3.c2.rangeC.min.f,SeqA3.c2.rangeC.max.f,SeqA3.c3
.rangeC.min.f,SeqA3.c3.rangeC.max.f,SeqA1.c1.units.multiplier,SeqA1.c2.units.multip
lier,SeqA1.c3.units.multiplier,SeqA2.c1.units.multiplier,SeqA2.c2.units.multiplier,
SeqA2.c3.units.multiplier,SeqA4.c1.units.multiplier,SeqA4.c2.units.multiplier,SeqA4
.c3.units.multiplier,SeqA5.c1.units.multiplier,SeqA5.c2.units.multiplier,SeqA5.c3.u
nits.multiplier,SeqA6.c1.units.multiplier,SeqA6.c2.units.multiplier,SeqA6.c3.units.
multiplier,SeqA3.c1.units.multiplier,SeqA3.c2.units.multiplier,SeqA3.c3.units.multi
plier,</Private>
<DOI name="Beh">
<DAI desc="[FE 23] - One_Box Measurement Beh" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 22] - One_Box Measurement Mod" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>One box mode sequence measurements</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="SeqA1">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 63] - I1-T1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 63] - I1-T1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 64] - I2-T1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 64] - I2-T1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 62] - I0-T1 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 62] - I0-T1 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA2">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 6A] - I1-T2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 6A] - I1-T2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 6B] - I2-T2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 6B] - I2-T2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 69] - I0-T2 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 69] - I0-T2 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA3">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 71] - I1-T3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 71] - I1-T3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 72] - I2-T3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 72] - I2-T3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 70] - I0-T3 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 70] - I0-T3 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA4">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 78] - I1-T4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 78] - I1-T4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 79] - I2-T4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 79] - I2-T4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 77] - I0-T4 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 77] - I0-T4 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA5">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 7D] - I1-T5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7D] - I1-T5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 7E] - I2-T5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7E] - I2-T5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 7C] - I0-T5 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 7C] - I0-T5 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
<DOI name="SeqA6">
<SDI name="c1">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 82] - I1-T6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 82] - I1-T6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c2">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 83] - I2-T6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 83] - I2-T6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<SDI name="c3">
<SDI name="cVal">
<SDI name="mag">
<DAI desc="[02 81] - I0-T6 Magnitude" name="f" valKind="RO" />
</SDI>
</SDI>
<DAI name="db" valKind="Set">
<Val>1000</Val>
</DAI>
<SDI name="rangeC">
<SDI name="hhLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="hLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="lLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="llLim">
<DAI name="f" valKind="RO">
<Val>0</Val>
</DAI>
</SDI>
<SDI name="max">
<DAI name="f" valKind="Set">
<Val>3</Val>
</DAI>
</SDI>
<SDI name="min">
<DAI name="f" valKind="Set">
<Val>0.05</Val>
</DAI>
</SDI>
</SDI>
<SDI name="units">
<DAI name="multiplier" valKind="Set">
<Val></Val>
</DAI>
<DAI desc="[02 81] - I0-T6 Magnitude" name="SIUnit"
valKind="RO" />
</SDI>
</SDI>
<DAI name="seqT" valKind="RO">
<Val>pos-neg-zero</Val>
</DAI>
</DOI>
</LN>
</LDevice>
<LDevice desc="P746 Protection" inst="Protection">
<LN0 desc="Protection LLN0" lnType="LLN0_PROT" inst="" lnClass="LLN0">
<Private type="MiCOM-
ConfigurableAttributes">DifMod.ctlModel,DznMod.ctlModel,OcpMod.ctlModel,EfmMod.ctlM
odel,CbfMod.ctlModel,SvnMod.ctlModel,</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="CbfBeh">
<DAI desc="[09 20] - CB Fail" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="[09 20] - CB Fail" name="stVal" valKind="RO" />
</DOI>
<DOI name="CbfMod">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<DAI desc="[09 20] - CB Fail" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI desc="[09 20] - CB Fail" name="stVal" valKind="RO" />
</DOI>
<DOI name="DifBeh">
<DAI desc="[09 0C] - Diff Protection" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="[09 0C] - Diff Protection" name="stVal" valKind="RO" />
</DOI>
<DOI name="DifMod">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<DAI desc="[09 0C] - Diff Protection" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI desc="[09 0C] - Diff Protection" name="stVal" valKind="RO" />
</DOI>
<DOI name="DznBeh">
<DAI desc="[09 0D] - Dead Zone OC" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="[09 0D] - Dead Zone OC" name="stVal" valKind="RO" />
</DOI>
<DOI name="DznMod">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<DAI desc="[09 0D] - Dead Zone OC" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI desc="[09 0D] - Dead Zone OC" name="stVal" valKind="RO" />
</DOI>
<DOI name="EfmBeh">
<DAI desc="[09 13] - Earth Fault" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="[09 13] - Earth Fault" name="stVal" valKind="RO" />
</DOI>
<DOI name="EfmMod">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<DAI desc="[09 13] - Earth Fault" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI desc="[09 13] - Earth Fault" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="Returns the Configuration Revision of the Physical
Device." name="configRev" valKind="RO" />
<DAI name="d" valKind="RO">
<Val>Protection Logical Device</Val>
</DAI>
<DAI name="ldNs" valKind="RO">
<Val>IEC61850-7-4:2003</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OcpBeh">
<DAI desc="[09 10] - Overcurrent" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="[09 10] - Overcurrent" name="stVal" valKind="RO" />
</DOI>
<DOI name="OcpMod">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<DAI desc="[09 10] - Overcurrent" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI desc="[09 10] - Overcurrent" name="stVal" valKind="RO" />
</DOI>
<DOI name="SvnBeh">
<DAI desc="[09 21] - Supervision" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="[09 21] - Supervision" name="stVal" valKind="RO" />
</DOI>
<DOI name="SvnMod">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<DAI desc="[09 21] - Supervision" name="d" valKind="RO" />
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI desc="[09 21] - Supervision" name="stVal" valKind="RO" />
</DOI>
</LN0>
<LN desc="Busbar Differential - T1" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT01">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 915" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 915" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T2" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT02">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 916" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 916" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T3" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT03">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 917" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 917" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T4" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT04">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 918" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 918" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T5" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT05">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 919" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 919" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T6" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT06">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 920" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 920" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T7" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT07">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 921" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 921" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T8" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT08">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 922" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 922" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T9" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT09">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 923" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 923" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T10" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT10">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 924" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 924" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T11" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT11">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 925" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 925" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T12" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT12">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 926" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 926" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T13" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT13">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 927" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 927" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T14" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT14">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 928" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 928" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T15" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT15">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 929" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 929" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T16" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT16">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 930" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 930" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T17" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT17">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 931" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 931" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Busbar Differential - T18" lnType="PDIF_NEU" lnClass="PDIF"
inst="1" prefix="BbpT18">
<DOI name="Beh">
<DAI desc="[FE 02] - BbpPDIF.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 01] - BbpPDIF.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 932" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 932" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Differential Protection - Zone1" lnType="PDIF_NEU_SEG"
lnClass="PDIF" inst="1" prefix="BbpZon">
<DOI name="Beh">
<DAI desc="[FE 29] - BbpZonPDIF1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 28] - BbpZonPDIF1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Deadzone 1 Differential</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 912" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 903" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 904" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 905" name="phsC" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1522" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1516" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1517" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1518" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Differential Protection - Zone2" lnType="PDIF_NEU_SEG"
lnClass="PDIF" inst="2" prefix="BbpZon">
<DOI name="Beh">
<DAI desc="[FE 2B] - BbpZonPDIF2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 2A] - BbpZonPDIF2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Deadzone 2 Differential</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 913" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 906" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 907" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 908" name="phsC" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1523" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1519" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1520" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1521" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T1" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT01">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB1 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1124" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1104" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T2" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT02">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB2 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1125" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1105" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T3" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT03">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB3 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1126" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1106" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T4" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT04">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB4 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1127" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1107" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T5" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT05">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB5 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1128" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1108" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T6" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT06">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB6 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1129" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1109" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T7" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT07">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB7 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1130" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1110" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T8" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT08">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB8 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1131" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1111" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T9" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT09">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB9 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1132" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1112" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T10" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT10">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB10 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1133" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1113" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T11" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT11">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB11 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1134" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1114" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T12" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT12">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB12 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1135" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1115" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T13" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT13">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB13 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1136" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1116" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T14" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT14">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB14 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1137" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1117" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T15" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT15">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB15 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1138" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1118" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T16" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT16">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB16 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1139" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1119" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T17" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT17">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB17 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1140" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1120" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="CB Fail - T18" lnType="RBRF_STANDARD" lnClass="RBRF" inst="1"
prefix="CbfT18">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>CB18 Fail Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OpEx">
<DAI desc="DDB Ordinal: 1141" name="general" valKind="RO" />
</DOI>
<DOI name="OpIn">
<DAI desc="DDB Ordinal: 1121" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Check Zone Differential Protection"
lnType="PDIF_NEU_SEG_NO_STR" lnClass="PDIF" inst="1" prefix="Czn">
<DOI name="Beh">
<DAI desc="[FE 06] - CznPDIF1.Beh All terminals" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 05] - CznPDIF1.Mod All terminals" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Checkzone Differential</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1527" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1524" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1525" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1526" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T1 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT01">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 933" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 933" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1316" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1624" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1642" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1660" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T2 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT02">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 934" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 934" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1317" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1625" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1643" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1661" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T3 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT03">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 935" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 935" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1318" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1626" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1644" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1662" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T4 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT04">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 936" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 936" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1319" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1627" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1645" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1663" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T5 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT05">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 937" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 937" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1320" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1628" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1646" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1664" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T6 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT06">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 938" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 938" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1321" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1629" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1647" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1665" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T7 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT07">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 939" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 939" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1322" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1630" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1648" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1666" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T8 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT08">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 940" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 940" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1323" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1631" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1649" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1667" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T9 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT09">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 941" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 941" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1324" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1632" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1650" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1668" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T10 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT10">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 942" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 942" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1325" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1633" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1651" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1669" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T11 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT11">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 943" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 943" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1326" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1634" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1652" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1670" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T12 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT12">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 944" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 944" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1327" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1635" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1653" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1671" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T13 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT13">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 945" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 945" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1328" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1636" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1654" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1672" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T14 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT14">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 946" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 946" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1329" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1637" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1655" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1673" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T15 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT15">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 947" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 947" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1330" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1638" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1656" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1674" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T16 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT16">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 948" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 948" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1331" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1639" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1657" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1675" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T17 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT17">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 949" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 949" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1332" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1640" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1658" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1676" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Deadzone Overcurrent - T18 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="DznT18">
<DOI name="Beh">
<DAI desc="[FE 04] - DznPTOC1.Beh terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 03] - DznPTOC1.Mod terminals 1-6" name="stVal"
valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 950" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 950" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1333" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1641" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1659" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1677" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T1 - Stage 1" lnType="PTOC_NEU"
lnClass="PTOC" inst="1" prefix="EfdT01">
<DOI name="Beh">
<DAI desc="[FE 08] - EfdT01PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 07] - EfdT01PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1142" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1142" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1496" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T1- Stage 2" lnType="PTOC_NEU"
lnClass="PTOC" inst="2" prefix="EfdT01">
<DOI name="Beh">
<DAI desc="[FE 14] - EfdT01PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 13] - EfdT01PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1143" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1143" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1497" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T2 - Stage 1" lnType="PTOC_NEU"
lnClass="PTOC" inst="1" prefix="EfdT02">
<DOI name="Beh">
<DAI desc="[FE 0A] - EfdT02PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 09] - EfdT02PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1144" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1144" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1498" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T2- Stage 2" lnType="PTOC_NEU"
lnClass="PTOC" inst="2" prefix="EfdT02">
<DOI name="Beh">
<DAI desc="[FE 16] - EfdT02PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 15] - EfdT02PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1145" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1145" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1499" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T3 - Stage 1" lnType="PTOC_NEU"
lnClass="PTOC" inst="1" prefix="EfdT03">
<DOI name="Beh">
<DAI desc="[FE 0C] - EfdT03PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 0B] - EfdT03PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1146" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1146" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1500" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T3- Stage 2" lnType="PTOC_NEU"
lnClass="PTOC" inst="2" prefix="EfdT03">
<DOI name="Beh">
<DAI desc="[FE 18] - EfdT03PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 17] - EfdT03PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1147" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1147" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1501" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T4 - Stage 1" lnType="PTOC_NEU"
lnClass="PTOC" inst="1" prefix="EfdT04">
<DOI name="Beh">
<DAI desc="[FE 0E] - EfdT04PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 0D] - EfdT04PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1148" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1148" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1502" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T4- Stage 2" lnType="PTOC_NEU"
lnClass="PTOC" inst="2" prefix="EfdT04">
<DOI name="Beh">
<DAI desc="[FE 1A] - EfdT04PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 19] - EfdT04PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1149" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1149" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1503" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T5 - Stage 1" lnType="PTOC_NEU"
lnClass="PTOC" inst="1" prefix="EfdT05">
<DOI name="Beh">
<DAI desc="[FE 10] - EfdT05PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 0F] - EfdT05PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1150" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1150" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1504" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T5- Stage 2" lnType="PTOC_NEU"
lnClass="PTOC" inst="2" prefix="EfdT05">
<DOI name="Beh">
<DAI desc="[FE 1C] - EfdT05PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 1B] - EfdT05PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1151" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1151" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1505" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T6 - Stage 1" lnType="PTOC_NEU"
lnClass="PTOC" inst="1" prefix="EfdT06">
<DOI name="Beh">
<DAI desc="[FE 12] - EfdT06PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 11] - EfdT06PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1152" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1152" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1506" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Earth Fault Protection - T6- Stage 2" lnType="PTOC_NEU"
lnClass="PTOC" inst="2" prefix="EfdT06">
<DOI name="Beh">
<DAI desc="[FE 1E] - EfdT06PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 1D] - EfdT06PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1153" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1153" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1507" name="general" valKind="RO" />
</DOI>
</LN>
<LN desc="Physical Device Information" lnType="LPHD_STANDARD"
lnClass="LPHD" inst="1">
<DOI name="PhyHealth">
<DAI desc="Returns the Health of the Physical Device." name="stVal"
valKind="RO" />
</DOI>
<DOI name="PhyNam">
<DAI desc="Returns the Hardware Revision of the Physical Device."
name="hwRev" valKind="RO" />
<DAI desc="[00 05] - Plant Reference" name="location" valKind="RO" />
<DAI desc="[00 06] - Model Number" name="model" valKind="RO" />
<DAI desc="[00 08] - Serial Number" name="serNum" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Proxy">
<DAI name="d" valKind="RO">
<Val>Logical Device is a Proxy</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="PwrUp">
<DAI name="d" valKind="RO">
<Val>Px40 Power-Up Detected</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>true</Val>
</DAI>
</DOI>
</LN>
<LN desc="Overcurrent Protection - T1 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT01">
<DOI name="Beh">
<DAI desc="[FE 49] - OcpT01PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 48] - OcpT01PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1008" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1008" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1340" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1341" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1342" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1343" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T1 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT01">
<DOI name="Beh">
<DAI desc="[FE 6D] - OcpT01PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 6C] - OcpT01PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1009" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1009" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1344" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1345" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1346" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1347" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T2 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT02">
<DOI name="Beh">
<DAI desc="[FE 4B] - OcpT02PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 4A] - OcpT02PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1010" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1010" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1348" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1349" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1350" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1351" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T2 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT02">
<DOI name="Beh">
<DAI desc="[FE 6F] - OcpT02PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 6E] - OcpT02PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1011" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1011" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1352" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1353" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1354" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1355" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T3 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT03">
<DOI name="Beh">
<DAI desc="[FE 4D] - OcpT03PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 4C] - OcpT03PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1012" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1012" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1356" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1357" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1358" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1359" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T3 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT03">
<DOI name="Beh">
<DAI desc="[FE 71] - OcpT03PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 70] - OcpT03PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1013" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1013" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1360" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1361" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1362" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1363" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T4 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT04">
<DOI name="Beh">
<DAI desc="[FE 4F] - OcpT04PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 4E] - OcpT04PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1014" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1014" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1364" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1365" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1366" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1367" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T4 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT04">
<DOI name="Beh">
<DAI desc="[FE 73] - OcpT04PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 72] - OcpT04PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1015" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1015" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1368" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1369" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1370" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1371" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T5 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT05">
<DOI name="Beh">
<DAI desc="[FE 51] - OcpT05PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 50] - OcpT05PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1016" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1016" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1372" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1373" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1374" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1375" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T5 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT05">
<DOI name="Beh">
<DAI desc="[FE 75] - OcpT05PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 74] - OcpT05PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1017" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1017" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1376" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1377" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1378" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1379" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T6 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT06">
<DOI name="Beh">
<DAI desc="[FE 53] - OcpT06PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 52] - OcpT06PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1018" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1018" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1380" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1381" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1382" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1383" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T6 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT06">
<DOI name="Beh">
<DAI desc="[FE 77] - OcpT06PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 76] - OcpT06PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1019" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1019" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1384" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1385" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1386" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1387" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T7 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT07">
<DOI name="Beh">
<DAI desc="[FE 55] - OcpT07PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 54] - OcpT07PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1020" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1020" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1388" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1389" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1390" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1391" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T7 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT07">
<DOI name="Beh">
<DAI desc="[FE 79] - OcpT07PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 78] - OcpT07PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1021" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1021" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1392" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1393" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1394" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1395" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T8 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT08">
<DOI name="Beh">
<DAI desc="[FE 57] - OcpT08PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 56] - OcpT08PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1022" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1022" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1396" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1397" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1398" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1399" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T8 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT08">
<DOI name="Beh">
<DAI desc="[FE 7B] - OcpT08PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 7A] - OcpT08PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1023" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1023" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1400" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1401" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1402" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1403" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T9 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT09">
<DOI name="Beh">
<DAI desc="[FE 59] - OcpT09PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 58] - OcpT09PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1024" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1024" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1404" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1405" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1406" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1407" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T9 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT09">
<DOI name="Beh">
<DAI desc="[FE 7D] - OcpT09PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 7C] - OcpT09PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1025" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1025" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1408" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1409" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1410" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1411" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T10 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT10">
<DOI name="Beh">
<DAI desc="[FE 5B] - OcpT10PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 5A] - OcpT10PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1026" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1026" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1412" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1413" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1414" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1415" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T10 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT10">
<DOI name="Beh">
<DAI desc="[FE 7F] - OcpT10PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 7E] - OcpT10PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1027" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1027" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1416" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1417" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1418" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1419" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T11 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT11">
<DOI name="Beh">
<DAI desc="[FE 5D] - OcpT11PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 5C] - OcpT11PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1028" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1028" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1420" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1421" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1422" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1423" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T11 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT11">
<DOI name="Beh">
<DAI desc="[FE 81] - OcpT11PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 80] - OcpT11PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1029" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1029" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1424" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1425" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1426" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1427" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T12 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT12">
<DOI name="Beh">
<DAI desc="[FE 5F] - OcpT12PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 5E] - OcpT12PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1030" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1030" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1428" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1429" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1430" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1431" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T12 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT12">
<DOI name="Beh">
<DAI desc="[FE 83] - OcpT12PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 82] - OcpT12PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1031" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1031" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1432" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1433" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1434" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1435" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T13 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT13">
<DOI name="Beh">
<DAI desc="[FE 61] - OcpT13PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 60] - OcpT13PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1032" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1032" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1436" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1437" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1438" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1439" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T13 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT13">
<DOI name="Beh">
<DAI desc="[FE 85] - OcpT13PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 84] - OcpT13PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1033" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1033" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1440" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1441" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1442" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1443" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T14 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT14">
<DOI name="Beh">
<DAI desc="[FE 63] - OcpT14PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 62] - OcpT14PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1034" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1034" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1444" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1445" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1446" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1447" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T14 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT14">
<DOI name="Beh">
<DAI desc="[FE 87] - OcpT14PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 86] - OcpT14PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1035" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1035" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1448" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1449" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1450" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1451" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T15 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT15">
<DOI name="Beh">
<DAI desc="[FE 65] - OcpT15PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 64] - OcpT15PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1036" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1036" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1452" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1453" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1454" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1455" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T15 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT15">
<DOI name="Beh">
<DAI desc="[FE 89] - OcpT15PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 88] - OcpT15PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1037" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1037" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1456" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1457" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1458" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1459" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T16 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT16">
<DOI name="Beh">
<DAI desc="[FE 67] - OcpT16PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 66] - OcpT16PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1038" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1038" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1460" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1461" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1462" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1463" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T16 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT16">
<DOI name="Beh">
<DAI desc="[FE 8B] - OcpT16PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 8A] - OcpT16PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1039" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1039" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1464" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1465" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1466" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1467" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T17 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT17">
<DOI name="Beh">
<DAI desc="[FE 69] - OcpT17PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 68] - OcpT17PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1040" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1040" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1468" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1469" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1470" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1471" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T17 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT17">
<DOI name="Beh">
<DAI desc="[FE 8D] - OcpT17PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 8C] - OcpT17PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1041" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1041" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1472" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1473" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1474" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1475" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T18 - Stage 1" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="1" prefix="OcpT18">
<DOI name="Beh">
<DAI desc="[FE 6B] - OcpT18PTOC1.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 6A] - OcpT18PTOC1.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1042" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1042" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1476" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1477" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1478" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1479" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Overcurrent Protection - T18 - Stage 2" lnType="PTOC_NEU_SEG"
lnClass="PTOC" inst="2" prefix="OcpT18">
<DOI name="Beh">
<DAI desc="[FE 8F] - OcpT18PTOC2.Beh" name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI desc="[FE 8E] - OcpT18PTOC2.Mod" name="stVal" valKind="RO" />
</DOI>
<DOI name="NamPlt">
<DAI desc="DDB Ordinal: 1043" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Op">
<DAI desc="DDB Ordinal: 1043" name="general" valKind="RO" />
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsA" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsB" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI name="dirPhsC" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1480" name="general" valKind="RO" />
<DAI desc="DDB Ordinal: 1481" name="phsA" valKind="RO" />
<DAI desc="DDB Ordinal: 1482" name="phsB" valKind="RO" />
<DAI desc="DDB Ordinal: 1483" name="phsC" valKind="RO" />
</DOI>
</LN>
<LN desc="Trip Conditioning" lnType="PTRC_NO_SEG" lnClass="PTRC"
inst="1">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Trip Conditioning</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Str">
<DAI name="dirGeneral" valKind="RO">
<Val>unknown</Val>
</DAI>
<DAI desc="DDB Ordinal: 1312" name="general" valKind="RO" />
</DOI>
<DOI name="Tr">
<DAI desc="DDB Ordinal: 886" name="general" valKind="RO" />
</DOI>
</LN>
</LDevice>
<LDevice desc="P746 Records" inst="Records">
<LN0 desc="Records Logical Device" lnType="LLN0_STANDARD" inst=""
lnClass="LLN0">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="Returns the Configuration Revision of the Physical
Device." name="configRev" valKind="RO" />
<DAI name="d" valKind="RO">
<Val>Records Logical Device</Val>
</DAI>
<DAI name="ldNs" valKind="RO">
<Val>IEC61850-7-4:2003</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN0>
<LN desc="Physical Device Information" lnType="LPHD_STANDARD"
lnClass="LPHD" inst="1">
<DOI name="PhyHealth">
<DAI desc="Returns the Health of the Physical Device." name="stVal"
valKind="RO" />
</DOI>
<DOI name="PhyNam">
<DAI desc="Returns the Hardware Revision of the Physical Device."
name="hwRev" valKind="RO" />
<DAI desc="[00 05] - Plant Reference" name="location" valKind="RO" />
<DAI desc="[00 06] - Model Number" name="model" valKind="RO" />
<DAI desc="[00 08] - Serial Number" name="serNum" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Proxy">
<DAI name="d" valKind="RO">
<Val>Logical Device is a Proxy</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="PwrUp">
<DAI name="d" valKind="RO">
<Val>Px40 Power-Up Detected</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>true</Val>
</DAI>
</DOI>
</LN>
<LN desc="Disturbance Recorder" lnType="RDRE_BASIC" lnClass="RDRE"
inst="1">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="FltNum">
<DAI name="stVal" valKind="RO">
<Val>0</Val>
</DAI>
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Disturbance Recorder Function</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="RcdMade">
<DAI desc="Returns if a Disturbance Record is available for
Extraction." name="stVal" valKind="RO" />
</DOI>
</LN>
</LDevice>
<LDevice desc="P746 System" inst="System">
<LN0 desc="System Logical Device" lnType="LLN0_SYSTEM" inst=""
lnClass="LLN0">
<Private type="MiCOM-
ConfigurableAttributes">LEDRs.ctlModel,LEDRs.sboTimeout,</Private>
<DataSet name="SYSTEM_T">
<FCDA doName="Mod" fc="ST" ldInst="System" lnClass="LLN0" />
<FCDA doName="PhyHealth" fc="ST" ldInst="System" lnClass="LPHD"
lnInst="1" />
<FCDA doName="Ind1" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind2" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind3" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind4" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind5" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind6" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind7" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind8" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind9" fc="ST" ldInst="System" lnClass="GGIO" lnInst="1"
prefix="Led" />
<FCDA doName="Ind10" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind11" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind12" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind13" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind14" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind15" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind16" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind17" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind18" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="1" prefix="Led" />
<FCDA doName="Ind1" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind2" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind3" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind4" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind5" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind6" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind7" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind8" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind9" fc="ST" ldInst="System" lnClass="GGIO" lnInst="2"
prefix="Led" />
<FCDA doName="Ind10" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind11" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind12" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind13" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind14" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind15" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind16" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind17" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
<FCDA doName="Ind18" fc="ST" ldInst="System" lnClass="GGIO"
lnInst="2" prefix="Led" />
</DataSet>
<DataSet name="GOOSE_T">
<FCDA daName="stVal" doName="Ind1" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind2" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind3" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind4" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind5" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind6" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind7" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind8" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind9" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind10" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind11" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind12" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind13" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind14" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind15" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind16" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind17" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind18" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind19" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind20" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind21" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind22" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind23" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind24" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind25" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind26" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind27" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind28" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind29" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind30" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind31" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind32" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind33" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind34" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind35" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind36" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind37" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind38" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind39" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
<FCDA daName="stVal" doName="Ind40" fc="ST" ldInst="System"
lnClass="GGIO" lnInst="2" prefix="Gos" />
</DataSet>
<DataSet name="PROTEKSI_T">
<FCDA doName="ABias" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriBbp" />
<FCDA doName="ADiff" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriBbp" />
<FCDA doName="ABias" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriCzn" />
<FCDA doName="ADiff" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriCzn" />
<FCDA doName="Hz" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
<FCDA doName="PPV.phsAB" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
<FCDA doName="PPV.phsBC" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
<FCDA doName="PPV.phsCA" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
<FCDA doName="Op" fc="ST" ldInst="Protection" lnClass="PDIF"
lnInst="1" prefix="BbpZon" />
<FCDA doName="Op" fc="ST" ldInst="Protection" lnClass="PDIF"
lnInst="2" prefix="BbpZon" />
<FCDA doName="PhV.phsA" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
<FCDA doName="PhV.phsB" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
<FCDA doName="PhV.phsC" fc="MX" ldInst="Measurements" lnClass="MMXU"
lnInst="1" prefix="PriFou" />
</DataSet>
<ReportControl name="urcbA" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$RP$urcbA01" confRev="4"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbB" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$RP$urcbB01" confRev="4"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbC" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$RP$urcbC01" confRev="4"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbD" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$RP$urcbD01" confRev="4"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbE" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$RP$urcbE01" confRev="4"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbF" desc="System Logical Device Report Control
Block" datSet="PROTEKSI_T" rptID="F87BB11TSystem/LLN0$RP$urcbF01" confRev="1"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbG" desc="System Logical Device Report Control
Block" datSet="PROTEKSI_T" rptID="F87BB11TSystem/LLN0$RP$urcbG01" confRev="1"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbH" desc="System Logical Device Report Control
Block" datSet="PROTEKSI_T" rptID="F87BB11TSystem/LLN0$RP$urcbH01" confRev="1"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbI" desc="System Logical Device Report Control
Block" datSet="PROTEKSI_T" rptID="F87BB11TSystem/LLN0$RP$urcbI01" confRev="1"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbJ" desc="System Logical Device Report Control
Block" datSet="PROTEKSI_T" rptID="F87BB11TSystem/LLN0$RP$urcbJ01" confRev="1"
buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbK" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$RP$urcbK01" confRev="0" buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbL" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$RP$urcbL01" confRev="0" buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbM" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$RP$urcbM01" confRev="0" buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbN" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$RP$urcbN01" confRev="0" buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbO" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$RP$urcbO01" confRev="0" buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="urcbP" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$RP$urcbP01" confRev="0" buffered="false">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbA" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$BR$brcbA01" confRev="4"
buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbB" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$BR$brcbB01" confRev="4"
buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbC" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$BR$brcbC01" confRev="4"
buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbD" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$BR$brcbD01" confRev="4"
buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbE" desc="System Logical Device Report Control
Block" datSet="SYSTEM_T" rptID="System/LLN0$BR$brcbE01" confRev="4"
buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbF" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$BR$brcbF01" confRev="0" buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbG" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$BR$brcbG01" confRev="0" buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<ReportControl name="brcbH" desc="System Logical Device Report Control
Block" rptID="F87BB11TSystem/LLN0$BR$brcbH01" confRev="0" buffered="true">
<TrgOps dchg="true" qchg="false" dupd="false" period="true" />
<OptFields seqNum="true" timeStamp="true" dataSet="true"
reasonCode="true" dataRef="false" entryID="false" configRef="false" />
<RptEnabled max="1" />
</ReportControl>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="LEDRs">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>0</Val>
</DAI>
<DAI desc="[01 FF] - Reset Indication" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="Returns the Configuration Revision of the Physical
Device." name="configRev" valKind="RO" />
<DAI name="d" valKind="RO">
<Val>System Logical Device</Val>
</DAI>
<DAI name="ldNs" valKind="RO">
<Val>IEC61850-7-4:2003</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="OrdRun">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="Order Running indication" name="stVal" valKind="RO" />
</DOI>
<DOI name="SyncSt">
<DAI name="dataNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-4:2003</Val>
</DAI>
<DAI desc="IED time synchronisation state" name="stVal"
valKind="RO" />
</DOI>
<GSEControl name="gcb01" desc="System Logical Device GOOSE Control
Block 1" datSet="GOOSE_T" confRev="4" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb01"
type="GOOSE" />
<GSEControl name="gcb02" desc="System Logical Device GOOSE Control
Block 2" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb02" type="GOOSE" />
<GSEControl name="gcb03" desc="System Logical Device GOOSE Control
Block 3" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb03" type="GOOSE" />
<GSEControl name="gcb04" desc="System Logical Device GOOSE Control
Block 4" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb04" type="GOOSE" />
<GSEControl name="gcb05" desc="System Logical Device GOOSE Control
Block 5" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb05" type="GOOSE" />
<GSEControl name="gcb06" desc="System Logical Device GOOSE Control
Block 6" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb06" type="GOOSE" />
<GSEControl name="gcb07" desc="System Logical Device GOOSE Control
Block 7" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb07" type="GOOSE" />
<GSEControl name="gcb08" desc="System Logical Device GOOSE Control
Block 8" confRev="0" appID="F87BB11TTEMPLATESystem/LLN0$GO$gcb08" type="GOOSE" />
<SettingControl numOfSGs="4" actSG="1" />
</LN0>
<LN desc="Alarms" lnType="GGIO_ALM_96" lnClass="GGIO" inst="1"
prefix="Alm">
<DOI name="Alm1">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm10">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm11">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm12">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm13">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm14">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm15">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm16">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm17">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm18">
<DAI desc="DDB Ordinal: 465" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 465" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm19">
<DAI desc="DDB Ordinal: 466" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 466" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm2">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm20">
<DAI desc="DDB Ordinal: 467" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 467" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm21">
<DAI desc="DDB Ordinal: 468" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 468" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm22">
<DAI desc="DDB Ordinal: 469" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 469" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm23">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm24">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm25">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm26">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm27">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm28">
<DAI desc="DDB Ordinal: 475" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 475" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm29">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm3">
<DAI desc="DDB Ordinal: 450" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 450" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm30">
<DAI desc="DDB Ordinal: 477" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 477" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm31">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm32">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm33">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm34">
<DAI desc="DDB Ordinal: 481" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 481" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm35">
<DAI desc="DDB Ordinal: 482" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 482" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm36">
<DAI desc="DDB Ordinal: 483" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 483" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm37">
<DAI desc="DDB Ordinal: 484" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 484" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm38">
<DAI desc="DDB Ordinal: 485" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 485" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm39">
<DAI desc="DDB Ordinal: 486" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 486" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm4">
<DAI desc="DDB Ordinal: 451" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 451" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm40">
<DAI desc="DDB Ordinal: 487" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 487" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm41">
<DAI desc="DDB Ordinal: 488" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 488" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm42">
<DAI desc="DDB Ordinal: 489" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 489" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm43">
<DAI desc="DDB Ordinal: 490" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 490" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm44">
<DAI desc="DDB Ordinal: 491" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 491" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm45">
<DAI desc="DDB Ordinal: 492" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 492" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm46">
<DAI desc="DDB Ordinal: 493" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 493" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm47">
<DAI desc="DDB Ordinal: 494" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 494" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm48">
<DAI desc="DDB Ordinal: 495" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 495" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm49">
<DAI desc="DDB Ordinal: 496" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 496" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm5">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm50">
<DAI desc="DDB Ordinal: 497" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 497" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm51">
<DAI desc="DDB Ordinal: 498" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 498" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm52">
<DAI desc="DDB Ordinal: 499" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 499" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm53">
<DAI desc="DDB Ordinal: 500" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 500" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm54">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm55">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm56">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm57">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm58">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm59">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm6">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm60">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm61">
<DAI desc="DDB Ordinal: 508" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 508" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm62">
<DAI desc="DDB Ordinal: 509" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 509" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm63">
<DAI desc="DDB Ordinal: 510" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 510" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm64">
<DAI desc="DDB Ordinal: 511" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 511" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm65">
<DAI desc="DDB Ordinal: 512" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 512" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm66">
<DAI desc="DDB Ordinal: 513" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 513" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm67">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm68">
<DAI desc="DDB Ordinal: 515" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 515" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm69">
<DAI desc="DDB Ordinal: 516" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 516" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm7">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm70">
<DAI desc="DDB Ordinal: 517" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 517" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm71">
<DAI desc="DDB Ordinal: 518" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 518" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm72">
<DAI desc="DDB Ordinal: 519" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 519" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm73">
<DAI desc="DDB Ordinal: 520" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 520" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm74">
<DAI desc="DDB Ordinal: 521" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 521" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm75">
<DAI desc="DDB Ordinal: 522" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 522" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm76">
<DAI desc="DDB Ordinal: 523" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 523" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm77">
<DAI desc="DDB Ordinal: 524" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 524" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm78">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm79">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm8">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm80">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm81">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm82">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm83">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm84">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm85">
<DAI desc="DDB Ordinal: 532" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 532" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm86">
<DAI desc="DDB Ordinal: 533" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 533" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm87">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm88">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm89">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm9">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm90">
<DAI desc="DDB Ordinal: 537" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 537" name="stVal" valKind="RO" />
</DOI>
<DOI name="Alm91">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm92">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm93">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm94">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm95">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Alm96">
<DAI name="d" valKind="RO">
<Val>Unused</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Alarm Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Function Key Indications" lnType="GGIO_IND_10" lnClass="GGIO"
inst="1" prefix="Fnk">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 352" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 352" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 361" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 361" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 353" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 353" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 354" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 354" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 355" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 355" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 356" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 356" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 357" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 357" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 358" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 358" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 359" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 359" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 360" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 360" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>Function Key Indications</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="GOOSE Input signals" lnType="GGIO_IND_128" lnClass="GGIO"
inst="1" prefix="Gos">
<Private type="MiCOM-BindableType">VI</Private>
<Private type="MiCOM-BindableSignals">
Ind1.stVal,
Ind2.stVal,
Ind3.stVal,
Ind4.stVal,
Ind5.stVal,
Ind6.stVal,
Ind7.stVal,
Ind8.stVal,
Ind9.stVal,
Ind10.stVal,
Ind11.stVal,
Ind12.stVal,
Ind13.stVal,
Ind14.stVal,
Ind15.stVal,
Ind16.stVal,
Ind17.stVal,
Ind18.stVal,
Ind19.stVal,
Ind20.stVal,
Ind21.stVal,
Ind22.stVal,
Ind23.stVal,
Ind24.stVal,
Ind25.stVal,
Ind26.stVal,
Ind27.stVal,
Ind28.stVal,
Ind29.stVal,
Ind30.stVal,
Ind31.stVal,
Ind32.stVal,
Ind33.stVal,
Ind34.stVal,
Ind35.stVal,
Ind36.stVal,
Ind37.stVal,
Ind38.stVal,
Ind39.stVal,
Ind40.stVal,
Ind41.stVal,
Ind42.stVal,
Ind43.stVal,
Ind44.stVal,
Ind45.stVal,
Ind46.stVal,
Ind47.stVal,
Ind48.stVal,
Ind49.stVal,
Ind50.stVal,
Ind51.stVal,
Ind52.stVal,
Ind53.stVal,
Ind54.stVal,
Ind55.stVal,
Ind56.stVal,
Ind57.stVal,
Ind58.stVal,
Ind59.stVal,
Ind60.stVal,
Ind61.stVal,
Ind62.stVal,
Ind63.stVal,
Ind64.stVal,
Ind65.stVal,
Ind66.stVal,
Ind67.stVal,
Ind68.stVal,
Ind69.stVal,
Ind70.stVal,
Ind71.stVal,
Ind72.stVal,
Ind73.stVal,
Ind74.stVal,
Ind75.stVal,
Ind76.stVal,
Ind77.stVal,
Ind78.stVal,
Ind79.stVal,
Ind80.stVal,
Ind81.stVal,
Ind82.stVal,
Ind83.stVal,
Ind84.stVal,
Ind85.stVal,
Ind86.stVal,
Ind87.stVal,
Ind88.stVal,
Ind89.stVal,
Ind90.stVal,
Ind91.stVal,
Ind92.stVal,
Ind93.stVal,
Ind94.stVal,
Ind95.stVal,
Ind96.stVal,
Ind97.stVal,
Ind98.stVal,
Ind99.stVal,
Ind100.stVal,
Ind101.stVal,
Ind102.stVal,
Ind103.stVal,
Ind104.stVal,
Ind105.stVal,
Ind106.stVal,
Ind107.stVal,
Ind108.stVal,
Ind109.stVal,
Ind110.stVal,
Ind111.stVal,
Ind112.stVal,
Ind113.stVal,
Ind114.stVal,
Ind115.stVal,
Ind116.stVal,
Ind117.stVal,
Ind118.stVal,
Ind119.stVal,
Ind120.stVal,
Ind121.stVal,
Ind122.stVal,
Ind123.stVal,
Ind124.stVal,
Ind125.stVal,
Ind126.stVal,
Ind127.stVal,
Ind128.stVal,
</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 1856" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1856" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 1865" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1865" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind100">
<DAI desc="DDB Ordinal: 698" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 698" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind101">
<DAI desc="DDB Ordinal: 699" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 699" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind102">
<DAI desc="DDB Ordinal: 700" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 700" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind103">
<DAI desc="DDB Ordinal: 701" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 701" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind104">
<DAI desc="DDB Ordinal: 702" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 702" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind105">
<DAI desc="DDB Ordinal: 703" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 703" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind106">
<DAI desc="DDB Ordinal: 704" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 704" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind107">
<DAI desc="DDB Ordinal: 705" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 705" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind108">
<DAI desc="DDB Ordinal: 706" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 706" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind109">
<DAI desc="DDB Ordinal: 707" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 707" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind11">
<DAI desc="DDB Ordinal: 1866" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1866" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind110">
<DAI desc="DDB Ordinal: 708" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 708" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind111">
<DAI desc="DDB Ordinal: 709" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 709" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind112">
<DAI desc="DDB Ordinal: 710" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 710" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind113">
<DAI desc="DDB Ordinal: 711" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 711" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind114">
<DAI desc="DDB Ordinal: 712" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 712" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind115">
<DAI desc="DDB Ordinal: 713" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 713" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind116">
<DAI desc="DDB Ordinal: 714" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 714" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind117">
<DAI desc="DDB Ordinal: 715" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 715" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind118">
<DAI desc="DDB Ordinal: 1484" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1484" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind119">
<DAI desc="DDB Ordinal: 1485" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1485" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind12">
<DAI desc="DDB Ordinal: 1867" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1867" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind120">
<DAI desc="DDB Ordinal: 1486" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1486" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind121">
<DAI desc="DDB Ordinal: 1487" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1487" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind122">
<DAI desc="DDB Ordinal: 1488" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1488" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind123">
<DAI desc="DDB Ordinal: 1489" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1489" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind124">
<DAI desc="DDB Ordinal: 1490" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1490" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind125">
<DAI desc="DDB Ordinal: 1491" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1491" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind126">
<DAI desc="DDB Ordinal: 1492" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1492" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind127">
<DAI desc="DDB Ordinal: 1493" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1493" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind128">
<DAI desc="DDB Ordinal: 1494" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1494" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind13">
<DAI desc="DDB Ordinal: 1868" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1868" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind14">
<DAI desc="DDB Ordinal: 1869" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1869" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind15">
<DAI desc="DDB Ordinal: 1870" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1870" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind16">
<DAI desc="DDB Ordinal: 1871" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1871" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind17">
<DAI desc="DDB Ordinal: 1872" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1872" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind18">
<DAI desc="DDB Ordinal: 1873" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1873" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind19">
<DAI desc="DDB Ordinal: 1874" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1874" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 1857" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1857" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind20">
<DAI desc="DDB Ordinal: 1875" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1875" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind21">
<DAI desc="DDB Ordinal: 1876" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1876" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind22">
<DAI desc="DDB Ordinal: 1877" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1877" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind23">
<DAI desc="DDB Ordinal: 1878" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1878" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind24">
<DAI desc="DDB Ordinal: 1879" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1879" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind25">
<DAI desc="DDB Ordinal: 1880" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1880" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind26">
<DAI desc="DDB Ordinal: 1881" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1881" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind27">
<DAI desc="DDB Ordinal: 1882" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1882" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind28">
<DAI desc="DDB Ordinal: 1883" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1883" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind29">
<DAI desc="DDB Ordinal: 1884" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1884" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 1858" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1858" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind30">
<DAI desc="DDB Ordinal: 1885" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1885" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind31">
<DAI desc="DDB Ordinal: 1886" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1886" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind32">
<DAI desc="DDB Ordinal: 1887" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1887" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind33">
<DAI desc="DDB Ordinal: 1888" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1888" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind34">
<DAI desc="DDB Ordinal: 1889" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1889" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind35">
<DAI desc="DDB Ordinal: 1890" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1890" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind36">
<DAI desc="DDB Ordinal: 1891" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1891" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind37">
<DAI desc="DDB Ordinal: 1892" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1892" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind38">
<DAI desc="DDB Ordinal: 1893" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1893" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind39">
<DAI desc="DDB Ordinal: 1894" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1894" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 1859" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1859" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind40">
<DAI desc="DDB Ordinal: 1895" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1895" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind41">
<DAI desc="DDB Ordinal: 1896" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1896" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind42">
<DAI desc="DDB Ordinal: 1897" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1897" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind43">
<DAI desc="DDB Ordinal: 1898" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1898" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind44">
<DAI desc="DDB Ordinal: 1899" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1899" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind45">
<DAI desc="DDB Ordinal: 1900" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1900" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind46">
<DAI desc="DDB Ordinal: 1901" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1901" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind47">
<DAI desc="DDB Ordinal: 1902" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1902" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind48">
<DAI desc="DDB Ordinal: 1903" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1903" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind49">
<DAI desc="DDB Ordinal: 1904" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1904" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 1860" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1860" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind50">
<DAI desc="DDB Ordinal: 1905" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1905" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind51">
<DAI desc="DDB Ordinal: 1906" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1906" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind52">
<DAI desc="DDB Ordinal: 1907" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1907" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind53">
<DAI desc="DDB Ordinal: 1908" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1908" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind54">
<DAI desc="DDB Ordinal: 1909" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1909" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind55">
<DAI desc="DDB Ordinal: 1910" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1910" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind56">
<DAI desc="DDB Ordinal: 1911" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1911" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind57">
<DAI desc="DDB Ordinal: 1912" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1912" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind58">
<DAI desc="DDB Ordinal: 1913" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1913" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind59">
<DAI desc="DDB Ordinal: 1914" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1914" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 1861" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1861" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind60">
<DAI desc="DDB Ordinal: 1915" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1915" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind61">
<DAI desc="DDB Ordinal: 1916" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1916" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind62">
<DAI desc="DDB Ordinal: 1917" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1917" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind63">
<DAI desc="DDB Ordinal: 1918" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1918" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind64">
<DAI desc="DDB Ordinal: 1919" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1919" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind65">
<DAI desc="DDB Ordinal: 663" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 663" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind66">
<DAI desc="DDB Ordinal: 664" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 664" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind67">
<DAI desc="DDB Ordinal: 665" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 665" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind68">
<DAI desc="DDB Ordinal: 666" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 666" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind69">
<DAI desc="DDB Ordinal: 667" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 667" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 1862" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1862" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind70">
<DAI desc="DDB Ordinal: 668" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 668" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind71">
<DAI desc="DDB Ordinal: 669" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 669" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind72">
<DAI desc="DDB Ordinal: 670" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 670" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind73">
<DAI desc="DDB Ordinal: 671" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 671" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind74">
<DAI desc="DDB Ordinal: 672" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 672" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind75">
<DAI desc="DDB Ordinal: 673" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 673" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind76">
<DAI desc="DDB Ordinal: 674" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 674" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind77">
<DAI desc="DDB Ordinal: 675" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 675" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind78">
<DAI desc="DDB Ordinal: 676" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 676" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind79">
<DAI desc="DDB Ordinal: 677" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 677" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 1863" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1863" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind80">
<DAI desc="DDB Ordinal: 678" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 678" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind81">
<DAI desc="DDB Ordinal: 679" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 679" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind82">
<DAI desc="DDB Ordinal: 680" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 680" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind83">
<DAI desc="DDB Ordinal: 681" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 681" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind84">
<DAI desc="DDB Ordinal: 682" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 682" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind85">
<DAI desc="DDB Ordinal: 683" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 683" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind86">
<DAI desc="DDB Ordinal: 684" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 684" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind87">
<DAI desc="DDB Ordinal: 685" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 685" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind88">
<DAI desc="DDB Ordinal: 686" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 686" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind89">
<DAI desc="DDB Ordinal: 687" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 687" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 1864" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1864" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind90">
<DAI desc="DDB Ordinal: 688" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 688" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind91">
<DAI desc="DDB Ordinal: 689" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 689" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind92">
<DAI desc="DDB Ordinal: 690" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 690" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind93">
<DAI desc="DDB Ordinal: 691" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 691" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind94">
<DAI desc="DDB Ordinal: 692" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 692" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind95">
<DAI desc="DDB Ordinal: 693" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 693" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind96">
<DAI desc="DDB Ordinal: 694" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 694" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind97">
<DAI desc="DDB Ordinal: 695" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 695" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind98">
<DAI desc="DDB Ordinal: 696" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 696" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind99">
<DAI desc="DDB Ordinal: 697" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 697" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>GOOSE Input Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<Inputs>
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind1" intAddr="Ind1.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind2" intAddr="Ind2.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind3" intAddr="Ind3.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind4" intAddr="Ind4.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind5" intAddr="Ind5.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind6" intAddr="Ind6.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind7" intAddr="Ind7.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind8" intAddr="Ind8.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind9" intAddr="Ind9.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind10" intAddr="Ind10.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind11" intAddr="Ind11.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind12" intAddr="Ind12.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind1" intAddr="Ind13.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind2" intAddr="Ind14.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind3" intAddr="Ind15.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind4" intAddr="Ind16.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind5" intAddr="Ind17.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind6" intAddr="Ind18.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind7" intAddr="Ind19.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind8" intAddr="Ind20.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind15" intAddr="Ind21.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind12" intAddr="Ind22.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind16" intAddr="Ind23.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind13" intAddr="Ind24.stVal" lnInst="2" />
<ExtRef iedName="F87BB11R" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind17" intAddr="Ind25.stVal" lnInst="2" />
<ExtRef iedName="F87BB11S" ldInst="System" prefix="Gos"
lnClass="GGIO" daName="stVal" doName="Ind14" intAddr="Ind26.stVal" lnInst="2" />
</Inputs>
</LN>
<LN desc="GOOSE Output signals" lnType="GGIO_IND_128" lnClass="GGIO"
inst="2" prefix="Gos">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 1592" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1592" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 1601" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1601" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind100">
<DAI desc="DDB Ordinal: 1685" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1685" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind101">
<DAI desc="DDB Ordinal: 1686" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1686" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind102">
<DAI desc="DDB Ordinal: 1687" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1687" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind103">
<DAI desc="DDB Ordinal: 1688" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1688" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind104">
<DAI desc="DDB Ordinal: 1689" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1689" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind105">
<DAI desc="DDB Ordinal: 1690" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1690" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind106">
<DAI desc="DDB Ordinal: 1691" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1691" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind107">
<DAI desc="DDB Ordinal: 1692" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1692" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind108">
<DAI desc="DDB Ordinal: 1693" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1693" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind109">
<DAI desc="DDB Ordinal: 1694" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1694" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind11">
<DAI desc="DDB Ordinal: 1602" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1602" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind110">
<DAI desc="DDB Ordinal: 1695" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1695" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind111">
<DAI desc="DDB Ordinal: 1722" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1722" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind112">
<DAI desc="DDB Ordinal: 1723" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1723" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind113">
<DAI desc="DDB Ordinal: 1724" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1724" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind114">
<DAI desc="DDB Ordinal: 1725" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1725" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind115">
<DAI desc="DDB Ordinal: 1726" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1726" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind116">
<DAI desc="DDB Ordinal: 1727" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1727" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind117">
<DAI desc="DDB Ordinal: 1728" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1728" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind118">
<DAI desc="DDB Ordinal: 1729" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1729" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind119">
<DAI desc="DDB Ordinal: 1730" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1730" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind12">
<DAI desc="DDB Ordinal: 1603" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1603" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind120">
<DAI desc="DDB Ordinal: 1731" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1731" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind121">
<DAI desc="DDB Ordinal: 1732" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1732" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind122">
<DAI desc="DDB Ordinal: 1733" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1733" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind123">
<DAI desc="DDB Ordinal: 1734" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1734" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind124">
<DAI desc="DDB Ordinal: 1735" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1735" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind125">
<DAI desc="DDB Ordinal: 1736" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1736" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind126">
<DAI desc="DDB Ordinal: 1737" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1737" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind127">
<DAI desc="DDB Ordinal: 1738" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1738" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind128">
<DAI desc="DDB Ordinal: 1739" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1739" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind13">
<DAI desc="DDB Ordinal: 1604" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1604" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind14">
<DAI desc="DDB Ordinal: 1605" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1605" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind15">
<DAI desc="DDB Ordinal: 1606" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1606" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind16">
<DAI desc="DDB Ordinal: 1607" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1607" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind17">
<DAI desc="DDB Ordinal: 1608" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1608" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind18">
<DAI desc="DDB Ordinal: 1609" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1609" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind19">
<DAI desc="DDB Ordinal: 1610" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1610" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 1593" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1593" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind20">
<DAI desc="DDB Ordinal: 1611" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1611" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind21">
<DAI desc="DDB Ordinal: 1612" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1612" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind22">
<DAI desc="DDB Ordinal: 1613" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1613" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind23">
<DAI desc="DDB Ordinal: 1614" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1614" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind24">
<DAI desc="DDB Ordinal: 1615" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1615" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind25">
<DAI desc="DDB Ordinal: 1616" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1616" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind26">
<DAI desc="DDB Ordinal: 1617" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1617" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind27">
<DAI desc="DDB Ordinal: 1618" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1618" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind28">
<DAI desc="DDB Ordinal: 1619" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1619" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind29">
<DAI desc="DDB Ordinal: 1620" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1620" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 1594" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1594" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind30">
<DAI desc="DDB Ordinal: 1621" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1621" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind31">
<DAI desc="DDB Ordinal: 1622" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1622" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind32">
<DAI desc="DDB Ordinal: 1623" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1623" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind33">
<DAI desc="DDB Ordinal: 1044" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1044" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind34">
<DAI desc="DDB Ordinal: 1045" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1045" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind35">
<DAI desc="DDB Ordinal: 1046" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1046" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind36">
<DAI desc="DDB Ordinal: 1047" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1047" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind37">
<DAI desc="DDB Ordinal: 1048" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1048" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind38">
<DAI desc="DDB Ordinal: 1049" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1049" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind39">
<DAI desc="DDB Ordinal: 1050" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1050" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 1595" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1595" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind40">
<DAI desc="DDB Ordinal: 1051" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1051" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind41">
<DAI desc="DDB Ordinal: 1052" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1052" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind42">
<DAI desc="DDB Ordinal: 1053" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1053" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind43">
<DAI desc="DDB Ordinal: 1054" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1054" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind44">
<DAI desc="DDB Ordinal: 1055" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1055" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind45">
<DAI desc="DDB Ordinal: 1056" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1056" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind46">
<DAI desc="DDB Ordinal: 1057" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1057" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind47">
<DAI desc="DDB Ordinal: 1058" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1058" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind48">
<DAI desc="DDB Ordinal: 1059" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1059" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind49">
<DAI desc="DDB Ordinal: 1060" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1060" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 1596" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1596" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind50">
<DAI desc="DDB Ordinal: 1061" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1061" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind51">
<DAI desc="DDB Ordinal: 1062" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1062" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind52">
<DAI desc="DDB Ordinal: 1063" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1063" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind53">
<DAI desc="DDB Ordinal: 1064" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1064" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind54">
<DAI desc="DDB Ordinal: 1065" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1065" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind55">
<DAI desc="DDB Ordinal: 1066" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1066" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind56">
<DAI desc="DDB Ordinal: 1067" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1067" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind57">
<DAI desc="DDB Ordinal: 1068" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1068" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind58">
<DAI desc="DDB Ordinal: 1069" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1069" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind59">
<DAI desc="DDB Ordinal: 1070" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1070" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 1597" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1597" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind60">
<DAI desc="DDB Ordinal: 1071" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1071" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind61">
<DAI desc="DDB Ordinal: 1072" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1072" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind62">
<DAI desc="DDB Ordinal: 1073" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1073" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind63">
<DAI desc="DDB Ordinal: 1074" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1074" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind64">
<DAI desc="DDB Ordinal: 1075" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1075" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind65">
<DAI desc="DDB Ordinal: 1076" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1076" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind66">
<DAI desc="DDB Ordinal: 1077" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1077" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind67">
<DAI desc="DDB Ordinal: 1078" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1078" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind68">
<DAI desc="DDB Ordinal: 1079" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1079" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind69">
<DAI desc="DDB Ordinal: 1080" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1080" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 1598" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1598" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind70">
<DAI desc="DDB Ordinal: 1081" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1081" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind71">
<DAI desc="DDB Ordinal: 1082" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1082" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind72">
<DAI desc="DDB Ordinal: 1083" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1083" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind73">
<DAI desc="DDB Ordinal: 1084" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1084" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind74">
<DAI desc="DDB Ordinal: 1085" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1085" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind75">
<DAI desc="DDB Ordinal: 1086" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1086" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind76">
<DAI desc="DDB Ordinal: 1087" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1087" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind77">
<DAI desc="DDB Ordinal: 1088" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1088" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind78">
<DAI desc="DDB Ordinal: 1089" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1089" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind79">
<DAI desc="DDB Ordinal: 1090" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1090" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 1599" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1599" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind80">
<DAI desc="DDB Ordinal: 1091" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1091" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind81">
<DAI desc="DDB Ordinal: 1092" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1092" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind82">
<DAI desc="DDB Ordinal: 1093" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1093" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind83">
<DAI desc="DDB Ordinal: 1094" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1094" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind84">
<DAI desc="DDB Ordinal: 1095" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1095" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind85">
<DAI desc="DDB Ordinal: 1096" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1096" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind86">
<DAI desc="DDB Ordinal: 1097" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1097" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind87">
<DAI desc="DDB Ordinal: 1098" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1098" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind88">
<DAI desc="DDB Ordinal: 1099" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1099" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind89">
<DAI desc="DDB Ordinal: 1100" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1100" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 1600" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1600" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind90">
<DAI desc="DDB Ordinal: 1101" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1101" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind91">
<DAI desc="DDB Ordinal: 1102" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1102" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind92">
<DAI desc="DDB Ordinal: 1103" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1103" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind93">
<DAI desc="DDB Ordinal: 1678" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1678" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind94">
<DAI desc="DDB Ordinal: 1679" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1679" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind95">
<DAI desc="DDB Ordinal: 1680" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1680" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind96">
<DAI desc="DDB Ordinal: 1681" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1681" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind97">
<DAI desc="DDB Ordinal: 1682" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1682" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind98">
<DAI desc="DDB Ordinal: 1683" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1683" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind99">
<DAI desc="DDB Ordinal: 1684" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1684" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>GOOSE Output Status</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Red LED Signals" lnType="GGIO_IND_18" lnClass="GGIO" inst="1"
prefix="Led">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 257" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 256" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 275" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 274" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind11">
<DAI desc="DDB Ordinal: 277" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 276" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind12">
<DAI desc="DDB Ordinal: 279" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 278" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind13">
<DAI desc="DDB Ordinal: 281" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 280" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind14">
<DAI desc="DDB Ordinal: 283" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 282" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind15">
<DAI desc="DDB Ordinal: 285" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 284" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind16">
<DAI desc="DDB Ordinal: 287" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 286" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind17">
<DAI desc="DDB Ordinal: 289" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 288" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind18">
<DAI desc="DDB Ordinal: 291" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 290" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 259" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 258" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 261" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 260" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 263" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 262" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 265" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 264" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 267" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 266" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 269" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 268" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 271" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 270" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 273" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 272" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="[0F 15] - Red LED Status" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Green LED Signals" lnType="GGIO_IND_18" lnClass="GGIO" inst="2"
prefix="Led">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 256" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 257" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 274" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 275" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind11">
<DAI desc="DDB Ordinal: 276" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 277" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind12">
<DAI desc="DDB Ordinal: 278" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 279" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind13">
<DAI desc="DDB Ordinal: 280" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 281" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind14">
<DAI desc="DDB Ordinal: 282" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 283" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind15">
<DAI desc="DDB Ordinal: 284" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 285" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind16">
<DAI desc="DDB Ordinal: 286" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 287" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind17">
<DAI desc="DDB Ordinal: 288" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 289" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind18">
<DAI desc="DDB Ordinal: 290" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 291" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 258" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 259" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 260" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 261" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 262" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 263" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 264" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 265" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 266" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 267" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 268" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 269" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 270" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 271" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 272" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 273" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="[0F 16] - Green LED Status" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Physical Device Information" lnType="LPHD_STANDARD"
lnClass="LPHD" inst="1">
<DOI name="PhyHealth">
<DAI desc="Returns the Health of the Physical Device." name="stVal"
valKind="RO" />
</DOI>
<DOI name="PhyNam">
<DAI desc="Returns the Hardware Revision of the Physical Device."
name="hwRev" valKind="RO" />
<DAI desc="[00 05] - Plant Reference" name="location" valKind="RO" />
<DAI desc="[00 06] - Model Number" name="model" valKind="RO" />
<DAI desc="[00 08] - Serial Number" name="serNum" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="Proxy">
<DAI name="d" valKind="RO">
<Val>Logical Device is a Proxy</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="PwrUp">
<DAI name="d" valKind="RO">
<Val>Px40 Power-Up Detected</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>true</Val>
</DAI>
</DOI>
</LN>
<LN desc="Opto Inputs" lnType="GGIO_IND_40" lnClass="GGIO" inst="1"
prefix="Opt">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 64" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 64" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 73" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 73" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind11">
<DAI desc="DDB Ordinal: 74" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 74" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind12">
<DAI desc="DDB Ordinal: 75" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 75" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind13">
<DAI desc="DDB Ordinal: 76" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 76" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind14">
<DAI desc="DDB Ordinal: 77" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 77" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind15">
<DAI desc="DDB Ordinal: 78" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 78" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind16">
<DAI desc="DDB Ordinal: 79" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 79" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind17">
<DAI desc="DDB Ordinal: 80" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 80" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind18">
<DAI desc="DDB Ordinal: 81" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 81" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind19">
<DAI desc="DDB Ordinal: 82" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 82" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 65" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 65" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind20">
<DAI desc="DDB Ordinal: 83" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 83" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind21">
<DAI desc="DDB Ordinal: 84" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 84" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind22">
<DAI desc="DDB Ordinal: 85" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 85" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind23">
<DAI desc="DDB Ordinal: 86" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 86" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind24">
<DAI desc="DDB Ordinal: 87" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 87" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind25">
<DAI desc="DDB Ordinal: 88" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 88" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind26">
<DAI desc="DDB Ordinal: 89" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 89" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind27">
<DAI desc="DDB Ordinal: 90" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 90" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind28">
<DAI desc="DDB Ordinal: 91" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 91" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind29">
<DAI desc="DDB Ordinal: 92" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 92" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 66" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 66" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind30">
<DAI desc="DDB Ordinal: 93" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 93" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind31">
<DAI desc="DDB Ordinal: 94" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 94" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind32">
<DAI desc="DDB Ordinal: 95" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 95" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind33">
<DAI desc="DDB Ordinal: 96" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 96" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind34">
<DAI desc="DDB Ordinal: 97" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 97" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind35">
<DAI desc="DDB Ordinal: 98" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 98" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind36">
<DAI desc="DDB Ordinal: 99" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 99" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind37">
<DAI desc="DDB Ordinal: 100" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 100" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind38">
<DAI desc="DDB Ordinal: 101" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 101" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind39">
<DAI desc="DDB Ordinal: 102" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 102" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 67" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 67" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind40">
<DAI desc="DDB Ordinal: 103" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 103" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 68" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 68" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 69" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 69" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 70" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 70" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 71" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 71" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 72" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 72" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="[0F 01] - Opto I/P Status" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="Uniqueness of control &quot;Order Running&quot; indications for
Control Operations" lnType="GGIO_IND_64" lnClass="GGIO" inst="1" prefix="OrdRun">
<Private type="MiCOM-BindableType">OrdRun</Private>
<Private type="MiCOM-BindableSignals">
Ind1.stVal,
Ind2.stVal,
Ind3.stVal,
Ind4.stVal,
Ind5.stVal,
Ind6.stVal,
Ind7.stVal,
Ind8.stVal,
Ind9.stVal,
Ind10.stVal,
Ind11.stVal,
Ind12.stVal,
Ind13.stVal,
Ind14.stVal,
Ind15.stVal,
Ind16.stVal,
Ind17.stVal,
Ind18.stVal,
Ind19.stVal,
Ind20.stVal,
Ind21.stVal,
Ind22.stVal,
Ind23.stVal,
Ind24.stVal,
Ind25.stVal,
Ind26.stVal,
Ind27.stVal,
Ind28.stVal,
Ind29.stVal,
Ind30.stVal,
Ind31.stVal,
Ind32.stVal,
Ind33.stVal,
Ind34.stVal,
Ind35.stVal,
Ind36.stVal,
Ind37.stVal,
Ind38.stVal,
Ind39.stVal,
Ind40.stVal,
Ind41.stVal,
Ind42.stVal,
Ind43.stVal,
Ind44.stVal,
Ind45.stVal,
Ind46.stVal,
Ind47.stVal,
Ind48.stVal,
Ind49.stVal,
Ind50.stVal,
Ind51.stVal,
Ind52.stVal,
Ind53.stVal,
Ind54.stVal,
Ind55.stVal,
Ind56.stVal,
Ind57.stVal,
Ind58.stVal,
Ind59.stVal,
Ind60.stVal,
Ind61.stVal,
Ind62.stVal,
Ind63.stVal,
Ind64.stVal,
</Private>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind10">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind11">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind12">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind13">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind14">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind15">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind16">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind17">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind18">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind19">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind2">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind20">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind21">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind22">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind23">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind24">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind25">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind26">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind27">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind28">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind29">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind3">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind30">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind31">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind32">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind33">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind34">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind35">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind36">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind37">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind38">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind39">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind4">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind40">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind41">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind42">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind43">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind44">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind45">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind46">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind47">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind48">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind49">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind5">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind50">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind51">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind52">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind53">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind54">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind55">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind56">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind57">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind58">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind59">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind6">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind60">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind61">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind62">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind63">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind64">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind7">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind8">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Ind9">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>false</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI name="d" valKind="RO">
<Val>External device order running indication</Val>
</DAI>
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
<LN desc="PSL Control Inputs" lnType="GGIO_IND_32_CTRL" lnClass="GGIO"
inst="1" prefix="Plo">
<Private type="MiCOM-
ConfigurableAttributes">SPCSO1.ctlModel,SPCSO1.sboTimeout,SPCSO2.ctlModel,SPCSO2.sb
oTimeout,SPCSO3.ctlModel,SPCSO3.sboTimeout,SPCSO4.ctlModel,SPCSO4.sboTimeout,SPCSO5
.ctlModel,SPCSO5.sboTimeout,SPCSO6.ctlModel,SPCSO6.sboTimeout,SPCSO7.ctlModel,SPCSO
7.sboTimeout,SPCSO8.ctlModel,SPCSO8.sboTimeout,SPCSO9.ctlModel,SPCSO9.sboTimeout,SP
CSO10.ctlModel,SPCSO10.sboTimeout,SPCSO11.ctlModel,SPCSO11.sboTimeout,SPCSO12.ctlMo
del,SPCSO12.sboTimeout,SPCSO13.ctlModel,SPCSO13.sboTimeout,SPCSO14.ctlModel,SPCSO14
.sboTimeout,SPCSO15.ctlModel,SPCSO15.sboTimeout,SPCSO16.ctlModel,SPCSO16.sboTimeout
,SPCSO17.ctlModel,SPCSO17.sboTimeout,SPCSO18.ctlModel,SPCSO18.sboTimeout,SPCSO19.ct
lModel,SPCSO19.sboTimeout,SPCSO20.ctlModel,SPCSO20.sboTimeout,SPCSO21.ctlModel,SPCS
O21.sboTimeout,SPCSO22.ctlModel,SPCSO22.sboTimeout,SPCSO23.ctlModel,SPCSO23.sboTime
out,SPCSO24.ctlModel,SPCSO24.sboTimeout,SPCSO25.ctlModel,SPCSO25.sboTimeout,SPCSO26
.ctlModel,SPCSO26.sboTimeout,SPCSO27.ctlModel,SPCSO27.sboTimeout,SPCSO28.ctlModel,S
PCSO28.sboTimeout,SPCSO29.ctlModel,SPCSO29.sboTimeout,SPCSO30.ctlModel,SPCSO30.sboT
imeout,SPCSO31.ctlModel,SPCSO31.sboTimeout,SPCSO32.ctlModel,SPCSO32.sboTimeout,</Pr
ivate>
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="[12 01] - Ctrl I/P Status" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
<DOI name="SPCSO1">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1824" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO10">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1833" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO11">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1834" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO12">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1835" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO13">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1836" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO14">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1837" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO15">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1838" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO16">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1839" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO17">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1840" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO18">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1841" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO19">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1842" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO2">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1825" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO20">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1843" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO21">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1844" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO22">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1845" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO23">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1846" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO24">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1847" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO25">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1848" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO26">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1849" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO27">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1850" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO28">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1851" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO29">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1852" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO3">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1826" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO30">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1853" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO31">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1854" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO32">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1855" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO4">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1827" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO5">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1828" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO6">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1829" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO7">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1830" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO8">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1831" name="stVal" valKind="RO" />
</DOI>
<DOI name="SPCSO9">
<DAI name="cdcName" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="cdcNs" valKind="RO">
<Val>ALSTOM-SII:PCS-Px40&gt;IEC 61850-7-3:2003</Val>
</DAI>
<DAI name="ctlModel" valKind="Set">
<Val>status-only</Val>
</DAI>
<SDI name="origin">
<DAI name="orCat" valKind="RO">
<Val>process</Val>
</DAI>
<DAI name="orIdent" valKind="RO" />
</SDI>
<DAI name="sboTimeout" valKind="Set">
<Val>30000</Val>
</DAI>
<DAI desc="DDB Ordinal: 1832" name="stVal" valKind="RO" />
</DOI>
</LN>
<LN desc="Relay Outputs" lnType="GGIO_IND_32" lnClass="GGIO" inst="1"
prefix="Rly">
<DOI name="Beh">
<DAI desc="Determines the Mode/Behaviour of the Device based on the
'Test Mode' DDB." name="stVal" valKind="RO" />
</DOI>
<DOI name="Health">
<DAI name="stVal" valKind="RO">
<Val>Ok</Val>
</DAI>
</DOI>
<DOI name="Ind1">
<DAI desc="DDB Ordinal: 0" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 0" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind10">
<DAI desc="DDB Ordinal: 9" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 9" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind11">
<DAI desc="DDB Ordinal: 10" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 10" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind12">
<DAI desc="DDB Ordinal: 11" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 11" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind13">
<DAI desc="DDB Ordinal: 12" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 12" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind14">
<DAI desc="DDB Ordinal: 13" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 13" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind15">
<DAI desc="DDB Ordinal: 14" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 14" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind16">
<DAI desc="DDB Ordinal: 15" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 15" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind17">
<DAI desc="DDB Ordinal: 16" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 16" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind18">
<DAI desc="DDB Ordinal: 17" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 17" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind19">
<DAI desc="DDB Ordinal: 18" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 18" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind2">
<DAI desc="DDB Ordinal: 1" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 1" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind20">
<DAI desc="DDB Ordinal: 19" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 19" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind21">
<DAI desc="DDB Ordinal: 20" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 20" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind22">
<DAI desc="DDB Ordinal: 21" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 21" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind23">
<DAI desc="DDB Ordinal: 22" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 22" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind24">
<DAI desc="DDB Ordinal: 23" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 23" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind25">
<DAI desc="DDB Ordinal: 24" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 24" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind26">
<DAI desc="DDB Ordinal: 25" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 25" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind27">
<DAI desc="DDB Ordinal: 26" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 26" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind28">
<DAI desc="DDB Ordinal: 27" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 27" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind29">
<DAI desc="DDB Ordinal: 28" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 28" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind3">
<DAI desc="DDB Ordinal: 2" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 2" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind30">
<DAI desc="DDB Ordinal: 29" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 29" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind31">
<DAI desc="DDB Ordinal: 30" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 30" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind32">
<DAI desc="DDB Ordinal: 31" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 31" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind4">
<DAI desc="DDB Ordinal: 3" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 3" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind5">
<DAI desc="DDB Ordinal: 4" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 4" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind6">
<DAI desc="DDB Ordinal: 5" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 5" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind7">
<DAI desc="DDB Ordinal: 6" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 6" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind8">
<DAI desc="DDB Ordinal: 7" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 7" name="stVal" valKind="RO" />
</DOI>
<DOI name="Ind9">
<DAI desc="DDB Ordinal: 8" name="d" valKind="RO" />
<DAI desc="DDB Ordinal: 8" name="stVal" valKind="RO" />
</DOI>
<DOI name="Mod">
<DAI name="ctlModel" valKind="RO">
<Val>status-only</Val>
</DAI>
<DAI name="stVal" valKind="RO">
<Val>on</Val>
</DAI>
</DOI>
<DOI name="NamPlt">
<DAI desc="[0F 03] - Rly O/P Status" name="d" valKind="RO" />
<DAI desc="[00 11] - Software Ref. 1" name="swRev" valKind="RO" />
<DAI name="vendor" valKind="RO">
<Val>MiCOM</Val>
</DAI>
</DOI>
</LN>
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
<LNodeType id="GGIO_ALM_96" desc="Generic Process I/O (w.r.t 96 Alarm
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Alm1" type="SPS_D" />
<DO name="Alm2" type="SPS_D" />
<DO name="Alm3" type="SPS_D" />
<DO name="Alm4" type="SPS_D" />
<DO name="Alm5" type="SPS_D" />
<DO name="Alm6" type="SPS_D" />
<DO name="Alm7" type="SPS_D" />
<DO name="Alm8" type="SPS_D" />
<DO name="Alm9" type="SPS_D" />
<DO name="Alm10" type="SPS_D" />
<DO name="Alm11" type="SPS_D" />
<DO name="Alm12" type="SPS_D" />
<DO name="Alm13" type="SPS_D" />
<DO name="Alm14" type="SPS_D" />
<DO name="Alm15" type="SPS_D" />
<DO name="Alm16" type="SPS_D" />
<DO name="Alm17" type="SPS_D" />
<DO name="Alm18" type="SPS_D" />
<DO name="Alm19" type="SPS_D" />
<DO name="Alm20" type="SPS_D" />
<DO name="Alm21" type="SPS_D" />
<DO name="Alm22" type="SPS_D" />
<DO name="Alm23" type="SPS_D" />
<DO name="Alm24" type="SPS_D" />
<DO name="Alm25" type="SPS_D" />
<DO name="Alm26" type="SPS_D" />
<DO name="Alm27" type="SPS_D" />
<DO name="Alm28" type="SPS_D" />
<DO name="Alm29" type="SPS_D" />
<DO name="Alm30" type="SPS_D" />
<DO name="Alm31" type="SPS_D" />
<DO name="Alm32" type="SPS_D" />
<DO name="Alm33" type="SPS_D" />
<DO name="Alm34" type="SPS_D" />
<DO name="Alm35" type="SPS_D" />
<DO name="Alm36" type="SPS_D" />
<DO name="Alm37" type="SPS_D" />
<DO name="Alm38" type="SPS_D" />
<DO name="Alm39" type="SPS_D" />
<DO name="Alm40" type="SPS_D" />
<DO name="Alm41" type="SPS_D" />
<DO name="Alm42" type="SPS_D" />
<DO name="Alm43" type="SPS_D" />
<DO name="Alm44" type="SPS_D" />
<DO name="Alm45" type="SPS_D" />
<DO name="Alm46" type="SPS_D" />
<DO name="Alm47" type="SPS_D" />
<DO name="Alm48" type="SPS_D" />
<DO name="Alm49" type="SPS_D" />
<DO name="Alm50" type="SPS_D" />
<DO name="Alm51" type="SPS_D" />
<DO name="Alm52" type="SPS_D" />
<DO name="Alm53" type="SPS_D" />
<DO name="Alm54" type="SPS_D" />
<DO name="Alm55" type="SPS_D" />
<DO name="Alm56" type="SPS_D" />
<DO name="Alm57" type="SPS_D" />
<DO name="Alm58" type="SPS_D" />
<DO name="Alm59" type="SPS_D" />
<DO name="Alm60" type="SPS_D" />
<DO name="Alm61" type="SPS_D" />
<DO name="Alm62" type="SPS_D" />
<DO name="Alm63" type="SPS_D" />
<DO name="Alm64" type="SPS_D" />
<DO name="Alm65" type="SPS_D" />
<DO name="Alm66" type="SPS_D" />
<DO name="Alm67" type="SPS_D" />
<DO name="Alm68" type="SPS_D" />
<DO name="Alm69" type="SPS_D" />
<DO name="Alm70" type="SPS_D" />
<DO name="Alm71" type="SPS_D" />
<DO name="Alm72" type="SPS_D" />
<DO name="Alm73" type="SPS_D" />
<DO name="Alm74" type="SPS_D" />
<DO name="Alm75" type="SPS_D" />
<DO name="Alm76" type="SPS_D" />
<DO name="Alm77" type="SPS_D" />
<DO name="Alm78" type="SPS_D" />
<DO name="Alm79" type="SPS_D" />
<DO name="Alm80" type="SPS_D" />
<DO name="Alm81" type="SPS_D" />
<DO name="Alm82" type="SPS_D" />
<DO name="Alm83" type="SPS_D" />
<DO name="Alm84" type="SPS_D" />
<DO name="Alm85" type="SPS_D" />
<DO name="Alm86" type="SPS_D" />
<DO name="Alm87" type="SPS_D" />
<DO name="Alm88" type="SPS_D" />
<DO name="Alm89" type="SPS_D" />
<DO name="Alm90" type="SPS_D" />
<DO name="Alm91" type="SPS_D" />
<DO name="Alm92" type="SPS_D" />
<DO name="Alm93" type="SPS_D" />
<DO name="Alm94" type="SPS_D" />
<DO name="Alm95" type="SPS_D" />
<DO name="Alm96" type="SPS_D" />
</LNodeType>
<LNodeType id="GGIO_IND_10" desc="Generic Process I/O" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Ind1" type="SPS_D" />
<DO name="Ind2" type="SPS_D" />
<DO name="Ind3" type="SPS_D" />
<DO name="Ind4" type="SPS_D" />
<DO name="Ind5" type="SPS_D" />
<DO name="Ind6" type="SPS_D" />
<DO name="Ind7" type="SPS_D" />
<DO name="Ind8" type="SPS_D" />
<DO name="Ind9" type="SPS_D" />
<DO name="Ind10" type="SPS_D" />
</LNodeType>
<LNodeType id="GGIO_IND_128" desc="Generic Process I/O (w.r.t 64 Indication
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Ind1" type="SPS_D" />
<DO name="Ind2" type="SPS_D" />
<DO name="Ind3" type="SPS_D" />
<DO name="Ind4" type="SPS_D" />
<DO name="Ind5" type="SPS_D" />
<DO name="Ind6" type="SPS_D" />
<DO name="Ind7" type="SPS_D" />
<DO name="Ind8" type="SPS_D" />
<DO name="Ind9" type="SPS_D" />
<DO name="Ind10" type="SPS_D" />
<DO name="Ind11" type="SPS_D" />
<DO name="Ind12" type="SPS_D" />
<DO name="Ind13" type="SPS_D" />
<DO name="Ind14" type="SPS_D" />
<DO name="Ind15" type="SPS_D" />
<DO name="Ind16" type="SPS_D" />
<DO name="Ind17" type="SPS_D" />
<DO name="Ind18" type="SPS_D" />
<DO name="Ind19" type="SPS_D" />
<DO name="Ind20" type="SPS_D" />
<DO name="Ind21" type="SPS_D" />
<DO name="Ind22" type="SPS_D" />
<DO name="Ind23" type="SPS_D" />
<DO name="Ind24" type="SPS_D" />
<DO name="Ind25" type="SPS_D" />
<DO name="Ind26" type="SPS_D" />
<DO name="Ind27" type="SPS_D" />
<DO name="Ind28" type="SPS_D" />
<DO name="Ind29" type="SPS_D" />
<DO name="Ind30" type="SPS_D" />
<DO name="Ind31" type="SPS_D" />
<DO name="Ind32" type="SPS_D" />
<DO name="Ind33" type="SPS_D" />
<DO name="Ind34" type="SPS_D" />
<DO name="Ind35" type="SPS_D" />
<DO name="Ind36" type="SPS_D" />
<DO name="Ind37" type="SPS_D" />
<DO name="Ind38" type="SPS_D" />
<DO name="Ind39" type="SPS_D" />
<DO name="Ind40" type="SPS_D" />
<DO name="Ind41" type="SPS_D" />
<DO name="Ind42" type="SPS_D" />
<DO name="Ind43" type="SPS_D" />
<DO name="Ind44" type="SPS_D" />
<DO name="Ind45" type="SPS_D" />
<DO name="Ind46" type="SPS_D" />
<DO name="Ind47" type="SPS_D" />
<DO name="Ind48" type="SPS_D" />
<DO name="Ind49" type="SPS_D" />
<DO name="Ind50" type="SPS_D" />
<DO name="Ind51" type="SPS_D" />
<DO name="Ind52" type="SPS_D" />
<DO name="Ind53" type="SPS_D" />
<DO name="Ind54" type="SPS_D" />
<DO name="Ind55" type="SPS_D" />
<DO name="Ind56" type="SPS_D" />
<DO name="Ind57" type="SPS_D" />
<DO name="Ind58" type="SPS_D" />
<DO name="Ind59" type="SPS_D" />
<DO name="Ind60" type="SPS_D" />
<DO name="Ind61" type="SPS_D" />
<DO name="Ind62" type="SPS_D" />
<DO name="Ind63" type="SPS_D" />
<DO name="Ind64" type="SPS_D" />
<DO name="Ind65" type="SPS_D" />
<DO name="Ind66" type="SPS_D" />
<DO name="Ind67" type="SPS_D" />
<DO name="Ind68" type="SPS_D" />
<DO name="Ind69" type="SPS_D" />
<DO name="Ind70" type="SPS_D" />
<DO name="Ind71" type="SPS_D" />
<DO name="Ind72" type="SPS_D" />
<DO name="Ind73" type="SPS_D" />
<DO name="Ind74" type="SPS_D" />
<DO name="Ind75" type="SPS_D" />
<DO name="Ind76" type="SPS_D" />
<DO name="Ind77" type="SPS_D" />
<DO name="Ind78" type="SPS_D" />
<DO name="Ind79" type="SPS_D" />
<DO name="Ind80" type="SPS_D" />
<DO name="Ind81" type="SPS_D" />
<DO name="Ind82" type="SPS_D" />
<DO name="Ind83" type="SPS_D" />
<DO name="Ind84" type="SPS_D" />
<DO name="Ind85" type="SPS_D" />
<DO name="Ind86" type="SPS_D" />
<DO name="Ind87" type="SPS_D" />
<DO name="Ind88" type="SPS_D" />
<DO name="Ind89" type="SPS_D" />
<DO name="Ind90" type="SPS_D" />
<DO name="Ind91" type="SPS_D" />
<DO name="Ind92" type="SPS_D" />
<DO name="Ind93" type="SPS_D" />
<DO name="Ind94" type="SPS_D" />
<DO name="Ind95" type="SPS_D" />
<DO name="Ind96" type="SPS_D" />
<DO name="Ind97" type="SPS_D" />
<DO name="Ind98" type="SPS_D" />
<DO name="Ind99" type="SPS_D" />
<DO name="Ind100" type="SPS_D" />
<DO name="Ind101" type="SPS_D" />
<DO name="Ind102" type="SPS_D" />
<DO name="Ind103" type="SPS_D" />
<DO name="Ind104" type="SPS_D" />
<DO name="Ind105" type="SPS_D" />
<DO name="Ind106" type="SPS_D" />
<DO name="Ind107" type="SPS_D" />
<DO name="Ind108" type="SPS_D" />
<DO name="Ind109" type="SPS_D" />
<DO name="Ind110" type="SPS_D" />
<DO name="Ind111" type="SPS_D" />
<DO name="Ind112" type="SPS_D" />
<DO name="Ind113" type="SPS_D" />
<DO name="Ind114" type="SPS_D" />
<DO name="Ind115" type="SPS_D" />
<DO name="Ind116" type="SPS_D" />
<DO name="Ind117" type="SPS_D" />
<DO name="Ind118" type="SPS_D" />
<DO name="Ind119" type="SPS_D" />
<DO name="Ind120" type="SPS_D" />
<DO name="Ind121" type="SPS_D" />
<DO name="Ind122" type="SPS_D" />
<DO name="Ind123" type="SPS_D" />
<DO name="Ind124" type="SPS_D" />
<DO name="Ind125" type="SPS_D" />
<DO name="Ind126" type="SPS_D" />
<DO name="Ind127" type="SPS_D" />
<DO name="Ind128" type="SPS_D" />
</LNodeType>
<LNodeType id="GGIO_IND_18" desc="Generic Process I/O (w.r.t 18 Indication
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Ind1" type="SPS_D" />
<DO name="Ind2" type="SPS_D" />
<DO name="Ind3" type="SPS_D" />
<DO name="Ind4" type="SPS_D" />
<DO name="Ind5" type="SPS_D" />
<DO name="Ind6" type="SPS_D" />
<DO name="Ind7" type="SPS_D" />
<DO name="Ind8" type="SPS_D" />
<DO name="Ind9" type="SPS_D" />
<DO name="Ind10" type="SPS_D" />
<DO name="Ind11" type="SPS_D" />
<DO name="Ind12" type="SPS_D" />
<DO name="Ind13" type="SPS_D" />
<DO name="Ind14" type="SPS_D" />
<DO name="Ind15" type="SPS_D" />
<DO name="Ind16" type="SPS_D" />
<DO name="Ind17" type="SPS_D" />
<DO name="Ind18" type="SPS_D" />
</LNodeType>
<LNodeType id="GGIO_IND_32" desc="Generic Process I/O (w.r.t 32 Indication
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Ind1" type="SPS_D" />
<DO name="Ind2" type="SPS_D" />
<DO name="Ind3" type="SPS_D" />
<DO name="Ind4" type="SPS_D" />
<DO name="Ind5" type="SPS_D" />
<DO name="Ind6" type="SPS_D" />
<DO name="Ind7" type="SPS_D" />
<DO name="Ind8" type="SPS_D" />
<DO name="Ind9" type="SPS_D" />
<DO name="Ind10" type="SPS_D" />
<DO name="Ind11" type="SPS_D" />
<DO name="Ind12" type="SPS_D" />
<DO name="Ind13" type="SPS_D" />
<DO name="Ind14" type="SPS_D" />
<DO name="Ind15" type="SPS_D" />
<DO name="Ind16" type="SPS_D" />
<DO name="Ind17" type="SPS_D" />
<DO name="Ind18" type="SPS_D" />
<DO name="Ind19" type="SPS_D" />
<DO name="Ind20" type="SPS_D" />
<DO name="Ind21" type="SPS_D" />
<DO name="Ind22" type="SPS_D" />
<DO name="Ind23" type="SPS_D" />
<DO name="Ind24" type="SPS_D" />
<DO name="Ind25" type="SPS_D" />
<DO name="Ind26" type="SPS_D" />
<DO name="Ind27" type="SPS_D" />
<DO name="Ind28" type="SPS_D" />
<DO name="Ind29" type="SPS_D" />
<DO name="Ind30" type="SPS_D" />
<DO name="Ind31" type="SPS_D" />
<DO name="Ind32" type="SPS_D" />
</LNodeType>
<LNodeType id="GGIO_IND_32_CTRL" desc="Generic Process I/O (w.r.t 32 Indication
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="SPCSO1" type="SPC_CONTROL" />
<DO name="SPCSO2" type="SPC_CONTROL" />
<DO name="SPCSO3" type="SPC_CONTROL" />
<DO name="SPCSO4" type="SPC_CONTROL" />
<DO name="SPCSO5" type="SPC_CONTROL" />
<DO name="SPCSO6" type="SPC_CONTROL" />
<DO name="SPCSO7" type="SPC_CONTROL" />
<DO name="SPCSO8" type="SPC_CONTROL" />
<DO name="SPCSO9" type="SPC_CONTROL" />
<DO name="SPCSO10" type="SPC_CONTROL" />
<DO name="SPCSO11" type="SPC_CONTROL" />
<DO name="SPCSO12" type="SPC_CONTROL" />
<DO name="SPCSO13" type="SPC_CONTROL" />
<DO name="SPCSO14" type="SPC_CONTROL" />
<DO name="SPCSO15" type="SPC_CONTROL" />
<DO name="SPCSO16" type="SPC_CONTROL" />
<DO name="SPCSO17" type="SPC_CONTROL" />
<DO name="SPCSO18" type="SPC_CONTROL" />
<DO name="SPCSO19" type="SPC_CONTROL" />
<DO name="SPCSO20" type="SPC_CONTROL" />
<DO name="SPCSO21" type="SPC_CONTROL" />
<DO name="SPCSO22" type="SPC_CONTROL" />
<DO name="SPCSO23" type="SPC_CONTROL" />
<DO name="SPCSO24" type="SPC_CONTROL" />
<DO name="SPCSO25" type="SPC_CONTROL" />
<DO name="SPCSO26" type="SPC_CONTROL" />
<DO name="SPCSO27" type="SPC_CONTROL" />
<DO name="SPCSO28" type="SPC_CONTROL" />
<DO name="SPCSO29" type="SPC_CONTROL" />
<DO name="SPCSO30" type="SPC_CONTROL" />
<DO name="SPCSO31" type="SPC_CONTROL" />
<DO name="SPCSO32" type="SPC_CONTROL" />
</LNodeType>
<LNodeType id="GGIO_IND_40" desc="Generic Process I/O (w.r.t 40 Indication
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Ind1" type="SPS_D" />
<DO name="Ind2" type="SPS_D" />
<DO name="Ind3" type="SPS_D" />
<DO name="Ind4" type="SPS_D" />
<DO name="Ind5" type="SPS_D" />
<DO name="Ind6" type="SPS_D" />
<DO name="Ind7" type="SPS_D" />
<DO name="Ind8" type="SPS_D" />
<DO name="Ind9" type="SPS_D" />
<DO name="Ind10" type="SPS_D" />
<DO name="Ind11" type="SPS_D" />
<DO name="Ind12" type="SPS_D" />
<DO name="Ind13" type="SPS_D" />
<DO name="Ind14" type="SPS_D" />
<DO name="Ind15" type="SPS_D" />
<DO name="Ind16" type="SPS_D" />
<DO name="Ind17" type="SPS_D" />
<DO name="Ind18" type="SPS_D" />
<DO name="Ind19" type="SPS_D" />
<DO name="Ind20" type="SPS_D" />
<DO name="Ind21" type="SPS_D" />
<DO name="Ind22" type="SPS_D" />
<DO name="Ind23" type="SPS_D" />
<DO name="Ind24" type="SPS_D" />
<DO name="Ind25" type="SPS_D" />
<DO name="Ind26" type="SPS_D" />
<DO name="Ind27" type="SPS_D" />
<DO name="Ind28" type="SPS_D" />
<DO name="Ind29" type="SPS_D" />
<DO name="Ind30" type="SPS_D" />
<DO name="Ind31" type="SPS_D" />
<DO name="Ind32" type="SPS_D" />
<DO name="Ind33" type="SPS_D" />
<DO name="Ind34" type="SPS_D" />
<DO name="Ind35" type="SPS_D" />
<DO name="Ind36" type="SPS_D" />
<DO name="Ind37" type="SPS_D" />
<DO name="Ind38" type="SPS_D" />
<DO name="Ind39" type="SPS_D" />
<DO name="Ind40" type="SPS_D" />
</LNodeType>
<LNodeType id="GGIO_IND_64" desc="Generic Process I/O (w.r.t 64 Indication
Elements)" lnClass="GGIO">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Ind1" type="SPS_D" />
<DO name="Ind2" type="SPS_D" />
<DO name="Ind3" type="SPS_D" />
<DO name="Ind4" type="SPS_D" />
<DO name="Ind5" type="SPS_D" />
<DO name="Ind6" type="SPS_D" />
<DO name="Ind7" type="SPS_D" />
<DO name="Ind8" type="SPS_D" />
<DO name="Ind9" type="SPS_D" />
<DO name="Ind10" type="SPS_D" />
<DO name="Ind11" type="SPS_D" />
<DO name="Ind12" type="SPS_D" />
<DO name="Ind13" type="SPS_D" />
<DO name="Ind14" type="SPS_D" />
<DO name="Ind15" type="SPS_D" />
<DO name="Ind16" type="SPS_D" />
<DO name="Ind17" type="SPS_D" />
<DO name="Ind18" type="SPS_D" />
<DO name="Ind19" type="SPS_D" />
<DO name="Ind20" type="SPS_D" />
<DO name="Ind21" type="SPS_D" />
<DO name="Ind22" type="SPS_D" />
<DO name="Ind23" type="SPS_D" />
<DO name="Ind24" type="SPS_D" />
<DO name="Ind25" type="SPS_D" />
<DO name="Ind26" type="SPS_D" />
<DO name="Ind27" type="SPS_D" />
<DO name="Ind28" type="SPS_D" />
<DO name="Ind29" type="SPS_D" />
<DO name="Ind30" type="SPS_D" />
<DO name="Ind31" type="SPS_D" />
<DO name="Ind32" type="SPS_D" />
<DO name="Ind33" type="SPS_D" />
<DO name="Ind34" type="SPS_D" />
<DO name="Ind35" type="SPS_D" />
<DO name="Ind36" type="SPS_D" />
<DO name="Ind37" type="SPS_D" />
<DO name="Ind38" type="SPS_D" />
<DO name="Ind39" type="SPS_D" />
<DO name="Ind40" type="SPS_D" />
<DO name="Ind41" type="SPS_D" />
<DO name="Ind42" type="SPS_D" />
<DO name="Ind43" type="SPS_D" />
<DO name="Ind44" type="SPS_D" />
<DO name="Ind45" type="SPS_D" />
<DO name="Ind46" type="SPS_D" />
<DO name="Ind47" type="SPS_D" />
<DO name="Ind48" type="SPS_D" />
<DO name="Ind49" type="SPS_D" />
<DO name="Ind50" type="SPS_D" />
<DO name="Ind51" type="SPS_D" />
<DO name="Ind52" type="SPS_D" />
<DO name="Ind53" type="SPS_D" />
<DO name="Ind54" type="SPS_D" />
<DO name="Ind55" type="SPS_D" />
<DO name="Ind56" type="SPS_D" />
<DO name="Ind57" type="SPS_D" />
<DO name="Ind58" type="SPS_D" />
<DO name="Ind59" type="SPS_D" />
<DO name="Ind60" type="SPS_D" />
<DO name="Ind61" type="SPS_D" />
<DO name="Ind62" type="SPS_D" />
<DO name="Ind63" type="SPS_D" />
<DO name="Ind64" type="SPS_D" />
</LNodeType>
<LNodeType id="LLN0_PROT" desc="Protection Domain Logical Node 0"
lnClass="LLN0">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LLN0" />
<DO name="DifMod" type="INC_CTRL_D_PRIV" />
<DO name="DifBeh" type="INS_BEH_D_PRIV" />
<DO name="DznMod" type="INC_CTRL_D_PRIV" />
<DO name="DznBeh" type="INS_BEH_D_PRIV" />
<DO name="OcpMod" type="INC_CTRL_D_PRIV" />
<DO name="OcpBeh" type="INS_BEH_D_PRIV" />
<DO name="EfmMod" type="INC_CTRL_D_PRIV" />
<DO name="EfmBeh" type="INS_BEH_D_PRIV" />
<DO name="CbfMod" type="INC_CTRL_D_PRIV" />
<DO name="CbfBeh" type="INS_BEH_D_PRIV" />
<DO name="SvnBeh" type="INS_BEH_D_PRIV" />
<DO name="SvnMod" type="INC_CTRL_D_PRIV" />
</LNodeType>
<LNodeType id="LLN0_STANDARD" desc="General Logical Node 0" lnClass="LLN0">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LLN0" />
</LNodeType>
<LNodeType id="LLN0_SYSTEM" desc="System Domain Logical Node 0" lnClass="LLN0">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LLN0" />
<DO name="LEDRs" type="SPC_CONTROL" />
<DO name="OrdRun" type="SPS_WD_NS" />
<DO name="SyncSt" type="SPS_WD_NS" />
</LNodeType>
<LNodeType id="LPHD_STANDARD" desc="Px40 Physical Device Information"
lnClass="LPHD">
<DO name="PhyNam" type="DPL_STANDARD" />
<DO name="PhyHealth" type="INS_HEALTH" />
<DO name="Proxy" type="SPS_D" />
<DO name="PwrUp" type="SPS_D" />
</LNodeType>
<LNodeType id="MMXU_A_18" desc="Standard Measurements for P746 Three-box Mode"
lnClass="MMXU">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="A1" type="WYE_SEG_ANONYMOUS" />
<DO name="A2" type="WYE_SEG_ANONYMOUS" />
<DO name="A3" type="WYE_SEG_ANONYMOUS" />
<DO name="A4" type="WYE_SEG_ANONYMOUS" />
<DO name="A5" type="WYE_SEG_ANONYMOUS" />
<DO name="A6" type="WYE_SEG_ANONYMOUS" />
<DO name="A7" type="WYE_SEG_ANONYMOUS" />
<DO name="A8" type="WYE_SEG_ANONYMOUS" />
<DO name="A9" type="WYE_SEG_ANONYMOUS" />
<DO name="A10" type="WYE_SEG_ANONYMOUS" />
<DO name="A11" type="WYE_SEG_ANONYMOUS" />
<DO name="A12" type="WYE_SEG_ANONYMOUS" />
<DO name="A13" type="WYE_SEG_ANONYMOUS" />
<DO name="A14" type="WYE_SEG_ANONYMOUS" />
<DO name="A15" type="WYE_SEG_ANONYMOUS" />
<DO name="A16" type="WYE_SEG_ANONYMOUS" />
<DO name="A17" type="WYE_SEG_ANONYMOUS" />
<DO name="A18" type="WYE_SEG_ANONYMOUS" />
</LNodeType>
<LNodeType id="MMXU_A_6" desc="Standard Measurements for P746 One-box Mode"
lnClass="MMXU">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="A1" type="WYE_SEG_ANONYMOUS" />
<DO name="A2" type="WYE_SEG_ANONYMOUS" />
<DO name="A3" type="WYE_SEG_ANONYMOUS" />
<DO name="A4" type="WYE_SEG_ANONYMOUS" />
<DO name="A5" type="WYE_SEG_ANONYMOUS" />
<DO name="A6" type="WYE_SEG_ANONYMOUS" />
</LNodeType>
<LNodeType id="MMXU_DERIVED_A_6" desc="Standard Measurements" lnClass="MMXU">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="A1" type="WYE_SEG_ANG" />
<DO name="A2" type="WYE_SEG_ANG" />
<DO name="A3" type="WYE_SEG_ANG" />
<DO name="A4" type="WYE_SEG_ANG" />
<DO name="A5" type="WYE_SEG_ANG" />
<DO name="A6" type="WYE_SEG_ANG" />
</LNodeType>
<LNodeType id="MMXU_FOURIER" desc="Fourier Standard Measurements"
lnClass="MMXU">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="V0" type="MV_FLOAT_NS" />
<DO name="Hz" type="MV_FLOAT_D" />
<DO name="V1" type="MV_FLOAT_NS" />
<DO name="PPV" type="DEL_SEG_ANG" />
<DO name="V2" type="MV_FLOAT_NS" />
<DO name="PhV" type="WYE_SEG_ANG" />
<DO name="VNd" type="WYE_RES_ANG_D_NS" />
</LNodeType>
<LNodeType id="MMXU_IDIFF" desc="Differential Measurements for P746"
lnClass="MMXU">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="ABias" type="WYE_SEG_NS" />
<DO name="ADiff" type="WYE_SEG_NS" />
</LNodeType>
<LNodeType id="MMXU_RMS" desc="Standard Measurements" lnClass="MMXU">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="PhV" type="WYE_SEG" />
</LNodeType>
<LNodeType id="MSQI_SEQ_6" desc="Sequence and Imbalance" lnClass="MSQI">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="SeqA1" type="SEQ_MAG" />
<DO name="SeqA2" type="SEQ_MAG" />
<DO name="SeqA3" type="SEQ_MAG" />
<DO name="SeqA4" type="SEQ_MAG" />
<DO name="SeqA5" type="SEQ_MAG" />
<DO name="SeqA6" type="SEQ_MAG" />
</LNodeType>
<LNodeType id="PDIF_NEU" desc="Differential (w.r.t Neutral)" lnClass="PDIF">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Op" type="ACT_NO_SEG" />
</LNodeType>
<LNodeType id="PDIF_NEU_SEG" desc="Differential" lnClass="PDIF">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Str" type="ACD_SEG" />
<DO name="Op" type="ACT_SEG" />
</LNodeType>
<LNodeType id="PDIF_NEU_SEG_NO_STR" desc="Differential" lnClass="PDIF">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Op" type="ACT_SEG" />
</LNodeType>
<LNodeType id="PTOC_NEU" desc="Timed Overcurrent (w.r.t Neutral)"
lnClass="PTOC">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Str" type="ACD_NO_SEG" />
<DO name="Op" type="ACT_NO_SEG" />
</LNodeType>
<LNodeType id="PTOC_NEU_SEG" desc="Timed Overcurrent" lnClass="PTOC">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Str" type="ACD_SEG" />
<DO name="Op" type="ACT_NO_SEG" />
</LNodeType>
<LNodeType id="PTRC_NO_SEG" desc="Protection Trip Conditioning (w.r.t No Phase
Segregation)" lnClass="PTRC">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="Tr" type="ACT_NO_SEG" />
<DO name="Str" type="ACD_NO_SEG" />
</LNodeType>
<LNodeType id="RBRF_STANDARD" desc="Breaker Failure" lnClass="RBRF">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="OpEx" type="ACT_NO_SEG" />
<DO name="OpIn" type="ACT_NO_SEG" />
</LNodeType>
<LNodeType id="RDRE_BASIC" desc="Disturbance Recorder Function (w.r.t Mandatory
Attributes only)" lnClass="RDRE">
<DO name="Mod" type="INC_MOD" />
<DO name="Beh" type="INS_BEH" />
<DO name="Health" type="INS_HEALTH" />
<DO name="NamPlt" type="LPL_LN" />
<DO name="RcdMade" type="SPS_WD" />
<DO name="FltNum" type="INS_BASIC" />
</LNodeType>
<DOType id="ACD_NO_SEG" desc="Directional Protection Activation Information
(w,r,t No Phase Segregation)" cdc="ACD">
<DA name="general" bType="BOOLEAN" fc="ST" />
<DA name="dirGeneral" bType="Enum" type="dir" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="ACD_SEG" desc="Directional Protection Activation Information (w.r.t
Phase Segregation)" cdc="ACD">
<DA name="general" bType="BOOLEAN" fc="ST" />
<DA name="dirGeneral" bType="Enum" type="dir" fc="ST" />
<DA name="phsA" bType="BOOLEAN" fc="ST" />
<DA name="dirPhsA" bType="Enum" type="dir" fc="ST" />
<DA name="phsB" bType="BOOLEAN" fc="ST" />
<DA name="dirPhsB" bType="Enum" type="dir" fc="ST" />
<DA name="phsC" bType="BOOLEAN" fc="ST" />
<DA name="dirPhsC" bType="Enum" type="dir" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="ACT_NO_SEG" desc="Protection Activation Information (w.r.t No Phase
Segregation)" cdc="ACT">
<DA name="general" bType="BOOLEAN" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="ACT_SEG" desc="Protection Activation Information (w.r.t Phase
Segregation)" cdc="ACT">
<DA name="general" bType="BOOLEAN" fc="ST" />
<DA name="phsA" bType="BOOLEAN" fc="ST" />
<DA name="phsB" bType="BOOLEAN" fc="ST" />
<DA name="phsC" bType="BOOLEAN" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="CMV_MAG_ANG_FLOAT" desc="Phase to phase measurements for a 3-Phase
system (w.r.t Phase Segregation + Angle)" cdc="CMV">
<DA name="cVal" bType="Struct" type="Vector_MagnitudeAngle_Float" fc="MX" />
<DA name="q" bType="Quality" fc="MX" />
<DA name="t" bType="Timestamp" fc="MX" />
<DA name="units" bType="Struct" type="Unit_Multiplier" fc="CF" />
<DA name="db" bType="INT32U" fc="CF" />
<DA name="rangeC" bType="Struct" type="RangeConfig_Deadband" fc="CF" />
</DOType>
<DOType id="DEL_SEG_ANG" desc="Complex Measured value (w.r.t Floating Point
Magnitude and Angle)" cdc="DEL">
<SDO name="phsAB" desc="Measurement values for Phase A to Phase B"
type="CMV_MAG_ANG_FLOAT" />
<SDO name="phsBC" desc="Measurement values for Phase B to Phase C"
type="CMV_MAG_ANG_FLOAT" />
<SDO name="phsCA" desc="Measurement values for Phase C to Phase A"
type="CMV_MAG_ANG_FLOAT" />
</DOType>
<DOType id="DPL_STANDARD" desc="Standard Device Name Plate" cdc="DPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="hwRev" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="serNum" bType="VisString255" fc="DC" />
<DA name="model" bType="VisString255" fc="DC" />
<DA name="location" bType="VisString255" fc="DC" />
</DOType>
<DOType id="INC_CTRL_D_PRIV" desc="Controllable Integer Status (with NameSpace
and description)" cdc="INC">
<DA name="SBO" bType="VisString65" fc="CO" />
<DA name="SBOw" bType="Struct" type="INC_CTRL_D_PRIV_SelectWithValue" fc="CO"
/>
<DA name="Oper" bType="Struct" type="INC_CTRL_D_PRIV_Operate" fc="CO" />
<DA name="Cancel" bType="Struct" type="INC_CTRL_D_PRIV_Cancel" fc="CO" />
<DA name="bypass" bType="Enum" type="Bypass" fc="CO" />
<DA name="origin" bType="Struct" type="Originator" fc="ST" />
<DA name="stVal" bType="Enum" type="Mod" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" bType="Enum" type="ctlModel" fc="CF" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="cdcNs" bType="VisString255" fc="EX" />
<DA name="cdcName" bType="VisString255" fc="EX" />
<DA name="dataNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="INC_MOD" desc="Controllable Integer Status (w.r.t Mode)" cdc="INC">
<DA name="stVal" bType="Enum" type="Mod" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" bType="Enum" type="ctlModel" fc="CF" />
</DOType>
<DOType id="INS_BASIC" desc="Integer Status (w.r.t Mandatory Options only)"
cdc="INS">
<DA name="stVal" bType="INT32" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="INS_BEH" desc="Integer Status (w.r.t Behaviour)" cdc="INS">
<DA name="stVal" bType="Enum" type="Beh" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="INS_BEH_D_PRIV" desc="Integer Status (w.r.t Behaviour, with
Description (Private DO))" cdc="INS">
<DA name="stVal" bType="Enum" type="Beh" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="dataNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="INS_HEALTH" desc="Integer Status (w.r.t health)" cdc="INS">
<DA name="stVal" bType="Enum" type="Health" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="LPL_LLN0" desc="Logical Node 0 Name Plate" cdc="LPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="configRev" bType="VisString255" fc="DC" />
<DA name="ldNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="LPL_LN" desc="Standard Logical Node Name Plate" cdc="LPL">
<DA name="vendor" bType="VisString255" fc="DC" />
<DA name="swRev" bType="VisString255" fc="DC" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="MV_FLOAT_D" desc="Measured value (w.r.t Floating Point Value with
Description)" cdc="MV">
<DA name="mag" bType="Struct" type="AnalogueValue_Float" fc="MX" />
<DA name="q" bType="Quality" fc="MX" />
<DA name="t" bType="Timestamp" fc="MX" />
<DA name="units" bType="Struct" type="Unit_Multiplier" fc="CF" />
<DA name="db" bType="INT32U" fc="CF" />
<DA name="rangeC" bType="Struct" type="RangeConfig_Deadband" fc="CF" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="MV_FLOAT_NS" desc="MV_FLOAT with dataNs for extra Dos" cdc="MV">
<DA name="mag" bType="Struct" type="AnalogueValue_Float" fc="MX" />
<DA name="q" bType="Quality" fc="MX" />
<DA name="t" bType="Timestamp" fc="MX" />
<DA name="units" bType="Struct" type="Unit_Multiplier" fc="CF" />
<DA name="db" bType="INT32U" fc="CF" />
<DA name="rangeC" bType="Struct" type="RangeConfig_Deadband" fc="CF" />
<DA name="dataNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="CMV_MAG_FLOAT" desc="Sequence components of a measurement value"
cdc="CMV">
<DA name="cVal" bType="Struct" type="Vector_Magnitude_Float" fc="MX" />
<DA name="q" bType="Quality" fc="MX" />
<DA name="t" bType="Timestamp" fc="MX" />
<DA name="units" bType="Struct" type="Unit_Multiplier" fc="CF" />
<DA name="db" bType="INT32U" fc="CF" />
<DA name="rangeC" bType="Struct" type="RangeConfig_Deadband" fc="CF" />
</DOType>
<DOType id="SEQ_MAG" desc="Complex Measured value (w.r.t Floating Point
Magnitude)" cdc="SEQ">
<SDO name="c1" desc="Sequence component 1 (For semantic meaning see seqT)"
type="CMV_MAG_FLOAT" />
<SDO name="c2" desc="Sequence component 2 (For semantic meaning see seqT)"
type="CMV_MAG_FLOAT" />
<SDO name="c3" desc="Sequence component 3 (For semantic meaning see seqT)"
type="CMV_MAG_FLOAT" />
<DA name="seqT" bType="Enum" type="seqT" fc="MX" />
</DOType>
<DOType id="SPC_CONTROL" desc="Controllable Single Point" cdc="SPC">
<DA name="SBO" bType="VisString65" fc="CO" />
<DA name="SBOw" bType="Struct" type="SPC_CONTROL_SelectWithValue" fc="CO" />
<DA name="Oper" bType="Struct" type="SPC_CONTROL_Operate" fc="CO" />
<DA name="Cancel" bType="Struct" type="SPC_CONTROL_Cancel" fc="CO" />
<DA name="bypass" bType="Enum" type="Bypass" fc="CO" />
<DA name="origin" bType="Struct" type="Originator" fc="ST" />
<DA name="stVal" bType="BOOLEAN" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="ctlModel" bType="Enum" type="ctlModel" fc="CF" />
<DA name="sboTimeout" bType="INT32U" fc="CF" />
<DA name="cdcNs" bType="VisString255" fc="EX" />
<DA name="cdcName" bType="VisString255" fc="EX" />
</DOType>
<DOType id="SPS_D" desc="Standard Single Point Status (with Description)"
cdc="SPS">
<DA name="stVal" bType="BOOLEAN" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="SPS_WD" desc="Single Point Status (without Description)" cdc="SPS">
<DA name="stVal" bType="BOOLEAN" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
</DOType>
<DOType id="SPS_WD_NS" desc="Single Point Status (without Description, with
Namespace)" cdc="SPS">
<DA name="stVal" bType="BOOLEAN" fc="ST" />
<DA name="q" bType="Quality" fc="ST" />
<DA name="t" bType="Timestamp" fc="ST" />
<DA name="dataNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="WYE_RES_ANG_D_NS" desc="Phase to ground measurements for a 3-Phase
system (w.r.t Residual + Description + Angle)" cdc="WYE">
<SDO name="res" desc="Measurement values for the residual system current"
type="CMV_MAG_ANG_FLOAT" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="dataNs" bType="VisString255" fc="EX" />
</DOType>
<DOType id="WYE_SEG" desc="Phase to ground measurements for a 3-Phase system
(w.r.t Phase Segregation)" cdc="WYE">
<SDO name="phsA" desc="Measurement values for Phase A"
type="CMV_MAG_FLOAT" />
<SDO name="phsB" desc="Measurement values for Phase B"
type="CMV_MAG_FLOAT" />
<SDO name="phsC" desc="Measurement values for Phase C"
type="CMV_MAG_FLOAT" />
</DOType>
<DOType id="WYE_SEG_ANG" desc="Phase to ground measurements for a 3-Phase
system" cdc="WYE">
<SDO name="phsA" desc="Measurement values for Phase A"
type="CMV_MAG_ANG_FLOAT" />
<SDO name="phsB" desc="Measurement values for Phase B"
type="CMV_MAG_ANG_FLOAT" />
<SDO name="phsC" desc="Measurement values for Phase C"
type="CMV_MAG_ANG_FLOAT" />
</DOType>
<DOType id="WYE_SEG_ANONYMOUS" desc="Phase to ground measurements for anonymous
phase of a 3-Phase system" cdc="WYE">
<SDO name="neut" desc="Measurement values for neutral input"
type="CMV_MAG_ANG_FLOAT" />
</DOType>
<DOType id="WYE_SEG_NS" desc="WYE_SEG with dataNs DO" cdc="WYE">
<SDO name="phsA" desc="Measurement values for Phase A"
type="CMV_MAG_FLOAT" />
<SDO name="phsB" desc="Measurement values for Phase B"
type="CMV_MAG_FLOAT" />
<SDO name="phsC" desc="Measurement values for Phase C"
type="CMV_MAG_FLOAT" />
<DA name="d" bType="VisString255" fc="DC" />
<DA name="dataNs" bType="VisString255" fc="EX" />
</DOType>
<DAType id="INC_CTRL_D_PRIV_SelectWithValue" desc="Control Object">
<BDA desc="Control element" name="ctlVal" bType="INT32" />
<BDA desc="Control element" name="origin" bType="Struct" type="Originator" />
<BDA desc="Control element" name="ctlNum" bType="INT8U" />
<BDA desc="Control element" name="T" bType="Timestamp" />
<BDA desc="Control element" name="Test" bType="BOOLEAN" />
<BDA desc="Control element" name="Check" bType="Check" />
</DAType>
<DAType id="INC_CTRL_D_PRIV_Operate" desc="Control Object">
<BDA desc="Control element" name="ctlVal" bType="INT32" />
<BDA desc="Control element" name="origin" bType="Struct" type="Originator" />
<BDA desc="Control element" name="ctlNum" bType="INT8U" />
<BDA desc="Control element" name="T" bType="Timestamp" />
<BDA desc="Control element" name="Test" bType="BOOLEAN" />
<BDA desc="Control element" name="Check" bType="Check" />
</DAType>
<DAType id="INC_CTRL_D_PRIV_Cancel" desc="Control Object">
<BDA desc="Control element" name="ctlVal" bType="INT32" />
<BDA desc="Control element" name="origin" bType="Struct" type="Originator" />
<BDA desc="Control element" name="ctlNum" bType="INT8U" />
<BDA desc="Control element" name="T" bType="Timestamp" />
<BDA desc="Control element" name="Test" bType="BOOLEAN" />
</DAType>
<DAType id="SPC_CONTROL_SelectWithValue" desc="Control Object">
<BDA desc="Control element" name="ctlVal" bType="BOOLEAN" />
<BDA desc="Control element" name="origin" bType="Struct" type="Originator" />
<BDA desc="Control element" name="ctlNum" bType="INT8U" />
<BDA desc="Control element" name="T" bType="Timestamp" />
<BDA desc="Control element" name="Test" bType="BOOLEAN" />
<BDA desc="Control element" name="Check" bType="Check" />
</DAType>
<DAType id="SPC_CONTROL_Operate" desc="Control Object">
<BDA desc="Control element" name="ctlVal" bType="BOOLEAN" />
<BDA desc="Control element" name="origin" bType="Struct" type="Originator" />
<BDA desc="Control element" name="ctlNum" bType="INT8U" />
<BDA desc="Control element" name="T" bType="Timestamp" />
<BDA desc="Control element" name="Test" bType="BOOLEAN" />
<BDA desc="Control element" name="Check" bType="Check" />
</DAType>
<DAType id="SPC_CONTROL_Cancel" desc="Control Object">
<BDA desc="Control element" name="ctlVal" bType="BOOLEAN" />
<BDA desc="Control element" name="origin" bType="Struct" type="Originator" />
<BDA desc="Control element" name="ctlNum" bType="INT8U" />
<BDA desc="Control element" name="T" bType="Timestamp" />
<BDA desc="Control element" name="Test" bType="BOOLEAN" />
</DAType>
<DAType id="AnalogueValue_Float" desc="General analogue value (w.r.t Floating
Point value)">
<BDA desc="Floating point value" name="f" bType="FLOAT32" />
</DAType>
<DAType id="RangeConfig_Deadband" desc="Measurement range configuration">
<BDA desc="High High range limit" name="hhLim" bType="Struct"
type="AnalogueValue_Float" />
<BDA desc="High range limit" name="hLim" bType="Struct"
type="AnalogueValue_Float" />
<BDA desc="Low range limit" name="lLim" bType="Struct"
type="AnalogueValue_Float" />
<BDA desc="Low Low range limit" name="llLim" bType="Struct"
type="AnalogueValue_Float" />
<BDA desc="Minimum process measurement for which values of i and f are
considered within limits" name="min" bType="Struct" type="AnalogueValue_Float" />
<BDA desc="Maximum process measurement for which values of i and f are
considered within limits" name="max" bType="Struct" type="AnalogueValue_Float" />
</DAType>
<DAType id="Unit_Multiplier" desc="SI Unit definitions">
<BDA desc="SI Unit" name="SIUnit" bType="Enum" type="SIUnit" />
<BDA desc="Multiplier value, the default of which is 0 (i.e. multiplier = 1)"
name="multiplier" bType="Enum" type="multiplier" />
</DAType>
<DAType id="Vector_MagnitudeAngle_Float" desc="Complex vector (w.r.t Floating
Point Magnitude and Angle values)">
<BDA desc="The magnitude of the complex value" name="mag" bType="Struct"
type="AnalogueValue_Float" />
<BDA desc="The angle of the complex value (the unit is degrees)" name="ang"
bType="Struct" type="AnalogueValue_Float" />
</DAType>
<DAType id="Originator" desc="Originator of the last change of data attribute
representing the value of a controllable data object">
<BDA desc="Originator category (Not-supported, bay-control, station-control,
remote-control, automatic-bay, automatic-station, automatic-remote, maintenance or
process)" name="orCat" bType="Enum" type="orCategory" />
<BDA desc="Originator identification (Null value indicates unknown or not
reported)" name="orIdent" bType="Octet64" />
</DAType>
<DAType id="Vector_Magnitude_Float" desc="Complex vector (w.r.t Floating Point
Magnitude value)">
<BDA desc="The magnitude of the complex value" name="mag" bType="Struct"
type="AnalogueValue_Float" />
</DAType>
<EnumType id="Beh" desc="Behaviour">
<EnumVal ord="1">on</EnumVal>
<EnumVal ord="2">blocked</EnumVal>
<EnumVal ord="3">test</EnumVal>
<EnumVal ord="4">test/blocked</EnumVal>
<EnumVal ord="5">off</EnumVal>
</EnumType>
<EnumType id="ctlModel" desc="Control Model">
<EnumVal ord="0">status-only</EnumVal>
<EnumVal ord="1">direct-with-normal-security</EnumVal>
<EnumVal ord="2">sbo-with-normal-security</EnumVal>
<EnumVal ord="3">direct-with-enhanced-security</EnumVal>
<EnumVal ord="4">sbo-with-enhanced-security</EnumVal>
</EnumType>
<EnumType id="dir" desc="Direction">
<EnumVal ord="0">unknown</EnumVal>
<EnumVal ord="1">forward</EnumVal>
<EnumVal ord="2">backward</EnumVal>
<EnumVal ord="3">both</EnumVal>
</EnumType>
<EnumType id="Health" desc="Health">
<EnumVal ord="1">Ok</EnumVal>
<EnumVal ord="2">Warning</EnumVal>
<EnumVal ord="3">Alarm</EnumVal>
</EnumType>
<EnumType id="Mod" desc="Mode">
<EnumVal ord="1">on</EnumVal>
<EnumVal ord="2">blocked</EnumVal>
<EnumVal ord="3">test</EnumVal>
<EnumVal ord="4">test/blocked</EnumVal>
<EnumVal ord="5">off</EnumVal>
</EnumType>
<EnumType id="seqT" desc="Sequence Measurement Type">
<EnumVal ord="0">pos-neg-zero</EnumVal>
<EnumVal ord="1">dir-quad-zero</EnumVal>
</EnumType>
<EnumType id="multiplier" desc="Exponents of the multiplier value in base 10.">
<EnumVal ord="-24">y</EnumVal>
<EnumVal ord="-21">z</EnumVal>
<EnumVal ord="-18">a</EnumVal>
<EnumVal ord="-15">f</EnumVal>
<EnumVal ord="-12">p</EnumVal>
<EnumVal ord="-9">n</EnumVal>
<EnumVal ord="-6">µ</EnumVal>
<EnumVal ord="-3">m</EnumVal>
<EnumVal ord="-2">c</EnumVal>
<EnumVal ord="-1">d</EnumVal>
<EnumVal ord="0"></EnumVal>
<EnumVal ord="1">da</EnumVal>
<EnumVal ord="2">h</EnumVal>
<EnumVal ord="3">k</EnumVal>
<EnumVal ord="6">M</EnumVal>
<EnumVal ord="9">G</EnumVal>
<EnumVal ord="12">T</EnumVal>
<EnumVal ord="15">P</EnumVal>
<EnumVal ord="18">E</EnumVal>
<EnumVal ord="21">Z</EnumVal>
<EnumVal ord="24">Y</EnumVal>
</EnumType>
<EnumType id="orCategory" desc="orCategory">
<EnumVal ord="0">not-supported</EnumVal>
<EnumVal ord="1">bay-control</EnumVal>
<EnumVal ord="2">station-control</EnumVal>
<EnumVal ord="3">remote-control</EnumVal>
<EnumVal ord="4">automatic-bay</EnumVal>
<EnumVal ord="5">automatic-station</EnumVal>
<EnumVal ord="6">automatic-remote</EnumVal>
<EnumVal ord="7">maintenance</EnumVal>
<EnumVal ord="8">process</EnumVal>
</EnumType>
<EnumType id="SIUnit" desc="SI Units derived from ISO/IEC 1000">
<EnumVal ord="-16">years</EnumVal>
<EnumVal ord="-15">months</EnumVal>
<EnumVal ord="-14">weeks</EnumVal>
<EnumVal ord="-13">V/s</EnumVal>
<EnumVal ord="-12">mins</EnumVal>
<EnumVal ord="-11">hours</EnumVal>
<EnumVal ord="-10">days</EnumVal>
<EnumVal ord="-9">°F</EnumVal>
<EnumVal ord="-8">ratio</EnumVal>
<EnumVal ord="-7">miles</EnumVal>
<EnumVal ord="-6">inches</EnumVal>
<EnumVal ord="-5">feet</EnumVal>
<EnumVal ord="-4">df/dt</EnumVal>
<EnumVal ord="-3">Hz/s</EnumVal>
<EnumVal ord="-2">%</EnumVal>
<EnumVal ord="-1">pu</EnumVal>
<EnumVal ord="1">none</EnumVal>
<EnumVal ord="2">m</EnumVal>
<EnumVal ord="3">kg</EnumVal>
<EnumVal ord="4">s</EnumVal>
<EnumVal ord="5">A</EnumVal>
<EnumVal ord="6">K</EnumVal>
<EnumVal ord="7">mol</EnumVal>
<EnumVal ord="8">cd</EnumVal>
<EnumVal ord="9">deg</EnumVal>
<EnumVal ord="10">rad</EnumVal>
<EnumVal ord="11">sr</EnumVal>
<EnumVal ord="21">Gy</EnumVal>
<EnumVal ord="22">q</EnumVal>
<EnumVal ord="23">°C</EnumVal>
<EnumVal ord="24">Sv</EnumVal>
<EnumVal ord="25">F</EnumVal>
<EnumVal ord="26">C</EnumVal>
<EnumVal ord="27">S</EnumVal>
<EnumVal ord="28">H</EnumVal>
<EnumVal ord="29">V</EnumVal>
<EnumVal ord="30">ohm</EnumVal>
<EnumVal ord="31">J</EnumVal>
<EnumVal ord="32">N</EnumVal>
<EnumVal ord="33">Hz</EnumVal>
<EnumVal ord="34">lx</EnumVal>
<EnumVal ord="35">Lm</EnumVal>
<EnumVal ord="36">Wb</EnumVal>
<EnumVal ord="37">T</EnumVal>
<EnumVal ord="38">W</EnumVal>
<EnumVal ord="39">Pa</EnumVal>
<EnumVal ord="41">m²</EnumVal>
<EnumVal ord="42">m³</EnumVal>
<EnumVal ord="43">m/s</EnumVal>
<EnumVal ord="44">m/s²</EnumVal>
<EnumVal ord="45">m³/s</EnumVal>
<EnumVal ord="46">m/m³</EnumVal>
<EnumVal ord="47">M</EnumVal>
<EnumVal ord="48">kg/m³</EnumVal>
<EnumVal ord="49">m²/s</EnumVal>
<EnumVal ord="50">W/m K</EnumVal>
<EnumVal ord="51">J/K</EnumVal>
<EnumVal ord="52">ppm</EnumVal>
<EnumVal ord="53">1/s</EnumVal>
<EnumVal ord="54">rad/s</EnumVal>
<EnumVal ord="61">VA</EnumVal>
<EnumVal ord="62">Watts</EnumVal>
<EnumVal ord="63">VAr</EnumVal>
<EnumVal ord="64">phi</EnumVal>
<EnumVal ord="65">cos(phi)</EnumVal>
<EnumVal ord="66">Vs</EnumVal>
<EnumVal ord="67">V²</EnumVal>
<EnumVal ord="68">As</EnumVal>
<EnumVal ord="69">A²</EnumVal>
<EnumVal ord="70">A²t</EnumVal>
<EnumVal ord="71">VAh</EnumVal>
<EnumVal ord="72">Wh</EnumVal>
<EnumVal ord="73">VArh</EnumVal>
<EnumVal ord="74">V/Hz</EnumVal>
</EnumType>
<EnumType id="AddCause" desc="AddCause">
<EnumVal ord="0">Unknown</EnumVal>
<EnumVal ord="1">Not-supported</EnumVal>
<EnumVal ord="2">Blocked-by-switching-hierarchy</EnumVal>
<EnumVal ord="3">Select-failed</EnumVal>
<EnumVal ord="4">Invalid-position</EnumVal>
<EnumVal ord="5">Position-reached</EnumVal>
<EnumVal ord="6">Parameter-change-in-execution</EnumVal>
<EnumVal ord="7">Step-limit</EnumVal>
<EnumVal ord="8">Blocked-by-Mode</EnumVal>
<EnumVal ord="9">Blocked-by-process</EnumVal>
<EnumVal ord="10">Blocked-by-interlocking</EnumVal>
<EnumVal ord="11">Blocked-by-synchrocheck</EnumVal>
<EnumVal ord="12">Command-already-in-execution</EnumVal>
<EnumVal ord="13">Blocked-by-health</EnumVal>
<EnumVal ord="14">1-of-n-control</EnumVal>
<EnumVal ord="15">Abortion-by-cancel</EnumVal>
<EnumVal ord="16">Time-limit-over</EnumVal>
<EnumVal ord="17">Abortion-by-trip</EnumVal>
<EnumVal ord="18">Object-not-selected</EnumVal>
</EnumType>
<EnumType id="Error" desc="Error">
<EnumVal ord="0">No Error</EnumVal>
<EnumVal ord="1">Unknown</EnumVal>
<EnumVal ord="2">Timeout Test Not OK</EnumVal>
<EnumVal ord="3">Operator Test Not OK</EnumVal>
</EnumType>
<EnumType id="Bypass" desc="Bypass">
<EnumVal ord="0">locking-bypass</EnumVal>
<EnumVal ord="1">mode-bypass</EnumVal>
<EnumVal ord="2">automation-bypass</EnumVal>
<EnumVal ord="3">uniqueness-bypass</EnumVal>
<EnumVal ord="4">select-bypass</EnumVal>
<EnumVal ord="5">status-bypass</EnumVal>
</EnumType>
</DataTypeTemplates>
</SCL>