Control Output 1
Indication Accuracy
• Relay output
• Thermocouple input:
• Voltage output (for driving SSR)
±0.3% of PV
• Current output
• Pt input: ±0.2% of PV
• Analog input:
±0.2% of FS
Control Output 2
• None
Sampling Period • Voltage output (for driving SSR)
• 50 ms
Auxiliary Outputs
Event Inputs •3
• None • PF (shift) Key
•2 • Temperature status display
•4 • Simple programming Transfer Output
• Independent heating and • None
cooling PID control •1
Remote SP Input • Changed parameter display
• None • Display brightness setting
•1
1
E5CC
Model Number Legend
Model
Input Number Legend
Output Fixed option Alarms Order code (48x48mm model)
E5CC-@@ @ @ @ @ -@@@ (Example: E5CC-RX3A5M-000) AC110-240V AC/DC24V
−− − − − − −−−
Temperature
A Out1:
B C D E
F 3 relays E5CC-RX3A5M-000 E5CC-RX3D5M-000
&Analog Relay Event Input 2,
Out2: Heater Burnout SSR E5CC-RX3A5M-001 E5CC-RX3D5M-001
none defect detection
Communication
3-phase heater alarm E5CC-RX3A5M-003 E5CC-RX3D5M-003
Event Input 4 E5CC-RX3A5M-005 E5CC-RX3D5M-005
Event Input 2,
Transfer output E5CC-RX3A5M-006 E5CC-RX3D5M-006
Event Input 2,
Remote SP E5CC-RX3A5M-007 E5CC-RX3D5M-007
Out1: E5CC-QX3A5M-000 E5CC-QX3D5M-000
Voltage Event Input 2,
(pulse) Heater Burnout SSR E5CC-QX3A5M-001 E5CC-QX3D5M-001
Out2: defect detection
none Communication
3-phase heater alarm E5CC-QX3A5M-003 E5CC-QX3D5M-003
Event Input 4 E5CC-QX3A5M-005 E5CC-QX3D5M-005
Event Input 2,
Transfer output E5CC-QX3A5M-006 E5CC-QX3D5M-006
Event Input 2,
Remote SP E5CC-QX3A5M-007 E5CC-QX3D5M-007
Heating and Cooling Control
● Using Heating and Cooling Control
Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.
2
E5CC
Waterproof Packing
Model
Y92S-P8
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.
Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.
Waterproof Cover
Model
Y92A-48N
Note: This Cover complies with IP66 and NEMA 4X waterproofing.
Front panel: IP66 protection.
Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.
3
E5CC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VDC or
Power consumption 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VDC or 2.3 W max. at 24 VDC
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA *
Control
Voltage output
output Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Number of outputs 3
Auxiliary
output N.O. relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V
Number of inputs 2 or 4 (depends on model)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Contact output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 kΩ max, resolution: Approx. 10,000
Setting method Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)
Remote SP input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, simple calculations, temperature status display, simple programming, moving
average of input value, and display brightness setting
-10 to 55°C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65°C (with no condensation or icing)
* You cannot select a relay output or current output for control output 2.
4
E5CC
Input Ranges
●Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Platinum resistance Infrared temperature
Input type Thermocouple
thermometer sensor
10 to 60 to 115 to 140 to
Name Pt100 JPt100 K J T E L U N R S B W PLII 70°C 120°C 165°C 260°C
2300
2300
1800
1800
1700 1700
1700
1600
1500
1400
1300 1300 1300
1300
Temperature range (°C)
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Setting
number
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
●Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Setting number 25 26 27 28 29
5
E5CC
Alarm Outputs
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.
X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP
X X
ON ON The alarm will turn ON if the process value is larger than the
8 Absolute-value upper-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-limit ON ON A standby sequence is added to the absolute-value upper-lim-
10 OFF PV OFF PV
with standby sequence 0 0 it alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-limit
11 OFF PV OFF PV
with standby sequence 0 0 alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute value ON ON This alarm type turns ON the alarm when the set point (SP) is
14 OFF SP OFF SP
upper limit 0 0 higher than the alarm value (X).
X X
SP absolute value ON ON This alarm type turns ON the alarm when the set point (SP) is
15 OFF SP OFF SP
lower limit 0 0 smaller than the alarm value (X).
X X
MV absolute value ON ON This alarm type turns ON the alarm when the manipulated
16 OFF MV OFF MV
upper limit *9 0 0 variable (MV) is higher than the alarm value (X).
X X
MV absolute value ON ON This alarm type turns ON the alarm when the manipulated
17 OFF MV OFF MV
lower limit *9 0 0 variable (MV) is smaller than the alarm value (X).
X X
RSP absolute value ON ON The alarm will turn ON when the remote SP (RSP) is larger
18 OFF RSP OFF RSP
upper limit *10 0 0 than the alarm value (X).
X X
RSP absolute value ON ON The alarm will turn ON when the remote SP (RSP) is smaller
19 OFF RSP OFF RSP
lower limit *10 0 0 than the alarm value (X).
*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
ndependently for each alarm type, and are expressed as “L” and “H.” For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
• Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
L H SP SP L H H SP L • Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| ≥ |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
*6 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174)
H>0, L<0
for information on the operation of the standby sequence.
SP H L |H| ≤ |L|
*7 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No.H174)
*3 Set value: 4, Upper- and lower-limit range for information on the loop burnout alarm (LBA).
Case 1 Case 2 Case 3 (Always OFF) *8 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174)
H<0, L<0 for information on the PV change rate alarm.
L H SP SP L H H SP L *9 When heating/cooling control is performed, the MV absolute upper limit
H<0, L>0 H>0, L<0 H<0, L>0 alarm functions only for the heating operation and the MV absolute lower
|H| < |L| |H| > |L| H L SP |H| ≥ |L| limit alarm functions only for the cooling operation.
*10 This value is displayed only when a remote SP input is used. It functions in
H>0, L<0
both Local SP Mode and Remote SP Mode.
SP H L |H| ≤ |L|
6
E5CC
Characteristics
Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. *1
Indication accuracy Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit
(at the ambient temperature of 23°C) Analog input: ±0.2% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Transfer output accuracy ±0.3% FS max.
Remote SP Input Type ±0.2% FS ±1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3
Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Influence of voltage *2 Analog input: (±1%FS) ±1 digit max.
CT input: (±5% FS) ±1 digit max.
Remote SP input: (±1% FS) ±1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) *4
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *5
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1°C/Ω max. (100 Ωmax.)
Affect of signal source resistance
Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.)
Insulation resistance 20 MΩ min. (at 500 VDC)
Dielectric strength 2,300 VAC, 50 or 60 Hz for 1 min (between terminals with different charge)
resistance 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Malfunction 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Shock resistance 100 m/s2, 3 times each in X, Y, and Z directions
Destruction
Malfunction 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.4 or higher
E5CC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
Setup Tool port
computer with the port on the top panel of the E5CC. *6
Approved standards UL 61010-1, CSA C22.2 No. 611010-1 (evaluated by UL)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and
L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°Cmax. is
not specified. The indication accuracy of B thermocouples in the 400 to 800°Crange is ±3°C max. The indication accuracy of the R and S
thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is ±0.3 of PV or ±3°C,
whichever is greater, ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3 of PV or ±2°C, whichever is greater, ±1 digit max.
*2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100°C max.: ±10°C max.
*4 “EU” stands for Engineering Unit and is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
*5 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*6 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
7
E5CC
500
connection method
300
Communications RS-485 (two-wire, half duplex)
Synchronization
Start-stop synchronization 100
method
Protocol CompoWay/F, or Modbus 50
Baud rate 19200, 38400, or 57600 bps 30
8
E5CC
External Connections
E5CC
Control output 1 E5CC-@@ 3 @ 5 M - @ @ @
Relay output (1) (2) (3) (4) (5) (6)
250 VAC, 3A
↑
(resistive load) Terminal type
Voltage output
(for driving SSR) Auxiliary outputs 1 to 3
12 VDC, 21 mA Control output 2 Relay outputs
Current output
Voltage output Models with 3 auxiliary The E5CC is set for a K-type thermocouple (input type = 5) by
0 to 20 mA DC
4 to 20 mA DC (for driving SSR) outputs: 250 VAC, 2 A default. An input error (s.err) will occur if the input type setting does
Load: 500 Ω max. 12 VDC, 21 mA (resistive load) not agree with the temperature sensor. Check the input type.
3 3 3 3
1 13 7
2 14 8
(5) Sensor (Temperature/Analog) Input 3 15 9
(3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/VDC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
Relay output
Auxiliary outputs 1, 2, 3
: Reinforced insulation
: Functional isolation
9
E5CC
Nomenclature
E5CC Temperature unit
Top View
No.1 display
Setup Tool port
Operation on top panel
indicators No. 2 display
Controllers
E5CC Panel Cutout
4
73.1 Mounted Separately Group Mounted
60 (48 × number of units - 2.5)+1.0
0
48 × 48 1
45+0.6
0
45+0.6
0
LED (SD)
10
Terminal Cover
(E53-COV23)
22 44.8
9.1
10
E5CC
● Waterproof Packing Order the Waterproof Packing separately if it becomes lost or damaged.
Y92S-P8 (for DIN 48 × 48) The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years a rough standard. OMRON shall not be liable for the level of water resistance
if the customer does not perform periodic replacement.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
● Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
25 3
Winding resistance: 18±2 Ω
10.5
10 100Ω
E54-CT3
2.36 dia.
30 RL=10Ω
1
12 dia.
9
100μV
10
40 × 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
100V
Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug ∞
10 factor
1kΩ
10%
Lead 500Ω 3%
1 1%
100mV
18
100Ω
50Ω
• Plug 10
RL=10Ω
1
Approx. 6 dia.
100μV
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)
11
E5CC
Operation
Setting Levels Diagram
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.
O Key once.
Operating
Advanced Function
Setting Level
Used to set application
functions.
Calibration Level
Used to calibrate
the E5CC./E5EC.
*1. To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the PF Setting parameter to a-m (Auto/
Manual).
*2. The No. 1 display will flash in the middle when the keys are pressed for 1 s or longer.
12
E5CC
Error Displays (Troubleshooting)
When an error occurs, the No. 1 display or No. 2 display shows the error code.
Take necessary measure according to the error code, referring the following table.
Display Name Meaning Action Operation
After the error occurs and it is
The input value exceeded the control Check the wiring for input to be sure displayed, the alarm output will
range.* it is wired correctly, not broken, andoperate as if the upper limit was
The input type is not set correctly. not shorted. Also check the input exceeded.
The sensor is disconnected or short- type. It will also operate as if transfer
circuited. If there are no problems in the wiringoutput exceeded the upper limit.
The sensor is not wired correctly. or input type settings, cycle the If an input error is assigned to a
The sensor is not wired. power supply. control output or auxiliary output,
If the display remains the same, theoutput will turn ON when the input
* Control Range replace the Digital Temperature error occurs.
s.err Input error Temperature resistance Controller.
thermometer or thermocouple input: If the display is restored to normal,
The error message will appear in the
display for the PV.
SP Lower Limit - 20°C to SP Upper then the probable cause is external
Limit + 20°C noise affecting the control system. Note: 1. The heating and cooling
(SP Lower Limit - 40°F to SP Upper Check for external noise. control outputs will turn
Limit + 40°F) OFF.
ESIB input: Note: For a temperature resistance 2. When the manual MV, MV
Same as specified input range. thermometer, the input is at stop, or MV at error is
Analog input: considered disconnected if the set, the control output is
Scaling range -5% to 105% A, B, or B’line is broken. determined by the set
value.
This is not an error. It
is displayed when the
[[[[ Below -1,999 control range is wider Control continues and operation is
than the display normal.
range and the PV The value will appear in the display
Display
exceeds the display for the PV.
range -
range. The PV is Refer to the E5CC/E5EC Digital
exceeded
displayed for the Controllers User’s Manual (Cat. No.
range that is given on H174) for information on the
]]]] Above 9,999
the left (the number controllable range.
without the decimal
point).
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
A/D controller must be repaired. outputs, and transfer outputs turn
There is an error in the internal
e333 converter
circuits.
If the display is restored to normal, OFF. (A current output will be approx.
error then a probable cause can be 0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
controller must be repaired. outputs, and transfer outputs turn
Memory There is an error in the internal
e111 error memory operation.
If the display is restored to normal, OFF. (A current output will be approx.
then a probable cause can be 0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
Control continues and operation is
normal.
The error message will appear for the
This error is displayed when the peak following displays.
ffff Overcurrent
current exceeds 55.0 A.
-
Heater Current Value 1 Monitor
Heater Current Value 2 Monitor
Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
The No. 1 display for the following
parameter flashes in Operation Level
ct1 or Adjustment Level.
If there is a HB or HS alarm, the No. Heater Current Value 1 Monitor
ct2 HB or HS
1 display will flash in the relevant - Heater Current Value 2 Monitor
alarm
lcr1 setting level. Leakage Current Value 1 Monitor
lcr2 Leakage Current Value 2 Monitor
However, control continues and
operation is normal.
13
E5CC
Operation
Parameters
The related setting items in each level are described below. If you press the Mode Key at the last setting item, the display will return to the first
setting item in the same level.
M
25 Process Value/Set al-1 Alarm
Leakage Current 2
M M Value 4
M 0.0 Monitor 0
cp Control Period (Heating)
hs1 HS Alarm 1 c-d Derivative Time
M M 20
50.0 40 (Cooling) w3of Work Bit 3 OFF Set the ON/OFF
M
Delay
prst Program Start al4h Alarm Value M output cycle.
M rset Upper Limit 4
M 0
c-cp Control Period (Cooling)
lcr2 Leakage Current
c-db Dead Band M M 20
0 2 Monitor 0.0
w4on Work Bit 4 ON
Delay sktr Soak Time Remain al4l Alarm Value M
M M 0 0 Lower Limit 4
orev
Manual Reset Value M Direct/Reverse Operation
hs2 HS Alarm 2
of-r Clear the offset during M M or-r
50.0 50.0 stabilization of P or PD w4of Work Bit 4 OFF
control. Delay r-s RUN/STOP
o MV Monitor M
M M run 0.0 (Heating)
M alt1 Alarm 1 Type
sp-0 SP 0 hys Hysteresis (Heating) M M 2
0 1.0 w5on Work Bit 5 ON
Press the
Hysteresis settings
Delay c-o MV Monitor M
M M 0.0 (Cooling) O Key alh1 Alarm 1
M
sp-1 SP 1 chys Hysteresis (Cooling) M less than 0.2 Hysteresis
0 1.0 w5of Work Bit 5 OFF 1 s.
Delay M
M M Press the O and M Keys Press the O and M Keys
M
sp-2 SP 2 soak Soak Time for at least 3 s. for at least 1 s.
0 1 w6on Work Bit 6 ON
M
Delay Protect Level Communications Setting Level
M
M Note: The time ta ken to move to the protect level can be
sp-3 SP 3 wt-b Wait Band
adjusted by changing the "Move to protect level time" setting.
Note: Displayed only for models with communications. Changes
are effective after cycling power or after a software reset.
0 off w6of Work Bit 6 OFF
Delay
M Move to Protect Level:
M pmov Displayed only when a password is set.
sp-4 SP 4 mv-s MV at Stop 0 Restricts moving to protect level.
psel Protocol Setting:
0 0.0 w7on Work Bit 7 ON
M cwf
Switches between
Delay CompoWay/F and
M M M Modbus.
mv-e M oapt
Operation/Adjustment Protect:
sp-5 SP 5 MV at PV Error
0
Restricts displaying and modifying menus in u-no Communications
0 0.0 w7of Work Bit 7 OFF operation, adjustment, and manual control levels. 1 Unit No.
M M
Delay M
M
Initial Setting/Communications Protect: M
sp-6 SP 6 sprt SP Ramp Set Value
icpt This protect level restricts movement to the initial
0 off w8on Work Bit 8 ON
1 setting, communicationssetting, and advanced bps Communications
function setting levels. 9.6 Baud Rate
M
Delay M CompoWay/F only
M Setting Change Protect: M
M wtpt
sp-7 SP 7 sprl SP Ramp Fall Value off Protects changes to setups by len Communications
0 same w8of Work Bit 8 OFF
M
operating the front panel keys.
7 Data Length
Delay
M M M
M pfpt PF Key Protect
off
sbit Communications
M 2 Stop Bits
*1. When the PF
Display Changed Parameters
chgp M Setting parameter
off
prty Communications Parity is set to A-M.
M even
Parameter Mask Enable: *2. When the PF
pmsk Displayed only when a M Setting parameter
on parameter mask is set.
14
E5CC
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
alt2 Alarm 2 Type init Parameter Initialization ret Automatic Display rt RT sptr SP Tracking
2 off off Return Time off off
M M M M M
alh2 Alarm 2 Hysteresis mspu Number of Multi-SP brgt Display Brightness hsu HS Alarm Use manl Manual MV Limit
0.2 off Points 3 on off Enable
M M M M M
PV Rate of Change
alt3 Alarm 3 Type spru SP Ramp Time Unit a1lt Alarm 1 Latch hsl HS Alarm Latch pvrp
2 m off off 20 Calculation Period
M M M M M
Heating/Cooling
alh3 Alarm 3 Hysteresis rest Standby Sequence
a2lt Alarm 2 Latch hsh HS Alarm Hysteresis hctm
0.2 a Reset off 0.1 off Tuning Method
M M M M M
alt4 Alarm 4 Type sb1n Auxiliary Output 1 a3lt Alarm 3 Latch lba LBA Detection Time ompw Minimum Output
2 n-o Open in Alarm off 0 1.0 ON/OFF Band
M M M M M
Auxiliary Output 2
alh4 Alarm 4 Hysteresis sb2n a4lt Alarm 4 Latch lbal LBA Level pf PF Setting
0.2 n-o Open in Alarm off 8.0 shft
M M M M M
o1st Control Output 1 sb3n Auxiliary Output 3
prlt Move to Protect Level lbab LBA Band pfd1 Monitor/Setting Item 1
4-20 Signal Type n-o Open in Alarm 3 Time 3.0 1
M M M M M
o2st Control Output 2 sb4n Auxiliary Output 4
cjc Cold Junction out1 Control Output 1 pfd2 Monitor/Setting Item 2
4-20 Signal Type n-o Open in Alarm on Compensation Method o Assignment 0
M M M M M
trst Transfer Output hbu HB ON/OFF a1on Alarm 1 ON Delay out2 Control Output 2
pfd3 Monitor/Setting Item 3
4-20 Signal Type on 0 none Assignment 0
M M M M M
Auxiliary Output 1
tr-t Transfer Output Type hbl Heater Burnout Latch a2on Alarm 2 ON Delay sub1 pfd4 Monitor/Setting Item 4
off off 0 alm1 Assignment 0
Linear output
M M M M M
tr-h Transfer Output hbh Heater Burnout a3on Alarm 3 ON Delay sub2 Auxiliary Output 2
pfd5 Monitor/Setting Item 5
100.0 Upper Limit 0.1 Hysteresis 0 alm2 Assignment 0
M M M M M
tr-l Transfer Output st-b ST Stable Range
a4on Alarm 4 ON Delay sub3 Auxiliary Output 2
spd1 "PV/SP (1)" Display
0 alm3 Assignment
0.0 Lower Limit 15.0 4 Screen Selection
M M M M M
Auxiliary Output 4
ev-1 Event Input alfa α a1of Alarm 1 OFF Delay sub4 Assignment
spd2 "PV/SP (2)" Display
msp0 Assignment 1 0.65 0 alm4 0 Screen Selection
(E5EC only)
M M M M M
ev-2 Event Input tidu Integral/Derivative a2of Alarm 2 OFF Delay alma Integrated Alarm odsl MV Display Selection
stop Assignment 2 1 Time Unit 0 49 Assignment o
M M M M M
ev-3 Event Input at-g AT Calculated Gain a3of Alarm 3 OFF Delay t-u Soak Time Unit pvdp PV Decimal Point
none Assignment 3 0.8 0 m on Display
M M M M M
ev-4 Event Input at-h AT Hysteresis a4of Alarm 4 OFF Delay alsp Alarm SP Selection pvst PV Status Display
Function
none Assignment 4 0.8 0 sp-m off
M M M M M
ev-5 Event Input lcma Limit Cycle MV
mvse MV at Stop and Error rs-t Remote SP Input Type svst SV Status Display
none Assignment 5 20.0 Amplitude off Addition 4-20 off Function
(E5EC only)
M M M M M
ev-6 Event Input inf Input Digital Filter amad Auto/Manual Select rspu Remote SP Enable d.ref Display Refresh Period
none Assignment 6 0.0 off Addition off 0.25
(E5EC only)
M M M M M
sqr Extraction of Square mav Moving Average Count mant Manual Output Method rsph Remote SP Upper limit cmov Move to Calibration
off Root Enable off hold 1300 0 Level
M Move to Advanced M M M M
amov Function Setting Level: o-dp MV Display mani Manual MV Initial Value rspl Remote SP Lower limit
0 Displayed when initial setting/ M
off M0.0 -200
15
E5CC
Safety Precautions
Refer to Safety Precautions for All Digital Temperature Controllers.
CAUTION
Do not touch the terminals while power is being Tighten the terminal screws to the rated torque of
supplied. between 0.43 and 0.58 N•m.
Doing so may occasionally result in minor injury due Loose screws may occasionally result in fire.
to electric shock.
Set the parameters of the product so that they are
Electric shock may occur. Do not touch any cables or suitable for the system being controlled. If they are
connectors with wet hands. not suitable, unexpected operation may occasionally
result in property damage or accidents.
Electric shock, fire, or malfunction may occasionally A malfunction in the product may occasionally make
occur. Do not allow metal objects, conductors, control operations impossible or prevent alarm
cuttings from installation work, or moisture to enter outputs, resulting in property damage.
the Digital Temperature Controller or the Setup Tool To maintain safety in the event of malfunction of the
port or ports. Attach the cover to the front-panel Setup Tool port product, take appropriate safety measures, such as installing a
whenever you are not using it to prevent foreign objects from monitoring device on a separate line.
entering the port.
*1. An SELV circuit is one separated from the power supply withdouble
insulation or reinforced insulation, that does not exceed 30 V r.m.s. and
Do not use the Digital Temperature Controller where 42.4 V peak or 60 VDC.
subject to flammable or explosive gas. Otherwise, *2. A class 2 power supply is one tested and certified by UL as having the
minor injury from explosion may occasionally occur. current and voltage of the secondary output restricted to specific levels.
16
E5CC
17
E5CC
●Measurement Accuracy
1. When extending or connecting the thermocouple lead wire, be
sure to use compensating wires that match the thermocouple Water Proof Packing
types. Panel
2. When extending or connecting the lead wire of the platinum 1. For waterproof mounting, waterproof packing must be installed on
resistance thermometer, be sure to use wires that have low the Controller. Waterproofing is not possible when group mounting
resistance and keep the resistance of the three lead wires the several Controllers. Waterproof packing is not necessary when
same. there is no need for the waterproofing function.
3. Mount the product so that it is horizontally level. 2. Insert the E5CC into the mounting hole in the panel.
4. If the measurement accuracy is low, check to see if input shift has 3. Push the adapter from the terminals up to the panel, and
been set correctly. temporarily fasten the E5CC.
4. Tighten the two fastening screws on the adapter.
●Waterproofing Alternately tighten the two screws little by little to maintain a
The degree of protection is as shown below. Sections without any balance. Tighten the screws to a torque of 0.29 to 0.39 N•m.
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP66, Rear case: IP20, Terminal section: IP00
Mounting the Terminal Cover
●Operating Precautions E5CC
1. It takes approximately two seconds for the outputs to turn ON from
Slightly bend the E53-COV23 Terminal Cover to attach it to the
after the power supply is turned ON. Due consideration must be
given to this time when incorporating Digital Temperature terminal block as shown in the following diagram. The Terminal Cover
Controllers in a sequence circuit. cannot be attached in the opposite direction. E53-COV17 Terminal
2. Make sure that the Digital Temperature Controller has 30 minutes Cover can be also attached.
or more to warm up after turning ON the power before starting Make sure that the "UP" mark is facing up, and then attach the E53-
actual control operations to ensure the correct temperature COV17 Terminal Cover to the holes on the top and bottom of the
display. Digital Temperature Controller.
3. When using self-tuning, turn ON power for the load (e.g., heater)
at the same time as or before supplying power to the Temperature E53-COV17 E53-COV23
Controller. If power is turned ON for the Temperature Controller
before turning ON power for the load, self-tuning will not be
performed properly and optimum control will not be achieved.
4. When starting operation after the Digital Temperature Controller
has warmed up, turn OFF the power and then turn it ON again at
the same time as turning ON power for the load. (Instead of turning
the Digital Temperature Controller OFF and ON again, switching
from STOP mode to RUN mode can also be used.)
5. Avoid using the Controller in places near a radio, television set, or
Adapter
wireless installing. These devices can cause radio disturbances
which adversely affect the performance of the Controller. Terminal Cover
(E53-COV17) Enlarged illustration of
(Sold separately) Terminal Section
18
E5CC
Three-year Guarantee
●Period of Guarantee
The guarantee period of the Unit is three years starting from the date
the Unit is shipped from the factory.
Scope of Guarantee
The Unit is guaranteed under the following operating conditions.
1. Average Operating Temperature (see note): −10°C to 50°C
2. Mounting Method: Standard mounting
Top
Bottom
19
Terms and Conditions of Sale
1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
part of all quotes, agreements, purchase orders, acknowledgments, price lists, BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
catalogs, manuals, brochures and other documents, whether electronic or in PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
writing, relating to the sale of products or services (collectively, the "Products") INTENDED USE. Omron further disclaims all warranties and responsibility of
by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron any type for claims or expenses based on infringement by the Products or oth-
objects to any terms or conditions proposed in Buyer’s purchase order or other erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli-
documents which are inconsistent with, or in addition to, these Terms. gation hereunder shall be, at Omron’s election, to (i) replace (in the form
2. Prices; Payment Terms. All prices stated are current, subject to change with- originally shipped with Buyer responsible for labor charges for removal or
out notice by Omron. Omron reserves the right to increase or decrease prices replacement thereof) the non-complying Product, (ii) repair the non-complying
on any unshipped portions of outstanding orders. Payments for Products are Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
due net 30 days unless otherwise stated in the invoice. the non-complying Product; provided that in no event shall Omron be responsi-
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices ble for warranty, repair, indemnity or any other claims or expenses regarding
sent to Buyer after deducting transportation charges, taxes and duties, and will the Products unless Omron’s analysis confirms that the Products were prop-
be allowed only if (i) the invoice is paid according to Omron’s payment terms erly handled, stored, installed and maintained and not subject to contamina-
and (ii) Buyer has no past due amounts. tion, abuse, misuse or inappropriate modification. Return of any Products by
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or Buyer must be approved in writing by Omron before shipment. Omron Compa-
the maximum legal rate, whichever is less, on any balance not paid within the nies shall not be liable for the suitability or unsuitability or the results from the
stated terms. use of Products in combination with any electrical or electronic components,
5. Orders. Omron will accept no order less than $200 net billing. circuits, system assemblies or any other materials or substances or environ-
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all ments. Any advice, recommendations or information given orally or in writing,
costs involved in, obtaining any government approvals required for the impor- are not to be construed as an amendment or addition to the above warranty.
tation or sale of the Products. See http://www.omron247.com or contact your Omron representative for pub-
7. Taxes. All taxes, duties and other governmental charges (other than general lished information.
real property and income taxes), including any interest or penalties thereon, 14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
imposed directly or indirectly on Omron or required to be collected directly or FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
indirectly by Omron for the manufacture, production, sale, delivery, importa- LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
tion, consumption or use of the Products sold hereunder (including customs WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
duties and sales, excise, use, turnover and license taxes) shall be charged to BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
and remitted by Buyer to Omron. Further, in no event shall liability of Omron Companies exceed the individual
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory price of the Product on which liability is asserted.
to Omron, Omron reserves the right to stop shipments or require satisfactory 15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
security or payment in advance. If Buyer fails to make payment or otherwise their employees from and against all liabilities, losses, claims, costs and
comply with these Terms or any related agreement, Omron may (without liabil- expenses (including attorney's fees and expenses) related to any claim, inves-
ity and in addition to other remedies) cancel any unshipped portion of Prod- tigation, litigation or proceeding (whether or not Omron is a party) which arises
ucts sold hereunder and stop any Products in transit until Buyer pays all or is alleged to arise from Buyer's acts or omissions under these Terms or in
amounts, including amounts payable hereunder, whether or not then due, any way with respect to the Products. Without limiting the foregoing, Buyer (at
which are owing to it by Buyer. Buyer shall in any event remain liable for all its own expense) shall indemnify and hold harmless Omron and defend or set-
unpaid accounts. tle any action brought against such Companies to the extent based on a claim
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation that any Product made to Buyer specifications infringed intellectual property
unless Buyer indemnifies Omron against all related costs or expenses. rights of another party.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery 16. Property; Confidentiality. Any intellectual property in the Products is the exclu-
resulting from causes beyond its control, including earthquakes, fires, floods, sive property of Omron Companies and Buyer shall not attempt to duplicate it
strikes or other labor disputes, shortage of labor or materials, accidents to in any way without the written permission of Omron. Notwithstanding any
machinery, acts of sabotage, riots, delay in or lack of transportation or the charges to Buyer for engineering or tooling, all engineering and tooling shall
requirements of any government authority. remain the exclusive property of Omron. All information and materials supplied
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron: by Omron to Buyer relating to the Products are confidential and proprietary,
a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship and Buyer shall limit distribution thereof to its trusted employees and strictly
except in “break down” situations. prevent disclosure to any third party.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall 17. Export Controls. Buyer shall comply with all applicable laws, regulations and
constitute delivery to Buyer; licenses regarding (i) export of products or information; (iii) sale of products to
c. All sales and shipments of Products shall be FOB shipping point (unless oth- “forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of
erwise stated in writing by Omron), at which point title and risk of loss shall regulated technology or information.
pass from Omron to Buyer; provided that Omron shall retain a security inter- 18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
est in the Products until the full purchase price is paid; and no course of dealing between Buyer and Omron shall operate as a waiver
d. Delivery and shipping dates are estimates only; and of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
e. Omron will package Products as it deems proper for protection against nor- without Omron's written consent. (c) Law. These Terms are governed by the
mal handling and extra charges apply to special conditions. law of the jurisdiction of the home office of the Omron company from which
12. Claims. Any claim by Buyer against Omron for shortage or damage to the Buyer is purchasing the Products (without regard to conflict of law princi-
Products occurring before delivery to the carrier must be presented in writing ples). (d) Amendment. These Terms constitute the entire agreement between
to Omron within 30 days of receipt of shipment and include the original trans- Buyer and Omron relating to the Products, and no provision may be changed
portation bill signed by the carrier noting that the carrier received the Products or waived unless in writing signed by the parties. (e) Severability. If any provi-
from Omron in the condition claimed. sion hereof is rendered ineffective or invalid, such provision shall not invalidate
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
Products will be free from defects in materials and workmanship for a period of against the amount owing in respect of this invoice. (g) Definitions. As used
twelve months from the date of sale by Omron (or such other period expressed herein, “including” means “including without limitation”; and “Omron Compa-
in writing by Omron). Omron disclaims all other warranties, express or implied. nies” (or similar words) mean Omron Corporation and any direct or indirect
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, subsidiary or affiliate thereof.
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
OMRON ELECTRONICS DE MEXICO • SALES OFFICE OTHER OMRON LATIN AMERICA SALES
Apodaca, N.L. • 52.81.11.56.99.20 • 001.800.556.6766 • mela@omron.com 54.11.4783.5300
OMRON EUROpE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • Tel: +31 (0) 23 568 13 00 • Fax: +31 (0) 23 568 13 88 • www.industrial.omron.eu
Cat. No. H177-E5CC-E-01 11/11 Note: Specifications are subject to change. © 2011 Omron Electronics LLC Printed in U.S.A.