You are on page 1of 13

Engineering Structures 23 (2001) 1577–1589

www.elsevier.com/locate/engstruct

Interference effects on wind loads on low-rise hip roof buildings


a,* b
Shakeel Ahmad , Krishen Kumar
a
Department of Civil Engineering, Aligarh Muslim University, Aligarh, India
b
Department of Civil Engineering, University of Roorkee, Roorkee, India

Received 27 November 2000; received in revised form 21 May 2001; accepted 30 May 2001

Abstract

The Natural wind in the wind tunnel was simulated at the University of Roorkee (India) on the basis of full/model-scale compari-
son. For this, the Texas Tech University (TTU) building model was fabricated on a geometric scale of 1:50 and tested in the
simulated wind for comparison of the pressures with full-scale values. A hip roof building model (geometric scale 1:50) of plan
dimensions 280 mm×140 mm×58 mm (eave height) with 30° roof slope was selected as the test building (T.B.) so as to examine
interference with a similar building as well as three similar buildings placed on the upstream side at fifteen different locations (Fig.
2). A quadrant portion of the model roof was divided into ten different zones to see the effect of interference at critical roof
positions. Significant effects have been observed.  2001 Elsevier Science Ltd. All rights reserved.

Keywords: Low-rise structures; Flow simulation; Pressure coefficients; TTU building; Hip roof; Interference

1. Introduction the general relationship which may exist between wind


speed and the distribution of wind pressures over build-
Wind loads for various structure designs are ings of various forms, both under fully exposed con-
invariably obtained from design Codes and Standards. ditions and in close proximity to other buildings. Walker
The wind load specifications in the design Standards are and Roy [21] conducted an experimental study of wind
generally based on wind tunnel tests carried out on iso- loads on houses in an urban environment and compared
lated models. However, wind tunnel studies have the case with an isolated building in open terrain. It was
revealed that wind loads on buildings in realistic situ- concluded that the mean and peak loads and moments
ations may be considerably different from those meas- on the building in question increased. Peterka and Cer-
ured on isolated building models due to the presence of mak [13] examined the effect of four nearby octagonal
neighbouring structures. The flow induced pressures on structures on the wind pressure along the circumference
a building may either decrease or increase depending of a central circular structure. It was observed that
mainly on the geometry and relative position of these adverse effects can be encountered depending on the
structures, their orientation with respect to the direction relative placement of structures in the approaching wind.
of flow and the upstream terrain conditions. This effect Introducing variations in building geometry may
is commonly known as interference, which must be decrease these effects.
properly assessed. Most studies on low-rise buildings in Ho et al. [5] studied the effect of surroundings on
recent years have been focused on buildings free of wind loads on flat roof low buildings. They considered
obstructions in the surroundings. However, most low several cases with different types of immediate sur-
buildings are situated in urban areas in close vicinity to roundings, and concluded that with increase in the sur-
neighbouring buildings and other structures. Studies to rounding obstructions the mean wind pressure acting on
determine the effect of buildings in the immediate vicin- the building decreased (as expected), while unsteady
ity were undertaken early by Bailey et al. [1], who car- pressure increased. Pressures on the building exhibited
ried out tests on a number of model buildings to study large variations, thereby pointing towards the possibility
of large variations in building loads.
Holmes [6,7] studied the effect of grouping of houses
* Corresponding author. Tel.: +91 571 701 297. in characteristic suburban street patterns. A significant

0141-0296/01/$ - see front matter  2001 Elsevier Science Ltd. All rights reserved.
PII: S 0 1 4 1 - 0 2 9 6 ( 0 1 ) 0 0 0 5 7 - 8
1578 S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589

increase in the magnitude of the negative roof pressures difficult. The best that can be expected from more study
occurred when added with one extra half row of houses is a widened database with possibly some kind of gen-
was added to each side of an isolated low-set house. eralization for different “categories” of situations.
He also concluded that the shielding effect of upwind In its extension, a detailed and systematic interference
buildings is dependent strongly on the ratio of building effect study with various combinations of interfering
spacing to height. buildings on the upstream side on 30° hip roof with large
Stathopoulos [15] studied the effect of a tall nearby 1.1 m overhang has been attempted in the present study.
building on the wind loading of low buildings (5, 7.5 30° roof was selected as a test building because it seems
and 10 m high) with gable roofs in a wind tunnel at to be frequently used. The probability distributions of
1:250 geometric scale in two different terrain conditions the critical pressures of the corner and the roof ridge taps
(a=0.14 and a=0.20). The interfering building size was and the standard Gaussian density function have been
38 m×38 m×76 m. The results indicate significant shown in Fig. 8(a) and (b). In Fig. 8(a) there are moder-
increase of the pressure coefficients under conditions of ate deviations from the Gaussian distribution on negative
buffeting caused by a tall building. He further concluded tail, which indicates a higher probability for the larger
that the complexity of the problem of evaluation of wind negative pressures and a lower probability for the larger
loads on low buildings under buffeting conditions indi- positive pressures than a Gaussian distribution function
cates that, with the present state-of-the-art, it would be would predict. However, if compared with the roof ridge
extremely difficult to treat this nearby building situation tap [Fig. 8(b)] the deviation of probability density distri-
with any degree of generality. At present, for building bution from the Gaussian function is much smaller,
code purposes, this problem could be treated by provid- which indicates that very high suction at roof corner
ing possible adverse situations and recommending to occurs than the roof ridge.
seek specialist advice and possibly to perform special
wind tunnel tests. 1.1. Experimental program
In a detailed study on the effect of adjacent low-rise
building blocks on wind pressure distributions and heat Experiments were carried out in an open circuit wind
loss due to uncontrolled ventilation for a single family tunnel having a test section 15 m long, 2.1 m wide and
house, Wiren [22] measured the average pressure coef- 2.0 m high at the University of Roorkee (India).
ficients for two similar low-rise, sloped roof buildings A 30° hip roof model at a geometric scale of 1:50 was
in tandem arrangement vis-à-vis a similar isolated build- constructed representing a building of 14 m×7 m plan
ing for different angles of wind attack. It was found that dimension and having a 2.9 m eave height (Fig. 1) with
one house located upwind of the last house had a sig- a large overhang of 1.1 m. One hundred and twenty-
nificant effect on the pressures over all building surfaces four taps were arranged on the entire 30° roof. Particular
at small wind angles. This effect decreased and became attention has been paid to the number and positions of
negligible (compared to isolated building values) at the taps near the hip ridge, roof ridge and roof edge,
about 30° angle of wind attack for all house surfaces from where the air flow may get separated to form a
except the windward façade walls and at about 90° angle region of high velocity gradients with high local turbu-
of wind attack for the windward façade walls. lence and vorticity.
Kumar [10] studied the interference effect on a gable Models were also constructed to allow testing the
pitched roof building of a similar building and found that effect of a similar building and three similar buildings
the effect of interference is maximum when the spacing upwind of the test building. For the case of a similar
between the two buildings is between 0.25 and 0.50 of interfering building, the test building was placed in such
the width of the building. a way that the wind direction 0° is normal to the ridge.
Stathopoulos [16] carried out wind tunnel tests to Fifteen locations for the interfering building model were
examine the effect of the location of trees in the vicinity designated on the turntable. The schematic diagram for
of a low-rise building and concluded that pressure coef- the locations of the interfering building model is shown
ficients for the building with adjacent trees are generally in Fig. 2. The locations are numbered 1, 2, …, 15. The
lower than those specified by wind standards and codes centre of the interfering model coincides with the centre
of practice. Hussain and Lee [8], Tsutsumiet al. [20] and of the grid at each location. For every location of the
Ho et al. [4] also reported the significant effect of sur- interfering building the angle of wind incidence has been
rounding buildings on wind pressures on low-rise build- varied from 0° to 90° at an increment of 15° and the
ings. Khanduri et al. [9], in their state-of-the-art paper, surface pressure over the building roof measured for
have discussed enormous possible interference effects in each orientation. The observed values of area averaged
low as well as in high rise structures. mean, peak, rms and design wind pressure coefficients
Since numerous situations are possible amongst the for each zone of the building have been normalized by
possible surroundings for a building or group thereof, the corresponding value for the stand-alone (isolated)
generalization of results for the effect of interference is condition. The result is the Interference Factor (IF).
S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589 1579

Fig. 2. Schematic diagram for interfering building positions.

Fig. 1. Model configuration and pressure taps location for hip roof.
Fig. 3. Mean velocity profile comparison between full scale and
model scale (TTU data [2]).

Design pressure coefficients (Cpq)=peak factor∗rms


value+mean value. The peak factor has been calculated position 5 and the third at position 13 as per the grid
from time history of pressure record which, is the ratio numbers marked in Fig. 2.
of peak value and rms value. The mean value of peak The building models were fabricated using 6 mm thick
factor found here was 3. Position of the interfering build- Perspex sheet. Pressure taps 10 mm long, 1.3 mm exter-
ing (x, y) is described in terms of distance of the center nal diameter and 1 mm internal diameter of stainless
of the interfering building from the center of the test steel tubing were inserted into the holes drilled in the
building in longitudinal direction (x), and in transverse Perspex sheet with one end of the tap flush with the
direction (y) in cm. roof surface.
For the case where the effects of three interfering The tubing for measuring the surface pressures con-
buildings were studied, the positions of the interfering sisted of 500 mm vinyl tubes with a 40 mm restrictor
buildings were same as that for a similar building inter- placed at 400 mm from the pressure point. Pressure
ference case. Visualizing the innumerable possible dis- measurements were carried out by using a Scanivalve
positions of the neighbouring buildings in the real life ZOC12, a 32-port pressure scanner having a linear
situation, different possible combinations of interfering response upto 100 Hz. The sampling rate was kept at
buildings were arrived at. All the three interfering build- 375 samples per second per channel and the duration of
ings were placed simultaneously at different locations each run was 32 s.
like 1–5–13, i.e., first building at position 1 second at Natural wind was developed for the 1:50 scale hip
1580 S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589

Fig. 4. Turbulence intensity profile comparison between full scale Fig. 6. Auto correlation plot at eave height.
and model scale (TTU data [2]).

teristic dimension. The reduced spectra plot is shown in


Fig. 5. The integral scale was also evaluated at model
eave height of the longitudinal wind velocity and found
to be 0.45 m. The auto-correlation plot to find the inte-
gral scale is shown in Fig. 6.
To check the reliability of the data, a 1:50 scale model
of the TTU building (Fig. 7) of plan dimension 13.7
m×9.1 m with eave height 4.0 m, was fabricated and
tested in the simulated flow condition and terrain and
the results were compared with the full scale data. It was
observed that the mean, rms and peak pressures are in
good agreement at all the locations except the peak suc-
tions at the corners. Similar results have been reported
by other investigators [3,11,12,14,17–19].

Fig. 5. Normalized reduced spectrum plot at eave height.

roof model to simulate the wind over open country ter-


rain. The simulation was done on the basis of Texas
Tech University (TTU) full-scale data. The velocity pro-
file and the longitudinal Turbulence intensities obtained
in the tunnel are shown in Figs. 3 and 4. The mean longi-
tudinal wind speed profile measured in the wind tunnel
is in good agreement with TTU full-scale profile with a
power law exponent of 0.15. The mean wind velocity
at eave height is 10 m/s. The longitudinal Turbulence
Intensity at the model eave height is 19%, which satisfies
the field condition at eave height. The Small Scale Tur-
bulence Content (S) which is defied as
S=[nSu(n)/s2u][su/U]2×106 evaluated at n=10U/Lp where
n is frequency, Su(n) is spectral density, su is the stan-
dard deviation of the longitudinal mean velocity (U) and
Lp is the characteristic model dimension, is found to be
85. The model eave height has been taken as the charac- Fig. 7. TTU building and its tap locations.
S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589 1581

Fig. 8. Probability density function curve for (a) corner tap and (b) roof ridge tap.

Fig. 9. TTU building, Cpmean, Cprms and Cpmin for roof tap No. 50101.
1582 S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589

2. Results and discussion 2.1.2. Roof tap other than corner tap 50505
Variations of Cpmean, Cprms, Cpmin with angle of wind
2.1. Study of TTU building model incidence are shown in Fig. 10. The values obtained in
the test have been compared with CSU RII flow simu-
2.1.1. Corner roof tap 50101 lated values and TTU full scale values. Values obtained
The observed Cpmean, Cprms and Cpmin have been plot- in the present study have been found to be in better
ted against angle of wind incidence varying from 0° to agreement with the full-scale values than those of the
360° and compared with the prototype values. It has CSU RII experiment. The Cpmin has also been found to
been found that Cpmean and Cprms agree closely with the match closely with the full-scale values for wind azi-
prototype values. However, Cpmin does not show a good muths between 180° and 270°.
match for wind azimuths between 180° and 270° (Fig.
9) but it is well matched with CSU RII flow simulated 2.1.3. Wall tap 42206
values on the same geometric scale. This may be due to The variations of Cpmean, Cprms and Cpmin with angle
conical vortex formation where separation of the air bub- of wind incidence are shown in Fig. 11. The values have
ble started. Similar results have also been reported by been compared with the full-scale values and a good
others [3,11,12,14,17–19]. agreement with the prototype values has been found.

Fig. 10. TTU building, Cpmean, Cprms and Cpmin for roof tap No. 50505.
S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589 1583

Fig. 11. TTU building, Cpmean, Cprms and Cpmin for roof tap No. 42206.

2.2. Interference effect on hip roof models 28) for zone 5 and maximum shielding of 32% was
obtained for position 9 (⫺42, 0) in zone 2 of the roof
2.2.1. A similar building interference (Fig. 14). A maximum increment for Cpmean of 41% was
Both shielding and amplification was observed in the found for interfering building position 10 (⫺42, 28) in
various wind pressure coefficients (Cp) due to inter- zone 1 and a maximum shielding of 34% was found for
ference from similar neighbouring building(s). In the position 9 (⫺42, 0) in zone 2 of the hip roof (Fig. 15).
case of interference from a single building, maximum The maximum values for Cpmean, Cprms, Cpmin and Cpq in
enhancement in the design pressure coefficients (Cpq) each zone with the position of interfering building are
was observed to be 56% for interfering building position given in Tables 1–4.
5 (⫺28, 28) in zone 5 and maximum shielding of 33% In summary, for the interference from a single ident-
was found to occur for interfering building position 9 ical building, the maximum enhancement was found to
(⫺42, 0) in zone 2 of the roof (Fig. 12). Maximum vary from zone to zone for different Cps but the
enhancement of 52% for Cpmin was observed for inter- maximum shielding was found to be in zone 2 in most
fering building position 4 (0, 70) in zone 7 and cases.
maximum shielding of 11% was observed for interfering
building position 9 (⫺42, 0) in zone 2 of the hip roof 2.2.2. Interference from three similar buildings
(Fig. 13). Maximum amplification for Cprms was 66% In the case of interference from three identical build-
and was found for interfering building position 5 (⫺28, ings also, both enhancement and shielding was again
1584 S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589

Fig. 12. Interference factor contours for Cpq for zone 2 and zone 5 of a similar building interference (all azimuths).

Fig. 13. Interference factor contours for Cpmean for zone 2 and zone 7 of a similar building interference (all azimuths).

observed (Table 5). For most of the interfering building 8 and the maximum shielding was found to be 37% for
positions shielding was observed for the different Cps. positions 1–9–14 in zone 1. Maximum enhancement for
The maximum enhancement for Cpq was found to be Cprms was 61% and was observed for interfering building
53% for interfering buildings positions 3–12–14 in zone positions 3–10–12 in zone 6 and the maximum shielding
8 and the maximum shielding of 50% for the same was was 25% for positions 1–9–14 in zones 1 and 2.
observed for building positions 1–9–14 in zone 1. Maximum amplification for Cpmean was 64% and was
Maximum amplification for Cpmin was observed to be found for interfering buildings positions 3–12–14 in
73% for interfering buildings positions 3–9–12 in zone zone 8 whereas maximum shielding of 69% was
S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589 1585

Fig. 14. Interference factor contours for Cprms for zone 2 and zone 5 of a similar building interference (all azimuths).

Fig. 15. Interference factor contours for Cpmean for zone 1 and zone 2 of a similar building interference (all azimuths).

obtained in zone 1 for positions 1–9–14. The maximum positions 3–9–12) of the hip roof for most of the inter-
values for Cpmean, Cprms, Cpmin and Cpq in each zone, with fering building positions (in all 11 sets considered) for
the corresponding positions of interfering buildings are different Cps whereas shielding was found to occur for
given in Tables 6–9. zone 1 and 2 for all Cps for various interfering building
In summary, maximum enhancement in wind press- positions with the maximum shielding for Cpmean
ures due to interference from three identical buildings (IF=0.31) observed for zone1 for interfering building
was observed for zone 8 (IF for Cpmin=1.73 for building positions 3–5–12.
1586 S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589

Table 1 Table 3
Maximum interference factor for Cpq, all azimuths and 30° pitch roof Maximum interference factor for Cprms, all azimuths and 30° pitch roof
(interference with a similar building) (interference with a similar building)

Maximum Location of Maximum Location of


Zone interference interfering building Remarks Zone interfering interfering building Remarks
factor (IF) Na(x, y) factor (IF) Na(x, y)

1 1.46 10 (⫺42, 28) 1 1.47 4 (0, 70)


2 1.11 15 (⫺56, 42) Not significant 2 1.18 15 (⫺56, 42)
3 1.18 6 (⫺28, 42) 3 1.24 6 (⫺28, 42)
4 1.27 1 (0, 28) 4 1.57 5 (⫺28, 28)
5 1.56 5 (⫺28, 28) 5 1.66 5 (⫺28, 28)
6 1.30 10 (⫺42, 28) 6 1.55 10 (⫺42, 28)
7 1.27 8 (⫺28, 70) 7 1.52 4 (0, 70)
8 1.31 6 (⫺28, 42) 8 1.54 4 (0, 70)
9 1.28 5 (⫺28, 28) 9 1.63 3 (0, 56)
10 1.19 15 (⫺56, 42) 10 1.34 10 (⫺42, 28)

Table 2 Table 4
Maximum interference factor for Cpmin, all azimuths and 30° pitch roof Maximum interference factor for Cpmean, all azimuths and 30° pitch
(interference with a similar building) roof (interference with a similar building)

Maximum Location of Maximum Location of


Zone interference interfering building Remarks Zone interference interfering building Remark
factor (IF) Na(x, y) factor (IF) Na(x, y)

1 1.48 15 (⫺56, 42) 1 1.41 10 (⫺42, 28)


2 1.15 15 (⫺56, 42) 2 1.05 4 (0, 70) Not significant
3 1.39 6 (⫺28, 42) 3 1.26 8 (⫺28, 70)
4 1.35 11 (⫺42, 42) 4 1.20 15 (⫺56, 42)
5 1.45 7 (⫺28, 56) 5 1.36 10 (⫺42, 28)
6 1.46 15 (⫺56, 42) 6 1.20 15 9⫺56, 42)
7 1.52 4 (0, 70) 7 1.19 9 (⫺42, 0)
8 1.37 11 (⫺42, 42) 8 1.22 9 (⫺42, 0)
9 1.36 8 (⫺28, 70) 9 1.05 8 (⫺28, 70) Not significant
10 1.24 15 (⫺56, 42) 10 1.12 15 (⫺56, 42) Not significant

3. Conclusion For the case of three interfering buildings, both shield-


ing and enhancement in the pressure coefficients were
also found to occur. However, for most of the interfering
Significant enhancement and shielding were observed building locations, shielding was observed. Maximum
for different positions of a single interfering building. enhancement was found in Cpmin and was 73%. This
Maximum enhancement was observed in the rms value occurred in zone 8. The maximum shielding was 69%
of the pressures (IF=1.66 for zone 5 of the roof) while and was found in Cpmean. This occurred in zone 1 of
maximum shielding was seen in the mean value (IF=0.66 the roof.
for zone 2 of the roof).
S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589 1587

Table 5
Interference factors for different zones (all azimuths) for Cpmean, Cpmin, Cpq and Cprms due to interference with three similar buildings

Location Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10

Cpmean
1–9–10 0.327 0.439 0.865 0.972 1.045 0.885 0.648 0.791 0.784 0.884
1–9–14 0.313 0.446 0.874 0.981 1.082 0.863 0.642 0.811 0.649 0.895
1–13–14 0.332 0.567 0.878 1.007 1.075 0.871 0.697 0.905 0.724 0.943
2–13–15 0.432 0.588 1.099 1.041 1.095 1.107 0.807 1.013 0.731 1.092
2–11–13 0.398 0.519 1.122 0.883 0.949 0.896 1.203 1.512 0.635 0.935
2–9–11 0.343 0.477 1.166 0.870 0.991 0.914 0.968 1.200 0.720 0.935
3–9–12 0.431 0.533 1.251 0.920 1.029 0.902 0.828 1.029 0.847 0.953
3–12–13 0.453 0.559 1.231 0.955 1.006 0.909 0.851 1.046 0.896 1.025
3–12–14 0.463 0.671 1.071 0.974 1.042 1.188 1.292 1.648 0.708 0.995
3–10–12 0.433 0.620 0.983 0.960 1.032 1.219 0.702 0.903 0.732 0.980
3–5–12 0.491 0.662 0.946 0.951 1.038 1.072 0.754 1.955 0.953 0.945
Cpmin
1–9–10 0.808 0.834 1.013 1.196 1.132 1.051 1.102 1.378 1.238 1.119
1–9–14 0.630 0.809 1.062 1.217 1.180 1.114 1.177 1.248 1.194 1.121
1–13–14 0.696 0.729 0.977 1.091 1.117 1.219 1.110 1.360 1.367 1.150
2–13–15 0.737 0.859 1.538 1.203 1.024 1.125 1.329 1.727 1.424 1.244
2–11–13 0.808 0.798 1.478 1.283 1.153 1.101 1.201 1.383 1.139 1.412
2–9–11 0.781 0.872 1.112 1.298 1.216 1.081 1.084 1.410 1.228 1.227
3–9–12 0.851 0.791 1.208 1.192 1.181 1.183 1.533 1.734 1.432 1.195
3–12–13 0.880 0.791 1.206 1.286 1.091 1.053 1.293 1.499 1.457 1.329
3–12–14 0.802 0.903 1.209 1.198 1.174 1.431 1.214 1.550 1.197 1.269
3–10–12 0.853 0.807 1.192 1.192 1.176 1.888 1.107 1.342 1.310 1.341
3–5–12 0.801 0.751 1.026 1.114 1.219 1.298 1.192 1.266 1.473 1.216
Cpq
1–9–10 0.513 0.662 1.088 1.221 1.155 1.041 0.845 1.017 1.047 1.096
1–9–14 0.502 0.613 1.001 1.220 1.260 0.963 0.824 1.016 1.013 1.049
1–13–14 0.544 0.731 1.003 1.200 1.218 0.972 0.922 1.194 1.020 1.065
2–13–15 0.603 0.733 1.100 1.184 1.148 1.096 0.964 1.234 1.064 1.189
2–11–13 0.542 0.659 1.195 1.067 1.069 0.948 1.056 1.325 0.918 1.052
2–9–11 0.509 0.612 1.207 1.123 1.122 0.935 0.977 1.212 0.969 1.053
3–9–12 0.598 0.640 1.229 1.161 1.140 0.912 1.001 1.215 1.087 1.049
3–12–13 0.602 0.695 1.238 1.123 1.100 0.890 1.023 1.236 1.120 1.147
3–12–14 0.625 0.764 1.140 1.151 1.144 1.270 1.168 1.528 0.885 1.216
3–10–12 0.629 0.737 1.165 1.144 1.157 1.359 0.872 1.124 0.924 1.165
3–5–12 ⫺2.61 0.755 1.130 1.131 1.141 1.225 0.916 1.129 1.190 1.113
Cprms
1–9–10 0.765 0.765 0.889 1.274 1.576 1.295 1.296 1.028 1.248 1.343
1–9–14 0.757 0.757 0.782 1.106 1.561 1.485 1.141 0.994 1.224 1.424
1–13–14 0.832 0.899 1.106 1.477 1.398 1.154 1.131 1.488 1.352 1.219
2–13–15 0.833 0.881 1.099 1.390 1.214 1.145 1.109 1.46 1.441 1.317
2–11–13 0.736 0.801 1.254 1.330 1.221 1.066 0.918 1.144 1.238 1.202
2–9–11 0.734 0.749 1.240 1.483 1.286 1.015 0.985 1.228 1.248 1.202
3–9–12 0.825 0.747 1.206 1.507 1.280 0.977 1.162 1.408 1.359 1.172
3–12–13 0.802 0.833 1.240 1.363 1.218 0.917 1.184 1.428 1.375 1.300
3–12–14 0.844 0.860 1.195 1.402 1.274 1.444 1.053 1.412 1.084 1.496
3–10–12 0.893 0.856 1.316 1.408 1.314 1.611 1.030 1.348 1.140 1.398
3–5–12 0.874 0.850 1.285 1.390 1.274 1.485 1.067 1.304 1.457 1.324
1588 S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589

Table 6 Table 9
Maximum interference factor for Cpq, all azimuths and 30° pitch roof Maximum interference factor for Cpmean, all azimuths and 30° pitch
(interference with three similar buildings) roof (interference with three similar buildings)

Maximum Location of Maximum Location of


Zone interference interfering Remarks Zone interference interfering Remarks
factor (IF) buildings factor (IF) buildings

1 0.50 3–5–12 Shielding 1 0.31 3–5–12 Shielding


2 0.61 3–10–12 Shielding 2 0.44 3–12–14 Shielding
3 1.23 3–12–13 3 1.25 3–9–12
4 1.24 3–12–13 4 1.04 2–13–15 Not significant
5 1.26 1–9–14 5 1.09 2–13–15 Not significant
6 1.35 3–10–12 6 1.21 3–10–12
7 1.16 3–12–14 7 1.29 3–12–14
8 1.53 3–12–14 8 1.64 3–12–14
9 1.19 3–5–12 9 0.95 3–5–12 Shielding
10 1.22 3–12–14 10 1.09 2–13–15 Not significant

References
Table 7
Maximum interference factor for Cpmin, all azimuths and 30° pitch roof [1] Bailey PA, Vincent NDG. Wind pressures on building including
(interference with three similar buildings) effects of adjacent buildings. JICE, London 1943;20(8):243–75.
[2] Chok CV. Wind parameters of Texas Tech University field site.
Maximum Location of Master of Science thesis, Civil Engineering Department, Texas
Zone interference interfering Remarks Tech University, 1988.
factor (IF) buildings [3] Cochran LS. Wind tunnel modelling of low-rise structures. PhD
thesis, Colorado State University, 1992.
1 0.63 3–12–13 Shielding [4] Ho TCE, Surry D, Davenport AG. The variability of low-building
2 0.73 3–12–14 Shielding wind loads due to surrounding obstructions. J Wind Eng Ind Aer-
3 1.54 2–13–15 odynam 1990;38:161–70.
4 1.30 2–9–11 [5] Ho TCE, Surry D, Davenport AG. The variability of low-build-
5 1.22 3–5–12 ings wind loads due to surroundings. J Wind Eng Ind Aerodynam
6 1.48 3–10–12 1991;8:39–48.
7 1.53 3–9–12 [6] Holmes JD. Wind loads on low-rise buildings—a review. CSIRO
8 1.73 3–9–12 Division of Building Research, Highett, Victoria, Australia, 1983.
9 1.47 3–5–12 [7] Holmes JD. Wind pressures on tropical housing. J Wind Eng Ind
10 1.41 2–11–13 Aerodynam 1994;53:105–23.
[8] Hussain M, Lee BE. A wind tunnel study of the mean pressure
forces acting on a large group of low-rise buildings. J Wind Eng
Ind Aerodynam 1980;6:207–25.
[9] Khanduri AC, Stathopoulos T, Be’dard. Wind induced inter-
Table 8 ference effects on buildings—a review of the-state-of-the-art. J
Maximum interference factor for Cprms, all azimuths and 30° pitch roof Eng Struct 1998;20(7):617–30.
(interference with three similar buildings) [10] Kumar A. Wind interference amongst low-rise buildings. ME the-
sis, Department of Civil Engineering, University of Roorkee,
Maximum Location of India, 1994.
Zone interference interfering Remarks [11] Lin JX, Surry D, Tieleman HW. The distribution of pressure near
factor (IF) buildings roof corners of flat roof low building. J Wind Eng Ind Aerodynam
1995;56:235–65.
1 0.75 3–10–12 Shielding [12] Okada H, Young CH. Comparison of wind tunnel and full scale
2 0.75 3–12–14 Shielding pressure measurement tests on Texas Tech. building. J Wind Eng
3 1.31 3–10–12 Ind Aerodynam 1992;41-44:1601–12.
4 1.51 3–9–12 [13] Peterka JA, Cermak JE. Adverse wind loading induced by adjac-
5 1.57 1–9–10 ent buildings. J Structural Division, ASCE 1976;102(ST3):533–
6 1.61 3–10–12 48.
7 1.29 1–9–10 [14] Rofail AW. Full-scale/model scale comparison of wind pressures
8 1.43 3–12–13 on TTU building. In: 9th International Conference on Wind
9 1.45 3–5–12 Engineering, New Delhi, 1995. p. 1055–66.
10 1.49 3–12–14 [15] Stathopoulos T. Adverse wind load on low building due to buf-
feting. J Struct Eng ASCE 1984;110(10):2374–92.
[16] Stathopoulos T. Wind effects on low-buildings shielded by trees.
In: Proc. 1st Europeon African Regional Conference, Guernsey,
1993.
[17] Tieleman HW. Model/full scale comparison of pressures on the
S. Ahmad, K. Kumar / Engineering Structures 23 (2001) 1577–1589 1589

roof of the TTU experimental building. J Wind Eng Ind Aerody- [21] Walker GR, Roy RJ. Wind loads on houses in an urban enviorn-
nam 1996;65:133–42. ment. In: Asia Pacific Symposium on wind engineering, Univer-
[18] Tieleman HW, Hajj MR, Reinhold TA. (1997), Wind tunnel sity of Roorkee, India, 1985.
simulation requirements to assess wind loads on low-rise build- [22] Wiren BG. Effect of surrounding buildings on wind pressure dis-
ings. In: Proc. 2EACWE, Geneva, Italy, 1997. p. 1093–1100. 1
[19] Tieleman HW, Surry D, Mehta KC. Full/model scale comparison tributions Part—I, 1 storey detached houses. Publication bulletin
2
of surface pressures on Texas Tech. experimental building. J M85: 19, the National Swedish Institute for building research,
Wind Eng Ind Aerodynam 1996;61:1–23. 1985.
[20] Tsutsumi J, Katayania T, Nishida M. Wind tunnel tests of wind
pressure on regular alinged buildings. J Wind Eng Ind Aerody-
nam 1992;41-44:1799–810.

You might also like