1. Determine the fault currents at different fault conditions from the single-line diagram of the system
is given below. Fault occurs at F. Assume system to be initially on no load.
a) L-G fault.
b) L-L fault.

4. Examine the following power system network for a 3-phase symmetrical fault. A generating
station consisting of two generators, one of 40 MVA, 11kV, 0.20 pu reactance with the unit
transformer of 11/132 kV, 10 MVA, 0.09 pu reactance, and another of 15 MVA, 11 kV,
0.20 pu reactance with the transformer of 11/132 kV, 30 MVA, 0.10 pu reactance, transmits power
over two 132 kV, 3 phase transmission lines each with reactance of 210 ohm per phase. The 132 kV
lines are bussed at both ends. Determine the current in the windings of generators when a 3-phase
symmetrical fault takes place on the 132 kV bus bars at the receiving end station.