You are on page 1of 1

 How to Replace and Reload a VCMI board on a Mark VI

Status: published 

Document Audience: GE Internal and Customer

Environment

Mark VI
Resolution

1. If a VCMI has failed the rack should be powered down
and the IONet connector unplugged from the board front leaving the
network still running through the T­fitting. 

2. Loosen the top and bottom screws on the VCMI board.

3. Use the upper and lower ejector tabs to disengage the controller from the backplane

4. Remove the VCMI and replace it with a spare VCMI.

5. Use the upper and lower ejector tabs to install the new VCMI board.

6. Tighten the top and bottom screws to secure the new VCMI or VPRO to the VME rack.

7. Power up the VME rack.

8. From the toolbox Outline View under item Mark VI I/O locate the failed rack.
Locate the VCMI which is usually under the simplex rack and right­click the VCMI.

9. From the shortcut menu click Download. The topology downloads into the new board.
1/2

10. Cycle power to the rack to establish communication with the controller.

This is also available in System Manual GEH6421 Vol-I. U need not download the firmware in the first place

Wish u good Luck!