SUBJECT RECENT FAQs

Family: PTSOL
CONTENTS Range: PTMET
Question:

What is the measurement accuracy of PM5570 meter.


Answer:
Measurement accuracy

Apparent power +/- 0.5 %


FAQ1 Frequency +/- 0.05 %
Active energy +/- 0.2 %
Reactive energy +/- 1 %
Active power +/- 0.2 %
Voltage +/- 0.1 %
Power factor +/- 0.05 %
Current +/- 0.15 °C
Family: PTSOL
CONTENTS Range: PTMET

Question:

What communication protocols are available in PM5570 meter.


Answer:

FAQ2 Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation
2500 V
JBUS Modbus
TCP/IP at 10/100 Mbit/s, insulation 2500 V
Ethernet Modbus TCP/IP daisy chain
BACnet IP.

Find the answers you need with our new FAQ Technical Knowledge base. Over 6000 regularly up-
dated FAQs available.
http://www.schneider-electric.co.in/sites/india/en/support/faq/faq_main.page

Technical Support Team India


SUBJECT TECHNOTES

CONTENTS
Configure PM5000 Series Meter Using EcoStruxure Power Commission

This procedure explain method about configuration of PM5000

TECHNICAL
NOTE

Click Here Check out this Video!

▪ Application Assistance.
CUSTOMER ▪ Configuration
VALUE ▪ Troubleshooting

Technical Support Team India

You might also like