NOJA-523-12
USER MANUAL
®
NOJA Power
Switchgear
Revision History
Rev Author Date Comment
1 BOS 08-03-04 First Release
2 BOS 16-04-04 Clarified directional protection sections. Fixed typographical errors.
3 BOS 18-11-04 Added Delayed Close Feature. Corrected directional protection section.
4 BOS 14-4-05 Added minimum bending radius for control cable. Changed PSM input voltage
fluctuation from +/-25% to +/-20%. Added OSM coil, sensor and microswitch
measurements into troubleshooting section.
5 BOS 17-11-05 Clarified I/O description and wiring diagram. Added palm connector. Added VT to
installation drawings.
6 BOS 1-02-06 Added new feature to CO Operation log. Added note to IO Wiring drawing.
7 KL 20-07-06 Add appendix D, timing details, cable bend radius, minor edits.
8 KL 15-05-07 Add battery option. Update images. Update Loss of Supply Detector, protection
accuracy note, CLP element. Add note to UV alert. Clarify diagnostic warning and
caution.
9 BOS 14-05-08 Added new features – External Load Reset Time, Single Shot Timer, SCADA
GMT/Local time. Added new IEC60870-5-101 SCADA protocol.
10 BOS 20-05-09 Added Auto Open functionality to the ABR section. Added extra TCC curves.
11 BOS 1-02-10 Added OSM Disconnected status. Removed model 079 tank.
12 BOS 20-10-10 Added ABR Auto Open by power flow reduction/direction change. Added Loss of
Supply Reclosing Mode (LSRM). Added UV3 Auto Close. Added range extension
for External Load Time.
NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear Pty Ltd. This document is
copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains
information that is the intellectual property of NOJA Power Switchgear and the document, or any part
thereof, should not be copied or reproduced in any form without written permission from NOJA Power
Switchgear.
NOJA Power® is a registered trademark of NOJA Power Switchgear and should not be reproduced or
used in any way without written authorisation.
NOJA Power Switchgear applies a policy of ongoing development and reserves the right to change product
without notice. NOJA Power Switchgear does not accept any responsibility for loss or damage incurred as a
result of acting or refraining from action based on information in this User Manual.
CONTENTS
1 INTRODUCTION ......................................................................................................................................... 1
1.1 APPLICABILITY ...................................................................................................................................................... 1
1.1.1 MPM Firmware ............................................................................................................................................................... 1
1.1.2 TELUS Software .............................................................................................................................................................. 1
1.2 SAFETY INFORMATION .......................................................................................................................................... 1
1.2.1 Personnel Competence .................................................................................................................................................... 1
1.2.2 Hazard Statements ........................................................................................................................................................... 2
1.2.3 Safety Instructions ........................................................................................................................................................... 2
1.3 ACCEPTANCE AND INITIAL INSPECTION ................................................................................................................. 2
2 SPECIFICATIONS ....................................................................................................................................... 3
2.1 OSM AUTOMATIC CIRCUIT RECLOSER ................................................................................................................. 3
2.1.1 Basic Operating Parameters ........................................................................................................................................... 3
2.1.2 Ratings ............................................................................................................................................................................. 3
2.1.3 Sensor Accuracy .............................................................................................................................................................. 3
2.1.4 Breaking Duty.................................................................................................................................................................. 4
2.2 RECLOSER CONTROL (RC) CUBICLE ..................................................................................................................... 5
2.2.1 Basic Operating Parameters ........................................................................................................................................... 5
2.2.2 Measurement Accuracy ................................................................................................................................................... 5
2.2.3 Filtering ........................................................................................................................................................................... 6
2.2.4 Protection Accuracy ........................................................................................................................................................ 6
2.2.5 Electromagnetic Compatibility (EMC) Performance ...................................................................................................... 7
2.2.6 Power Supply Module (PSM) .......................................................................................................................................... 7
2.2.7 I/O module ....................................................................................................................................................................... 8
2.2.8 Rechargeable battery....................................................................................................................................................... 8
3 OSM AUTOMATIC CIRCUIT RECLOSER ................................................................................................. 9
3.1.1 Overview.......................................................................................................................................................................... 9
3.1.2 Cross Section Diagram: .................................................................................................................................................. 9
3.1.3 Dimensions: OSM15-200 and OSM27-203 ................................................................................................................... 10
3.1.4 Main Circuit Bushings ................................................................................................................................................... 11
3.1.5 Current and Voltage Sensing ......................................................................................................................................... 11
3.1.6 Mechanical Trip ............................................................................................................................................................ 11
3.1.7 Position Indicator .......................................................................................................................................................... 11
4 RECLOSER CONTROL (RC) CUBICLE .................................................................................................. 12
4.1 OVERVIEW........................................................................................................................................................... 12
4.1.1 Security Cover ............................................................................................................................................................... 13
4.1.2 Functional Diagram ...................................................................................................................................................... 13
4.2 DIMENSIONS ........................................................................................................................................................ 14
4.3 MAIN PROCESSOR MODULE ................................................................................................................................ 15
4.4 OPERATOR INTERFACE ........................................................................................................................................ 15
4.4.1 General Control Pushbuttons ........................................................................................................................................ 16
4.4.2 LCD Control Pushbuttons ............................................................................................................................................. 17
4.4.3 Fast Keys ....................................................................................................................................................................... 18
4.5 TELUS SOFTWARE ............................................................................................................................................. 19
4.6 AUXILIARY SUPPLY CONNECTION ....................................................................................................................... 19
4.7 COMMUNICATIONS INTERFACE............................................................................................................................ 20
4.7.1 I/O Modules ................................................................................................................................................................... 22
4.7.2 RS-485 Connector ......................................................................................................................................................... 23
4.7.3 RS-232 Connector ......................................................................................................................................................... 23
4.7.4 External Load Power Supply Connection for RTU ........................................................................................................ 23
4.8 UNINTERRUPTIBLE POWER SUPPLY ..................................................................................................................... 24
4.8.1 Power Supply Module.................................................................................................................................................... 24
4.8.2 Settings .......................................................................................................................................................................... 24
4.8.3 Operating States ............................................................................................................................................................ 25
4.8.4 Power Management ....................................................................................................................................................... 25
4.9 DRIVER MODULE................................................................................................................................................. 26
5 MEASUREMENT ....................................................................................................................................... 27
5.1 SAMPLING AND FILTERING .................................................................................................................................. 27
NOJA-523-12
1 Introduction
This manual applies to the range of Automatic Circuit Reclosers and Controls manufactured by NOJA Power.
1.1 Applicability
The following products are covered by this manual:
OSM-15.5-16/630-200 (Automatic Circuit Recloser rated at 15kV)
OSM-27-12.5/630-203 (Automatic Circuit Recloser rated at 27kV)
RC-01ES (recloser control)
Before Installing and / or operating the recloser or control, read and understand the contents of this manual.
Note that this manual cannot cover all the details or variations in the equipment or process being described.
Neither is it expected to address all contingencies associated with installation and operation of this
equipment. For any further information please contact your nearest NOJA Power Office or Distributor.
2 Specifications
2.1 OSM Automatic Circuit Recloser
OSM Automatic Circuit Reclosers comply with the ANSI / IEEE C37.60-2003 standard.
Note: 1. For altitudes above 1000m ratings should be corrected in accordance with ANSI C37.60-2003
2.1.2 Ratings
OSM15-200 OSM27-203
Rated maximum voltage 15.5kV 27kV
Rated continuous current 630A 630A
Fault make capacity RMS 16kA 12.5kA
Fault make capacity Peak 40kA 31.5kA
Fault break capacity 16kA 12.5kA
DC component Interruption capacity 20% 20%
Mechanical operations 30000 30000
Full Load Operations 30000 30000
Fault break capacity operations 200 200
Short time current withstand 4 seconds 16kA 12.5kA
Mainly active breaking capacity 630A 630A
Cable charging current 25A 25A
Line charging current 10A 5A
1
Impulse withstand phase to earth, phase to phase and across the interrupter 110kV 125kV
Power frequency withstand phase to Earth and across the interrupter 50kV 60kV
Closing Time <60ms <60ms
Opening Time <30ms <30ms
Breaking / Interrupting Time (including arcing time) <40ms <40ms
Note: 1. A 150kV BIL option is provided by supplying OSM complete with surge arrestors for each HV terminal and
associated mounting brackets.
The high and low current number of operations for each OSM type is summarised in the table below.
OSM15-200 OSM27-203
Number of operations at rated continuous current 30,000 ops at 630A 30,000 ops at 630A
Number of operations at rated interrupting current 200 ops at 16kA 200 ops at 12.5kA
Weight2, kg 50
Overall Dimensions, (width x height x depth) mm 400 x 1080 x 309
Notes:
1. Without RTU or other communications device
2. Battery and one I/O module included
2.2.3 Filtering
Harmonics rejection rates, not less than
– second 1:100
– third 1:316
– fifth 1:1000
Note: All protection and measurement is carried out on the basis of fundamental frequency values, ie post filtering.
Operational pickup voltage the greater of 1% or 0.1kV 0.5 – 18kV for UV1
0.5 – 30kV for UV2
Restoration time for automatic backfeed the greater of 0.1% ; +1ms 0 – 180s
restoration element
Note 1: Pickup is initiated at 100% of pickup current value and drops off at 97.5% (2.5% difference). When a current
multiplier is applied to the pickup value the same percentage (2.5%) applies to the new calculated value.
Pulse Magnetic Field Immunity (6.4/16 ms) 1000 A/m IEC 61000 – 4 – 9
Input resistance
– for IOM-12/60 3 kΩ
– for IOM-100/250 125 kΩ
Recognition time, ms 20 ms
Transmission time, ms 12 – 19 ms
Reset time, ms 20 ms
Output relay contacts
Rated voltage
– AC 6 – 230 Vac
– DC 4.5 – 125 Vdc
Rated current 16 A
Maximum breaking power
– DC at L/R=1ms 30 W
– AC at power factor 0.3 50 VA
742
750
280 300
1060 (OSM27-203)
960 (OSM15-200)
534
24mm dia
Slots For Strapping
Standard To Concrete Pole
OSM Mounting Bracket
760
Optional
OSM Side Mount Bracket
Earth
Connection
Arc-Fault
Vent IP65 Latching Connector For
Control Cable Connection
Mechanical
Trip Ring
Breather
Position
Indicator
The HV terminals have a tin-plated, brass connector at the end. This connector is suitable for cable sizes
from 40mm2 to 260mm2. Cables are secured in the connector with two hexagonal socket screws. A tin-plated
bronze palm connector can be fitted to the bushing instead if required. This has two holes 44.45mm (1.75”)
apart so a lug can be bolted onto the bushings.
The terminals on the (nominal) source side are marked A, B and C. The terminals furthest from the pole are
correspondingly marked R, S and T. Since operation is by low voltage magnetic actuators, there is no
requirement to have either side terminals energised for operation.
ABER FECH
PC with
TELUS AC Power
software Supply
OSM
Recloser Aux Supply RC
Input Module Cubicle
Phase Vacuum Residual
CS CS RS232
CVS Interrupter CVS
3 Phase HV Line Rechargeable
Battery
UPS
Power
Auxiliary Supply
Trip/Close Main Module
switch Processing
Coil
Module
RS485
RS232
I/O modules
Control Cable
Driver
RTU or
Radio /
modem Comms.
Power
Data
Control / Indication SCADA
4.2 Dimensions
Control Cable
M12 Earth Stud Connector
Breather
BOTTOM VIEW
RS-232
connection for
TELUS
software
ON / OFF
The MMI must be turned on before a user can use it for control and indication. The MMI will automatically
turn itself off again if no operator activity is detected for 5 minutes.
The ON / OFF pushbutton also provides a means of testing the LCD and all indicating diodes. Pressing and
holding will cause all the LED’s to blink and the message “TEST” to cycle through the four lines on the LCD.
Holding any pushbutton and subsequently releasing ON / OFF will cause the test to continue (provided the
pushbutton under test is healthy).
Control Mode
The Control mode pushbutton allows the Recloser Control to be set to either Local Control or Remote
Control mode.
When in Local control mode, indication is available to both local and remote applications but controls can
only be executed locally. When in Remote control mode, indication is available to both local and remote
applications but controls can only be executed by Remote applications. MPM data can still be viewed locally
on the LCD panel.
The exception to this is an Open control, which can be executed locally or remotely, independent of Control
mode.
Note: The MPM can be optionally configured to prevent the Open control from operating independently of the Control
Mode. Please contact NOJA Power or your local distributor if this is required.
‘I’ (Close)
The red pushbutton labelled ‘I’ is used to close the recloser contacts. The control is only executed if the MMI
is set to Local control mode. If the MMI is set to Remote control mode the control will not be accepted and
the LED will not blink.
A delayed close can be programmed into the MMI to allow an operator time to move away from the recloser
if required. A message is displayed on the LCD Panel when the Close button is pushed and the Closed LED
starts blinking. Pressing the ESC key will cancel the close operation otherwise the device will close after the
time delay has expired. Refer to section 8.1.
‘O’ (Open)
The green pushbutton labelled ‘O’ is used to open the recloser contacts. An Open control can be executed in
either Local or Remote mode.
Note: When the OSM tank is disconnected from the cubicle, both Open and Close LEDs are turned off.
Navigation pushbutton
These pushbuttons allow movement through the MMI menu structure and changes to setting values.
Each screen has one of two navigation symbols in the top right hand corner; “” indicates vertical scrolling,
ie the up and down pushbuttons can be used to access information, ”” indicates four way scrolling, ie up,
down, right and left pushbuttons can be used to access information.
Once a field has been selected for editing, the up and down pushbuttons are used to change the value.
Where the value being changed is a number, right and left arrow are used to select each digit, up and down
arrows are used to change the value of that digit only.
Enter pushbutton
The ENTER pushbutton is used to access a field within the data menu once it has been selected, (fields that
are unable to be changed, ie indication only, are bracketed by arrows, )
On pressing ENTER, the LCD will either display the next level screen or surround the selected field with
brackets. Triangular brackets ►◄ indicate another screen is available by pressing enter. Square brackets [ ]
indicate the value is able to be changed via the arrow push buttons.
All settings are password protected except for those accessible using the Fast Keys, refer section 4.4.3. A
request to enter the password is automatically generated when the user tries to edit protected parameters for
the first time after switching the MMI ON.
MMI passwords have the format AAAA, where A can be a digit (from 1 to 9) or a letter (from A to Z). Refer to
section 9.2.3 for an example of how to enter the password.
Escape pushbutton
The ESC pushbutton is used to either move the user back one screen or de–select a variable.
LCD control pushbuttons provide access to the following functions within the MMI menu structure:
view system status: date, time, recloser state (Open/Closed/Lockout), malfunction and warnings
signals, “protection initiated” indication signals. Measurements, I/O status. UPS status, Prot status
view Close/Open (CO) operations record, lifetime and fault counters, protection group settings,
system settings
change protection status, all settings except for protection Group names and PC baud rate
view MPM identification: serial number & software version
test operability of digital input / output (I/O) relays
The Protection Fast Key is used to turn Protection ON or OFF. When set to OFF, all protection
elements for all groups are disabled.
The Earth Fault Fast Key is used to disable or enable all Earth Fault overcurrent elements for
all groups. When set to OFF, all EF elements are disabled.
The Sensitive Earth Fault Fast Key is used to disable or enable all Sensitive Earth Fault
overcurrent elements for all groups.
The Reclosing Fast Key is used to disable or enable all Auto Reclose elements for all groups.
The Cold Load Fast Key is used to disable or enable Cold Load Pickup for all groups.
The Live Line Fast Key is used to enable or disable all Live Line elements for all groups.
The Active Group Fast Key is used to select which of the four Protection Groups is active.
Once the appropriate group has been chosen (indicated by flashing LED), press ENTER to
make it active.
The Active Protection group cannot be changed if a protection element pickup occurs. Where
this happens subsequent to pressing ENTER, the new group will become active once all
protection elements have reset.
The pre set auxiliary supply voltage can be determined by referring to the advisory information that appears
next to the PSM XS15 connector and comparing that to the actual link configuration.
The diagram below shows links installed for a 220Vac auxiliary supply.
All RC Cubicle connectors, with the exception of the auxiliary supply active and neutral connections, utilise
cage clamps which will accept solid or multi-stranded cable with cross section up to 2.5mm2. The cage clamp
installation method is illustrated in the diagram below.
IOM-XP1
Contact Signal Designation
1 COM1 Common for Inputs
2 In1 Input 1
3 IN2 Input 2
4 IN3 Input 3
5 IN4 Input 4
6 IN5 Input 5
7 IN6 Input 6
10 COM2 Common for Outputs 1 - 5
11 K1-12 Output 1.1
12 K1-14 Output 1.2
13 K2-12 Output 2.1
14 K2-14 Output 2.2
15 K3-12 Output 3.1
16 K3-14 Output 3.2
17 K4-12 Output 4.1
18 K4-14 Output 4.2
19 K5-12 Output 5.1
20 K5-14 Output 5.2
22 K6-12 Output 6.1
23 K6-14 Output 6.2
24 COM3 Common for Output 6
RS485 connector-XS1
Contact Signal Designation
1 +12V_EXT +12V for RTU
2 GND GROUND
3 TX+ TRANSMITTER 1.1
4 TX- TRANSMITTER 1.2
5 RX+ RECEIVER 1.1
6 RX- RECEIVER 1.2
7 EARTH EARTH
RS232 connector-X9
Pin Signal
1 DCD
2 RX
3 TX
4 DTR
5 GND
6 DSR
7 RTS
8 CTS
9 RI
Note:
Inputs are polarity sensitive.
Switch the +ve side only, not the
–ve common.
Using TELUS software, any available control can be programmed for each input, refer to section 8 for a
complete list of controls available for the IOM. Any combination of eight available indications can be
programmed for each output, refer section 11.4 for a complete list of available indications. Default control
and indication settings for the two modules are listed in section 8.4
Connector Connector
IOM-XP1 IOM-XP2
Captive Captive
screw screw
The IOM–XP1 connector has terminals for user installed input and output wiring.
The IOM–XP2 connector carries control and indication signals from the Main Processing Module and
connects to the RC wiring loom.
ON
.
OFF SYSTEM STATUS
28/12/01 13 : 14: 26
Closed Grp 4 ME
I/O UPS Prot UPS STATUS
SCADA
1-st ACsettings
SCADA input On
2-nd AC input Off
ENTER Ubt, V 12.1
Ibt, A +0.13
Cbt 0.87
Ext.load [Off]
4.8.2 Settings
ON
OFF
.
SYSTEM STATUS SYSTEM SETTINGS
28/12/01 13:14:26 ME settings
Closed Grp 4 ME I/O settings
I/O UPS Prot UPS settings
SCADA SCADA settings
PC settings
RTC settings ENTER
ESC
MAIN MENU MMI settings
System status ENTER
Groups settings
System settings
CO operations
Counters
Identification UPS SETTINGS
Erase data Shutdown level 0.2
Change password C_rated, A*h 26
Switch power Off T_Ext, min 120
Tres_Ext, hrs 000
5 Measurement
The Main Processing Module (MPM) converts analogue signals originating at the OSM into data as indicated
in the table below. The measurement data is filtered for harmonic content and the RMS value of the
fundamental signal is used by Protection and Indication applications as shown in the table.
Measured Applicability
Measured value Designation Resolution
range Protection Indication
Phase currents Ia, Ib, Ic 0 – 7000A 1A
1
Residual current In 0 – 6000A 1A
Phase to earth voltages Ua, Ub, Uc, Ur, Us, Ut 0 – 18kV 0.1kV
Line to line voltages Uab, Ubc, Uca 0 – 30kV 0.1kV –
Positive sequence current I1 0 – 7000A 1A –
Positive sequence voltage U1 0 – 18kV 0.1kV –
2
Residual voltage Un 0 – 18kV 0.1kV –
o o
Phase shift between A1 0 – 359 1 –
positive sequence voltage
and current
o o
Phase shift between An 0 – 359 1 –
residual voltage and
current
Single and three phase A, B & C kVA / kW / kVAr 0 – 65535 1 –
total, active and reactive 3 phase kVA / kVAr / kW
power
Single and three phase A, B & C +/ – kVAh 0 – 999999999 1 –
total and reactive energy A, B & C +/ – kVAhr,
related to forward and
reverse power flow 3 phase +/ – kVAh
directions 3 phase +/ – kVArh
3
Frequency from ABC and Fabc, Frst 45 – 65 Hz 0.01Hz
RST recloser sides
4
Phase sequence from Phase seq. ABC / ACB / ? NA –
ABC and RST sides RST / RTS / ?
4
SYSTEM SETTINGS
SYSTEM STATUS ME settings ENTER
ON .
OFF 28/12/01 13: 14:26 I/O settings
Closed Grp 4 ME UPS settings
I/ O UPS Prot SCADA settings
SCADA PC settings
RTC settings
MMI settings ME SETTINGS
ESC ENTER
U_rated,kV 12.0
F_rated,Hz 50
LSD_level, kV 0 .5
Tlp,min 15
MAIN MENU OSM # 01234
System status OSM sensors coeff :
Groups settings CIa,V /kA 2. 5001
System settings CIb,V /kA 2. 5016
CO operations CIc,V /kA 2. 4910
Counters CIn,V /kA 2. 4879
Identification CUa,V /kV 0. 1578
Erase data CUb,V /kV 0. 1765
Change password CUc,V /kV 0. 1546
Switch power Off CUr,V /kV 0. 1456
CUs,V /kV 0. 1763
CUt,V /kV 0. 1560
ON
SYSTEM STATUS SYSTEM SETTINGS
OFF
28/12/01 13: 14:26 ME settings
Closed Grp 4 ME I/O settings
I/ O UPS Prot UPS settings
SCADA SCADA settings
ENTER PC settings
RTC settings
ESC
MAIN MENU MMI settings
System status
Groups settings ENTER
System settings
CO operations
Counters
Identification
Erase data RTC SETTINGS
Change password Date fmt DD/MM/ YY
Switch power Off Time fmt 24 hours
31/12/00 14:37: 43
All user settings can be changed from the Man Machine Interface (MMI). Alternatively they can be
transferred using the TELUS software package (except for the LSD Level which is only programmable
through the MMI).
6 Protection
Four individual groups of Protection Settings are available. Each group has the following protection
functions:
Phase and Earth Overcurrent (OCEF)
Sensitive Earth Fault (SEF)
Live Line Overcurrent (LL)
Under Voltage (UV)
Under Frequency (UF)
Loss of Supply Detection (LSD)
Voltage Reclosing Control (VRC)
Automatic Backfeed Restoration (ABR)
Descriptions with up to 50 characters or numbers can be assigned for each of the protection groups using
the TELUS software package.
Group 1 – 4 settings
ON .
OFF
SYSTEM STATUS GROUPS 1 -4
28/12/01 13: 14:26 1 NORMAL
Closed Grp 4 ME 2 BUSHFIRE
I/ O UPS Prot 3 BACKFED
SCADA 4 RESERVE
ENTER
ESC
MAIN MENU
System status
Groups settings
System settings
CO operations
Counters
Identification
Erase data
Change password
Switch power Off
.
ON SYSTEM STATUS
OFF
28/12/01 13:14:26
Closed Grp 4 ME
I/ O UPS Prot
GRP 4 OC1+
TCC type ANSI I
SCADA
Ip,A 0020
TM 5.00
MIN 1.50
ENTER
Tmin,s 0.05
Tmax,s 100. 00
Ta,s 0.50
GRP 4 SETTINGS
OC EF LL SEF
UF UV ABR VRC
GRP 4 OC2+
TCC type IEC I
AR: OCEF SEF UV
Ip,A 0040
DE: OC EF SEF TM 1.00
CLP IR TTA MIN 1.00
MAX mode Disable
MAX 05.00
ENTER
Tmin,s 0.10
Tmax,s 80.00
Ta,s 1.00
Tres,s 10.00
GRP 4 OC
ENTER
OC1+ OC2+ OC3+
OC1- OC2- OC3-
GRP 4 OC3+
Ip,A 0040
Tt, s 0.02
3 where:
T Ip Pickup current
2 Imax = MAXIp
Imin = MIN*Ip
Protection
Protection
Operating
operating 1 Original TCC (without modifications)
Zone
Tmax zone 2 TCC additional time (Ta) only
1 3 TCC with all modifications applied1.
Tmin
Ta
Note 1: maximum current modification is
only applicable for the low set overcurrent
elements (OC2+, OC2-, EF2+, EF2-).
Ip Imin Imax I
ON
SYSTEM STATUS
OFF 28/12/01 13 :14:26 GRP 4 DE OC
Closed Grp 4 ME At,0 60
I /O UPS Prot DE control map:
SCADA ENTER
OC1+ E
OC2+ E
OC3+ E
OC1- D
ENTER
GRP 4 SETTINGS
OC2- D
OC EF LL SEF
UF UV ABR VRC OC3- D
AR: OCEF SEF UV
DE: OC EF SEF GRP 4 DE EF
CLP IR TTA At,0 60
DE control map:
EF1+ E
EF2+ E
EF3+ E
EF1- D
EF2- D
EF3- D
Directional Directional
Element Factory Default Element Factory Default
control control
OC1+ Enable/Disable D EF1+ Enable/Disable D
OC2+ Enable/Disable D EF2+ Enable/Disable D
OC3+ Enable/Disable D EF3+ Enable/Disable D
OC1- Enable/Disable D EF1- Enable/Disable D
OC2- Enable/Disable D EF2- Enable/Disable D
OC3- Enable/Disable D EF3- Enable/Disable D
Supply Supply
V < 0.5kV V < 0.5kV
& I < 10A & I < 10A
ti me ti me
P(LSD) P(LSD)
1 1
ti me ti me
0 0
Timer Timer
1 1
N
ti me ti me
0 0
Trec Tcl < Trec N x Tcl
OCLM OCLM
CLM
N x CLM
1 1
ti me ti me
0 0
where: CLM cold load multiplier P(LSD) Loss of Supply Detector (LSD) element pickup
OCLM operational cold load multiplier Trec cold load recognition time
Tcl cold load time (setting) N CLP timer reading when supply is restored
SYSTEM STATUS
ON . 28/12/01 13:14:26 GRP 4 CLP
OFF Closed Grp 4 ME CLM 1.9
I/ O UPS Prot Tcl,min 20
SCADA ENTER
Trec, min 30
Supply
V <0.5kV
& I< 10A
time
0
T ir
time
0 3 cycles
OIR M
IRM
1
time
0
SYSTEM STATUS
ON
28/12/01 13: 14:26 GRP 4 IR
OFF
Closed Grp 4 ME IRM 4. 2
I/ O UPS Prot Tir,s 10.50
SCADA ENTER
GRP 4 SETTINGS
ENTER
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR TTA
ON
SYSTEM STATUS AR OCEF Map
.
OFF 28/12/01 13:14:26 Trips 4: 1 2 3 4
Closed Grp 4 ME ENTER SST OC+ + - - -
I/O UPS Prot OC1+ R R R L
SCADA OC2+ R R D D
GRP 4 AR OCEF
OC3+ R L L L
AR map SST OC- + - - -
ZSC mode E OC1- D D D D
ENTER
VRC Control D OC2- D D D D
Tr1,s 0 OC3- D D D D
Tr2,s 10.00 SST EF+ + - - -
Tr3,s 100.00 EF1+ R R R L
GRP 4 SETTINGS Tres,s 10.00 EF2+ D D D D
OC EF LL SEF LSRM Mode D EF3+ L L L L
UF UV ABR VRC LSRM Time,s 015.00 SST EF- + - - -
AR: OCEF SEF UV EF1- D D D D
DE: OC EF SEF EF2- D D D D
CLP IR TTA
ENTER EF3- D D D D
Note: It is not recommended to set the AR Reset time to be shorter than the trip time.
Reclose sequence settings
Title Designation Range Resolution Factory Default
Zone sequence co-ordination mode ZSC Mode Enable/Disable – D
Voltage reclosing control element VRC Control Enable/Disable – D
First reclose time Tr1 0.1 – 180s 0.01s 010.00
Second reclose time Tr2 1 – 180s 0.01s 020.00
Third reclose time Tr3 1 – 180s 0.01s 020.00
Reset time Tres 5 – 180s 0.01s 030.00
LSRM Mode LSRM Mode Enable/Disable - D
LSRM Time LSRM Time,s 1 - 300 0.01s 015.00
Available operating modes for each of the master elements (OC1+, OC1- , EF1+ and EF1-) are;
trip and Reclose trip and Lockout
Alarm only Disable.
The maximum number of operations to lockout is defined by applying master element settings. Eg if 3
operations are required, the appropriate OC1 and EF1 elements have an L for the 3rd trip.
Available operating modes for each of the low and high set elements (OC2/3+, OC2/3-, EF2/3+ and EF2/3-)
are
trip and Reclose trip and Lockout
Disable
Fuse saving or burning regimes can be implemented through application of an appropriate operating mode
to the stage 2 and 3 protection elements.
ON
SYSTEM STATUS GRP 4 TTA
OFF
28/12/01 13:14:26 TTA Mode Trans
Closed Grp 4 ME Tat,s 2.00
I/O UPS Prot
ENTER
SCADA
ENTER
GRP 4 SETTINGS
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR TTA
TTA settings
ON
SYSTEM STATUS GRP 4 SEF
OFF
28/12/01 13: 14:26 ENTER SEF+ SEF-
Closed Grp 4 ME
I/ O UPS Prot
SCADA
ENTER
GRP 4 SETTINGS
ENTER
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF GRP 4 SEF +
CLP IR TTA Ip,A 0010
Tt,s 5 .00
Tres,s 5 .10
ON
SYSTEM STATUS GRP 4 DE SEF
OFF
28/12/01 13: 14:26 ENTER
At ,0 0
Closed Grp 4 ME DE control map:
I/ O UPS Prot SEF+ E
SEF- E
SCADA
GRP 4 SETTINGS
ENTER
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR TTA
DE SEF settings
Title Designation Range Resolution Factory Default
o o
Torque angle At 0 – 359 1 000
DE SEF control map:
Element DE control mode Factory Default
SEF+ Enable/Disable D
SEF – Enable/Disable D
ON
OFF
SYSTEM STATUS
28/12/01 13:14: 26
Closed Grp 4 ME
I/ O UPS Prot
SCADA GRP 4 AR SEF
AR map ENTER
VRC Control D
ENTER Tr1,s 0.10
Tr2,s 12.50
Tr3,s 120.00
Tres,s 12.00 AR SEF MAPA
GRP 4 SETTINGS LSRM Mode D Trips 4: 1 2 3 4
OC EF LL SEF LSRM Time,s 015.00 SEF+ R R R L
UF UV ABR VRC SEF- R R R L
AR: OCEF SEF UV
DE: OC EF SEF ENTER
CLP IR TTA
ON . SYSTEM STATUS
OFF
28/12/01 13:14:26 GRP 4 LL
Closed Grp 4 ME OCLL EFLL
I/O UPS Prot
SCADA
GRP 4 OCLL
ENTER ENTER
Ip,A 0040
Tt,s 0.02
OCLL settings
ON .
SYSTEM STATUS
OFF
28/12/01 13: 14:26 GRP 4 UV
Closed Grp 4 ME UV1 UM 0.90
I/ O UPS Prot UV1 Tt,s 10.00
SCADA ENTER
UV2 UM 0.90
UV2 Tt,s 9.50
UV3 Tt,s 0.00
ENTER
GRP 4 SETTINGS
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR RTA
UV3 settings
ON
SYSTEM STATUS
OFF
28/12/01 13: 14:26 GRP 4 AR UV
Closed Grp 4 ME Tr ,s 20.53
I/ O UPS Prot AR map ,:
SCADA UV1 R
ENTER UV2 L
UV3 L
AutoClose mode D
GRP 4 SETTINGS AutoClose T,s 120
ENTER
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR RTA
Reclosing map
Note: 1) When set to alarm, the alarm will be activated only when recloser is closed. Applies to UV1, UV2, UV3.
2) AutoClose mode is only available when the UV3 element is set to trip and Lockout (L).
ON
OFF
SYSTEM STATUS
28/12/01 13: 14:26
Closed Grp 4 ME GRP 4 UF
I/O UPS Prot UF mode D
SCADA ENTER
Fp,Hz 49. 65
Tt,s 10. 00
GRP 4 SETTINGS
ENTER
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR RTA
UF settings
ON .
OFF
SYSTEM STATUS
28/12/01 13:14:26 GRP 4 VRC
Closed Grp 4 ME VRC mode Ring
I/O UPS Prot UM 0.9
SCADA ENTER
ENTER
GRP 4 SETTINGS
OC EF LL SEF
UF UV ABR VRC
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR RTA
VRC settings
ON
OFF
SYSTEM STATUS
28/12/01 13:14:26 GRP 4 AR OCEF
Closed Grp 4 ME AR MAP
I/O UPS Prot ZSC mode E
SCADA VRC Control E
Tr1,s 000.80
Tr2,s 010.00
ENTER
Tr3,s 030.00
GRP 4 AR SEF
GRP 4 SETTINGS AR MAP
ENTER
OC EF LL SEF VRC Control E
UF UV ABR VRC Tr1,s 001.00
AR: OCEF SEF UV Tr2,s 020.00
DE: OC EF SEF Tr3,s 030.00
CLP IR RTA Tres,s 013.00
ON .
SYSTEM STATUS
OFF
28/12/01 13:14:26 GRP 4 ABR
Closed Grp 4 ME ABR mode D
I/ O UPS Prot Tr,s 100.00
SCADA ENTER
Auto Open mode D
T_ao,min 120
Operations 01
PF Dir Changed D
GRP 4 SETTINGS PF Reduced D
ENTER
OC EF LL SEF % of PF Reduced 50
UF UV ABR VRC T_ao,s 180
AR: OCEF SEF UV
DE: OC EF SEF
CLP IR RTA
7 Monitoring
The RC Cubicle generates and maintains the following records:
Close / Open (CO) operations OSM operation data
Fault Profile Fault episode data
Event log Event data
Change messages Setting and status change data
Load profile Real, Reactive and Active Power profile data
Lifetime and Fault counters
Monitoring records and counters can be downloaded to a laptop by means of TELUS software and can be
erased from the Main Processing Module (MPM) memory.
Applicable sources 2
Event Relevant state Critical parameter
of event
Open Any protection O1 (Lockout) Values registered between pickup start and open events
element or Maximum phase current (Max(Ia) / Max(Ib) / Max(Ic)) for
Operator by means of O2 / O3 / O4 OC elements
MMI, PC, I/O, SCADA (waiting to reclose) Maximum residual current (Max(In)) for EF elements
or mechanical trip
Minimum positive sequence voltage (Min(U1)) for UV1
Applicable sources 2
Event Relevant state Critical parameter
of event
ring Minimum line to line voltage (Min(Uab) / Min(Ubc) /
Min(Uca)) for UV2
Minimum frequency (Min(F)) for UF
Closed Any Auto Reclose C2 / C3 / C4 for AR NA
element, ABR, MMI, OCEF, AR SEF
SCADA, PC, I/O C0 or C1 for others
Note: 1. The CO operations record can be erased from the MPM memory.
7.6 Counters
The MPM monitors the number of operations and energy throughput during a fault and calculates the
percentage of contact wear remaining after each Close – Open operation.
Two lifetime counters are maintained, one for mechanism wear and the other for contact wear.
Fault counters provide indication of the number and type of each fault the OSM has operated for.
ON .
SYSTEM STATUS COUNTERS
OFF
28/12/01 13: 14:26 LIFETIME COUNTERS
Lifetime counters
Closed Grp 4 ME CO total 12314
Fault counters Mech. wear,% 41
I/ O UPS Prot SCADA counters Countact wear,% 12
SCADA
ENTER FAULT COUNTERS
OC A trips 844
ESC
MAIN MENU OC B trips 977
System status OC C trips 87
Groups settings EF trips 4314
System settings SEF trips 312
CO operations UV trips 30
Counters UF trips 2
Identification
Erase data
Change password SCADA COUNTERS
Switch power Off Call Drop outs 0
Tx Frames 32
Rx Frames 47
Length Error 0
CRC Error 0
C1 Buffer 10
C2 Buffer 15
C3 Buffer 20
C1 Timer,s 10
C2 Timer,s 100
C3 Timer,s 9999
Control data
Date -
Time -
Life time counters readings - -
Settings
System settings
ME settings - -
Key: UPS settings - -
ME Measurement RTC settings - -
Elements MMI settings
- -
UPS Uninterruptible Power PC settings
- -
Supply SCADA settings - -
RTC Real Time Clock I/O settings
- -
MMI Man Machine Group 1 settings - -
Interface Group 2 settings - -
I/O Input/Output module Group 3 settings - -
Remote Remote Control mode Group 4 settings - -
Grp Protection group Control signals
AR Auto Reclose Remote Off - - -
LL Live Line Trip/Close
CLP Cold Load Pickup On(Prot)/Off(Prot)
UV Under Voltage On(Grp1)
protection On(Grp2)
ABR Auto Backfeed
On(Grp4)
Restoration
On(AR)/Off(AR)
UF Under frequency
On(EF)/Off(EF)
On(SEF)/Off(SEF)
Ext External load power On(LL)/Off(LL)
supply
On(CLP)/Off(CLP)
On(UV)/Off(UV)
On(ABR)/Off(ABR)
Notes: Refer Appendix H – Control
On(UF)/Off(UF)
and Indication of Settings for
On(Power)
- -
further information regarding Off(Power)
Group settings. On(Ext)/Off(Ext)
Reset password - - -
Erase fault counters -
Erase energy meters -
Erase CO operations -
Erase event log
-
Erase change messages
-
Erase load profile -
Indication Capabilities
MMI PC SCADA I/O
Indication data
System status
Date, time
-
Measured data
-
UPS status
-
Indication signals
Key:
UPS Uninterruptible Power Supply Local mode
Lockout
AR Auto Reclose AR initiated - -
Prot Protection Prot initiated
Pickup signals - - -
Alarm signals - -
Open signals - -
Refer to section 1 for details on Closed signals - -
Measured date Prot status signals
Malfunctions
Refer to section 11.4 for details of Warnings
Indication Signals Counter readings
Lifetime counters -
Refer to section 6.9 for details on Prot Fault counters -
Status signals. Records
CO operations - -
Fault profile - - -
Event log - - -
Change messages - - -
Load profile - - -
Settings - -
ON .
SYSTEM STATUS SYSTEM SETTINGS
OFF
28/12/01 13:14:26 ME settings
Closed Grp 4 ME I/O settings
I/ O UPS Prot UPS settings
SCADA SCADA settings
PC settings
ENTER
RTC settings
ESC MAIN MENU MMI settings
System status
Groups settings
System settings ENTER
CO operations
Counters
Identification
Erase data MMI SETTINGS
Change password Fast keys control :
Switch power Off Prot On/Off E
EF On/Off D
SEF On/Off E
AR On/Off E
LL On/Off E
Groups 1-4 E
Delayed close D
Close delay,s 030
MMI settings
Title Designation Settings Factory Default
Prot On/Off pushbutton control mode Prot On/Off mode Enable/Disable E
EF On/Off pushbutton control mode EF On/Off mode Enable/Disable E
SEF On/Off pushbutton control mode SEF On/Off mode Enable/Disable E
CLP On/Off pushbutton control mode CLP On/Off mode Enable/Disable E
AR On/Off pushbutton control mode AR On/Off mode Enable/Disable E
LL On/Off pushbutton control mode LL On/Off mode Enable/Disable E
Delayed Close Delayed Close Enable/Disable D
Delayed Close Delay Time Close Delay,s 0-300 seconds 30
DELAYED CLOSE
IN: 030 SECONDS
Press <ESC>
To abort Close
Pressing the ESC key will cancel the close operation otherwise the device will close after the time delay has
expired.
PC settings
CO operations
Counters
Identification
PC SETTINGS
Erase data Baud rate: 19200
Change password
Switch power Off
General Settings
Port Settings
DNP3 Settings
Title Designation Range Resolution Factory Default
Slave Address Slave addr 0 - 65534 1 5
Master Address Master addr 0 - 65534 1 3
IEC Settings
Modbus Settings
ON
SYSTEM STATUS SCADA SETTINGS
OFF
28/12/01 13: 14:26 Comm device Radio
Protocol DNP3
Closed Grp 4 ME
Port settings
I/ O UPS Prot
SCADA SCADA time Local
DNP3/IEC101 settings
MODBUS settings
ESC
PORT SETTINGS
Port type RS232
Baud rate 19200
MAIN MENU Duplex type Full
System status Parity None
Groups settings
System settings DNP3 SETTINGS
CO operations Slave addr 00003
Counters Master addr 00005
Unsolicited Off
Identification
ENTER
Erase data IEC101 SETTINGS
Change password Link addr 00005
Switch power Off ASDU addr 00005
MSP addr 00001
SYSTEM SETTINGS
ENTER MDP addr 01000
ME settings CSC addr 03000
CDC addr 10000
I/O settings
MME addr 20000
UPS settings
PME addr 30000
SCADA settings MTT addr 40000
PC settings
RTC settings MODBUS SETINGS
MMI settings Slave addr 001
MSP addr 00001
A SCADA port monitoring screen can be viewed on the MPM under System Status:
ON SYSTEM STATUS
OFF
28/12/01 13:14:26
Closed Grp 4 ME
I/O UPS Prot
SCADA
ENTER
SCADA PORT
DRT H RTS L CD L
DSR H CTS L RI H
Dialing
Rx 65536 Tx 65536
Hangup
Test Off
This screen can be used to monitor the pin status, connection status, amount of packets received and
transmitted, hangup the connection and conduct tests.
Note: The “Modem is powered from external load” setting available only in TELUS can affect when the
communications protocol is running. Please refer to the SCADA Interface Description document (NOJA-520)
for a detailed description of this feature.
ON SYSTEM STATUS
SYSTEM SETTINGS
OFF 28/12/01 13:14:26
ME settings
Closed Grp 4 ME
I/O settings
I/O UPS Prot
UPS settings
SCADA
SCADA settings
PC settings
ESC MAIN MENU RTC settings
ENTER
System status MMI settings
Groups settings
System settings ENTER
CO operations
Counters
Identification
Erase data I /O SETTINGS
Change password I/O1 mode Test
Switch power Off I/O2 mode E
------- Inputs------
I/O1 I6 SETTING
ENTER I /O1: 1 2 3 4 5 6
Off (Prot)
I /O2: 1 2 3 4 5 6
I/O2 O1 SETTINGS ------ Outputs------
Trec,s 010.00 I /O1: 1 2 3 4 5 6
Tres,s 000.00 ENTER
I/O2: 1 2 3 4 5 6
Type: CLOSED
Signal map:
1 Closed
2 Disable
3 Disable
4 Disable
5 Disable
6 Disable
7 Disable
8 Disable
General settings
Title Designation Range Resolution Factory Default
1
I/O1 operation mode I/O1 mode Enable/Disable/Test – D
I/O2 operation mode 1 I/O2 mode Enable/Disable/Test – D
Note: 1. Selection of modes (Enable/Disable/Test) is only applicable if the relevant module is connected and
communication is established between the module and MPM.
Digital input signal map2
Input Range Factory Default
1 Any control signal + Disable Trip
2 Any control signal + Disable Close
3 Any control signal + Disable On (AR)
4 Any control signal + Disable Off (AR)
5 Any control signal + Disable On (SEF)
6 Any control signal3 + Disable Off (SEF)
Notes: 2. Refer to section 8 for available I/O controls.
3. On (Power) control signal can only be mapped to the 6th input of I/O 1.
Digital output settings4
9 Installation
Installation of both the OSM Auto Circuit Recloser and RC cubicle is straightforward. It is recommended the
preparation for installation be done in a clean workshop environment and the prepared equipment is
transported to site.
9.1 De–crating
The OSM Auto Circuit Recloser and RC cubicle are packed in a single crate containing;
Routine test summary
OSM15-200 or OSM27-203 recloser
RC cubicle with this manual in the document pocket on the inside of the door
Control cable
Pole mounting bracket and fasteners
Mechanical Trip Ring
Access to the crate is by lifting the metal tabs securing the lid. The contents can be removed without
dismantling the entire crate.
Note: The capacitive filtering on the auxiliary supply input will cause Earth Leakage Circuit Breakers to trip.
This filtering is provided to protect the electronics from high voltage spikes. During workshop testing it may
be necessary to connect the auxiliary supply through an isolating transformer to prevent nuisance tripping on
the power circuit. The earth wire MUST be connected even when in a workshop environment as the leakage
from the capacitors can cause damage to equipment.
ON
OFF .
SYSTEM SETTINGS
ME settings
SYSTEM STATUS I/O settings
28/12/01 13 : 14 :26 UPS settings
Cerrado Grp 4 ME SCADA settings
I/O UPS Prot PC settings RTC SETTINGS
SCADA RTC settings ENTER Date fmt DD/MM/YY
MMI seetings Time fmt 24 hours
ESC
31 12/00 14:37:43
ENTER
MAIN MENU
ENTER
ENTER PASSWORD
System status Password AAAA RTC SETTINGS
Groups settings Date fmt DD/MM/YY
System settings Time fmt 24 hours
CO operations [31]12/00 14:37:43
Counters
ENTER
If the correct Measurement settings have been misplaced, they can be supplied by your nearest NOJA
Power office or distributor. For provision of the correct settings the OSM serial number, as recorded on the
rating plate, is required.
3. If ‘Malfunction’ appears on the SYSTEM STATUS screen note any diagnostic messages and refer to
section 10.3.2 for what they indicate.
ON . SYSTEM STATUS
OFF . 28/12/01 13:14:26
Closed Grp 4 ME
UPS STATUS
1-st AC input On
I/O UPS Prot 2-nd AC input On
SCADA Ubt, V 12.1
Ibt, A +0. 13
ENTER
Cbt 0. 87
Ext.load [Off]
Confirm that 12Vdc appears across terminals 1 and 2 of the RS–485 connector (refer section 4.7.2).
Set Ext. Load voltage back to OFF, press the ESC key to return to SYSTEM STATUS.
5. If I/O modules are fitted, note the part number on the module case. Modules with part number IOM-
12/60 will accept input voltage from 12Vdc to 60Vdc. Modules with part number IOM-100/250 will
accept input voltage from 100Vdc to 250Vdc.
6. From the SYSTEM STATUS screen, select and view ‘System Settings’ then select and view ‘I/O
settings’ group to confirm the I/O Modules are indicating correctly. Note that if an IOM is not fitted, or
is disabled, NA appears next to the input / output status.
SYSTEM STATUS
ON .
. I/O STATUS
OFF
28/ 12/01 13:14: 26 Inputs I/01 I/02
Closed Grp 4 ME T1 On NA
I/O UPS Prot T2 On NA
SCADA T3 Off NA
T4 On NA
T5 On NA
ENTER T6 On NA
Outputs I/01 I/02
01 On NA
02 On NA
03 On NA
04 Off NA
05 Off NA
06 On NA
7. Select ‘Test’ mode for an I/O module. In this mode, application of the correct operating voltage to
any input will cause ALL outputs to change state. Applying voltage to each input and confirming that
all outputs change state each time tests operation of the I/O module.
ON .
OFF
SYSTEM STATUS SYSTEM SETTINGS
28/12/01 13:14:26 ME settings
Closed Grp 4 ME I/O settings
I/ O UPS Prot UPS settings
SCADA SCADA settings
PC settings
ENTER
RTC settings ENTER
On completion set the module under test back to ‘Enable’ mode. Press the ESC key to return to
SYSTEM SETTINGS
The above checks confirm the Recloser Control is functioning correctly and can be connected to an OSM
recloser for further testing.
Remove the security cover from the RC cubicle, it can be left off during workshop testing. Connect the
control cable to the RC plug and secure it using the integral clamping arrangement.
ON SYSTEM SETTINGS
SYSTEM STATUS
OFF ME settings ENTER
28/12/01 13: 14:26
I/O settings
Closed Grp 4 ME
UPS settings
I/ O UPS Prot
SCADA SCADA settings
PC settings
RTC settings
ESC
ENTER MMI settings
ME SETTINGS
Umax ,kV 12.0
F_rated,Hz
, 50
MAIN MENU LSD_level, kV 0.5
System status Tlp,minutes 15
Groups settings OSM # 01234
System settings OSM sensors coeff:
CO operations CIa,V /kA 2.5001
Counters CIb,V /kA 2.5016
Identification CIc,V /kA 2.4910
Erase data CIn,V /kA 2.4879
Change password CUa,V /kV 0.1578
Switch power Off CUb,V /kV 0.1765
CUc,V /kV 0.1546
CUr,V /kV 0.1456
CUs,V /kV 0.1763
CUt,V /kV 0.1560
9. Select ‘ME’ (measurements) from the SYSTEM STATUS page, then ‘Current’ from the
MEASUREMENTS page. Inject 20A primary current, one phase at a time and confirm that
indications of phase and earth current are correct in each case.
3 Phase Energy
1 Phase Energy
CURRENTS (A)
Ia 0020 Ib 0000
Ic 0000 In 0020
Settings can be manually entered using the MMI (refer section 4.4.2) or transferred using the PC based
TELUS software. This can be done on site or in the workshop as preferred.
9.3.2 HV Testing
All NOJA Power outdoor switching devices pass ANSI C37-60 requirements for power frequency and partial
discharge testing prior to dispatch from the manufacturer. Where Power frequency testing is required prior to
installation, testing to 80% ANSI C37-60 Power Frequency withstand voltage is recommended to confirm
insulation integrity without unduly stressing insulating components.
9.4.3 Installation
Make sure the pole mounting bracket is fitted to the OSM before lifting it onto the pole. The mounting bracket
has four lifting points for lifting the OSM with a sling.
The pole mounting bracket is secured to the pole by two M20 bolts at 280mm centres and the bracket has
the top hole keyed to facilitate fitting over a bolt head or nut. Once the top is secured, the bottom bolt can be
tightened to fix the recloser in place.
The pole mounting bracket can also be used to mount the recloser on concrete poles using banded
strapping. In this case two steel bands are threaded through the slots provided on the bracket and around
the pole.
Connect the HV cables into the HV connectors on each bushing. Tighten the hexagonal socket screws with
an 8mm Allen Key to 30Nm.
A tin-plated brass palm connector can be fitted to the bushing instead if required. This has two holes
44.45mm (1.75”) apart so a lug can be bolted onto the bushings.
Use an 8mm
Allen Key to
tighten the hex
screws to 30Nm.
9.4.4 RC Installation
The RC cubicle has lifting lugs in the top section of the pole mounting bracket. The RC cubicle is secured to
the pole by bolts or coach screws with diameter up to 22mm, the top hole is keyed to allow fitting over a bolt
or nut. Once the top is secured the bottom bolt can be fitted.
Refer to section 4.2 for RC cubicle dimensions.
9.4.5 Earthing
The OSM recloser is earthed by means of a (provided) M12 hex head bolt into a captive thread on the back
wall of the tank, recommended torque is 40Nm and 35mm2 copper conductor is the minimum requirement for
earth conductor, crimp lugs are recommended for connection to the OSM earth point.
The RC cubicle is earthed by means of an M12 stud on the base of the cubicle. Crimp connection at the RC
end is recommended, connect to the OSM earth by means of a short length of earth conductor and parallel
groove clamp or similar.
Voltage
Transformer
(optional)
Installation
Earth Conductor
Control Cable
Bond Cubicle To
OSM Earth
10 Maintenance
The OSM Auto Circuit Recloser and RC cubicle are designed for a maintenance free pole life. This section
provides recommendations for monitoring equipment condition.
10.2 RC Cubicle
The RC cubicle is maintenance free with the exception of the sealed lead acid battery which requires
periodic replacement.
There are two means of carrying out battery replacement, which method is used depends on whether an AC
supply is available.
10.2.1.1 AC Supply Not Available
With no AC supply available the UPS must be switched into Off mode which causes a Power Supply Module
relay to disable the battery connection. Off mode also disables the RC protection and communications
capabilities.
1. Turn MMI On using the On/Off pushbutton, press ESC to view the Main Menu.
2. Select ‘Switch Power Off’ from the ‘Main Menu’ to set the UPS into Standby mode.
CAUTION: Setting the UPS into standby mode saves the last 96
! load profile events. Prior load profile data will be erased and
should be captured using TELUS if required.
3. Wait until the MMI screen goes blank, this can take up to 60 seconds.
4. Replace battery (refer section 10.2.1.3). Turn the MMI ON, set the date and time.
10.2.1.2 AC Supply Available
Where AC supply is available, the UPS can be left active and the battery can be replaced without switching it
into Standby mode. Disconnection at the negative terminal breaks the battery circuit without risk of battery
generated arcing.
In this case battery replacement involves no loss of load profile data and no interruption to the RC protection
capabilities.
10.2.1.3 Replacement Procedure
Battery replacement is carried out as follows:
1. Open the escutcheon and disconnect the negative terminal of the battery, secure the wiring harness
to avoid accidental shorting.
2. Disconnect the positive terminal of the battery.
3. Remove the wingnuts securing the battery.
4. Remove the battery, install a replacement and tighten the wingnuts.
5. Connect the positive terminal followed by the negative terminal.
6. Close the escutcheon, turn MMI ON, select ‘System Status’ and then ‘UPS’ to confirm battery
voltage and charging current are correctly indicated.
Note: Damage due to accidental reverse polarity connection is prevented by an in-line fuse located near the battery
terminals. An incorrect fuse can result in Power Supply Module damage in the event of subsequent reverse
polarity connection.
10.3 Troubleshooting
This section provides information to allow fault determination to a module level by a qualified, competent
technician.
If problems are detected during normal service life the RC Malfunction events should be studied for a
probable cause. Fault events for the OSM Recloser, Power Supply Module, Main Processing Module, I/O
Module, UPS Module and driver module are indicated by specific events, refer section 10.3.2.
10.3.1 RC Cubicle
The diagram below identifies RC Cubicle Modules, Wiring Assemblies and connection points referenced in
this chapter.
The first thing to determine is what information is available from the Main Processing Module.
1. Press the ON/OFF pushbutton on the MMI to view the ‘SYSTEM STATUS’ screen.
2. Select ‘Warnings’ from SYSTEM STATUS’ and note all warning events with a recent time tag. Press
‘ESC’ to return to ‘SYSTEM STATUS’
3. Select ‘Malfunctions’ from ‘SYSTEM STATUS’ and note all diagnostic events. Press ‘ESC’ to return
to ‘SYSTEM STATUS’
4. Select ‘UPS’ from ‘SYSTEM STATUS’ and note status of battery, AC supplies and ext load (if
applicable).
Alternately, the same information can be accessed from the MPM using the PC based TELUS software.
Once the information has been extracted refer to section 10.3.2.1 for an explanation of Warning events and
section 10.3.2.2 for an explanation of Malfunction events.
Where tests point to an RC cubicle fault, it can be replaced and returned to a workshop environment for
further diagnostic testing. Carrying out the Tests described in this chapter and in section 9.2 should allow
faults to be traced to a module level.
Memory Corrupted memory Memory cells have Download system and protection settings using
error cell found become corrupted due TELUS software
to excessive EMI
Off state UPS controller is set Operator action Not applicable
into Off state
10.3.2.3 Communications
Refer to section 9.2.3 for a procedure to check the health of the I/O Modules.
RS-485 and RS-232 communications can be checked by monitoring signals at their terminals. If signals are
not within the expected range, check the wiring from MPM to the port, refer schematic on section 10.4.3. If
no wiring fault can be found then replace the Main Processing Module.
Carrying out testing as described in section 9.2.5 and 9.3.2 should allow the fault to be located.
10.3.3.1 OSM Output Signals
Output signals from Rogowski sensors and Capacitive Voltage sensors are not easily confirmed in the field.
The most effective way to test that these sensors are operating correctly is through substitution.
Where a current or voltage indication appears to be in error, use a different RC cubicle to see whether it
reports the same problem. If the new RC is correctly programmed with the OSM measurement coefficients
and displays the same errors as the old one then the OSM should be replaced.
10.3.3.2 OSM Actuator Coil Resistance Testing
The actuator coil resistance can be measured on pins 1 and 3 of the control cable if a malfunction is
suspected. The resistance measured should be 15 ohms +/-2ohms.
10.3.3.3 OSM Current Sensor Resistance Testing
The current sensors can be measured from the control cable pins as follows:
I(n) – Pins 17 and 21 – 195 ohms +/-10 ohms
I(a) – Pins 10 and 14 – 66 ohms +/-3 ohms
I(b) – Pins 11 and 15 – 66 ohms +/-3 ohms
I(c) – Pins 12 and 16 – 66 ohms +/-3 ohms
10.4 Schematics
10.4.1 Control Cable
10.4.7 RS-232
11 Appendices
11.1 Appendix A – Protection Element Structure
Element designation Description
PROT Protection element
Group1 Protection Group 1
Group2 Protection Group 2
Group3 Protection Group 3
Group4 Protection Group 4
OCEF Phase and earth overcurrent element
OC Phase overcurrent element
OC1+ Low set time delayed phase overcurrent element attributed with forward power flow
OC2+ Low set phase overcurrent element attributed with forward power flow
OC3+ High set instantaneous phase overcurrent element attributed with forward power flow
OC1- Low set time delayed phase overcurrent element attributed with reverse power flow
OC2- Low set phase overcurrent element attributed with reverse power flow
OC3- High set instantaneous phase overcurrent element attributed with reverse power flow
DE OC Phase overcurrent directional element
EF Earth overcurrent element
EF1+ Low set time delayed earth overcurrent element attributed with forward power flow
EF2+ Low set earth overcurrent element attributed with forward power flow
EF3+ High set instantaneous earth overcurrent element attributed with forward power flow
EF1- Low set time delayed earth overcurrent element attributed with reverse power flow
EF2- Low set earth overcurrent element attributed with reverse power flow
EF3- High set instantaneous earth element attributed with reverse power flow
DE EF Earth overcurrent directional element
CLP Cold load pickup element
IR Inrush restraint element
AR OCEF Phase and earth overcurrent reclosing element
TTA Temporary time adder
SEF Sensitive earth fault element
SEF+ Sensitive earth fault element attributed with forward power flow
SEF- Sensitive earth fault element attributed with reverse power flow
AR SEF Sensitive earth fault reclosing element
DE SEF Sensitive earth fault directional element
LL Live line overcurrent element
OCLL Live line phase overcurrent element
EFLL Live line earth overcurrent element
UV Undervoltage element
UV1
Phase undervoltage balanced element
UV2 Line to line undervoltage element
UV3 Loss of supply element
AR UV Undervoltage reclosing element
UF Underfrequency load shed element
ABR Automatic backfeed restoration element
LSD Loss of supply detector
Uabc< Loss of voltage detector related to ABC HV terminals
Urst< Loss of voltage detector related to RST HV terminals
Iabc< Loss of current detector
VRC Voltage reclosing control element
Uabc> Voltage restoration detector related to ABC HV terminals
Urst> Voltage restoration detector related to RST HV terminals
PSC Protection status control element
Note: Each individual protection Group 1 to 3 has the same functional structure as Group 4.
Operation of the Directional Element is illustrated in the state diagram below. Transitions 1 - 4 are illustrated
on the following pages.
+ -
1
3 3
4 4
?
S t(DE )
+
-
ti m e
<3 0 m s
At -900
S t ( D E)
+
- t i me
<30m
s
3 Polarization
Io p
~10A
ti m e
Up o l
~0.5kV
ti m e
S t(DE )
+(-)
? ti m e
<30m s
or Io p
~10A
ti m e
Up o l
~0.5kV
ti m e
S t(DE )
+(-)
? ti m e
<30m s
4 Depolarization
~10A
time
~0.5kV
time
St (D E)
+(-)
? time
3cy cles
P(E)
1
time
0
or
Io p
~10A
ti m e
Up o l
~0.5kV
ti m e
S t (DE )
+(-)
? ti m e
3 cycl es
P(E)
1
0 ti m e
Notes
1. during the 3 cycles DE uses remembered voltage or current for
polarization
2. if a pickup related to any element enabled for directional control is
detected within 3 cycles of voltage dropping below 0.5kV,
depolarization cannot proceed until the pickup is reset.
This avoids depolarization of DE during close short circuit faults.
Ip pickup current
Tt tripping time
I fault current
The ANSI TCC programmable within the RC Cubicle are defined by the parameters in the following Table, as
applied to the above equation.
For currents below 6kA the ANSI TCC programmable within the RC cubicle are defined by the parameters in
the following Table, as applied to the above equation.
For currents above 6kA, the time to trip is a constant time defined by the above equation with I=6kA and the
appropriate parameters from the table below.
ANSI TCC’s are provided with a disk emulating reset timer described by the following general equation:
A TM
Tt p
where: TM
A, p
time multiplier
constants
I 1 Ip pickup current
Ip Tt tripping time
I fault current
The IEC TCC programmable within the RC Cubicle are defined by the parameters in the following Table, as
applied to the above equation.
For currents below 6kA the IEC TCC programmable within the RC cubicle are defined by the parameters in
the following Table, as applied to the above equation.
For currents above 6kA, the time to trip is a constant time defined by the above equation with I=6kA and the
appropriate parameters from the table below.
Tm
Tt n
Ta where: Tm time multiplier
I 1 Tt
Ip
time to trip at current I
pickup current
Ip n power function coefficient
Ta additional time
Note that Tm, Ip, n apply to each section whereas Ta applies to the entire TCC.
A maximum of seven pairs of time-current coordinates describe UD1 as illustrated in the diagram below. The
current coordinate of the first characteristic point (I1) determines the minimum operating current (Imin) and
time coordinate of the last characteristic (T7) point determines the minimum operating time.
UD1 has a user configured, definite time reset timer.
T
Consequently the reset characteristic is independent of current.
Ta
T(1) UD1 can be modified with the aid of curve modifiers in the form
of a current multiplier (CM) and additional time (Ta). The effect of
T(2)
CM
these modifiers is to move the entire curve, as indicated by the
T(3) arrows in the diagram.
T(4) Note that setting (eg) T1 < T3 or I1 > I3 will automatically reduce
T(5) the number of sections, and correspondingly, the number of
characteristic points; similar for the other sections.
T(6)
T(7)
T(1)
UD2 is equipped with a user configured, definite time reset timer.
Consequently the reset characteristic is independent of current.
T(2)
T(3)
T(4)
Signal Description
TYPE: GENERAL
Lockout All AR OCEF, AR SEF, AR SEF, ABR elements are set in the O1 state
Remote off Control mode is set Local
AR initiated Any of AR OCEF, AR SEF, AR UV or ABR elements set in one of O2, O3 or O4 states
Prot initiated Logical OR of AR initiated and Pickup signals
TYPE: PICKUP
Pickup Pickup output of any of OC1+, OC2+, OC3+, OC1- , OC2- , OC3- , EF1+, EF2+, EF3+,
EF1- EF2-, EF3-, SEF+, SEF-, EFLL, OCLL, UF, UV1, UV2, UV3 elements activated
P(OC1+) Pickup output of OC1+ activated
P(OC2+) Pickup output of OC2+ activated
P(OC3+) Pickup output of OC3+ activated
P(OC1- ) Pickup output of OC1- activated
P(OC2- ) Pickup output of OC2- activated
P(OC3- ) Pickup output of OC3- activated
P(EF1+) Pickup output of EF1+ activated
P(EF2+) Pickup output of EF2+ activated
P(EF3+) Pickup output of EF3+ activated
P(EF1-) Pickup output of EF1- activated
P(EF2- ) Pickup output of EF2- activated
P(EF3- ) Pickup output of EF3- activated
P(SEF+) Pickup output of SEF+ activated
P(SEF- ) Pickup output of SEF- activated
P(OCLL) Pickup output of OCLL activated
P(EFLL) Pickup output of EFLL activated
P(UV1) Pickup output of UV1 activated
P(UV2) Pickup output of UV2 activated
P(UV3) Pickup output of UV3 activated
P(UF) Pickup output of UF activated
P(Uabc>) Pickup output of Uabc> activated
P(Urst>) Pickup output of Urst> activated
P(Uabc<) Pickup output of Uabc< activated
P(Urst<) Pickup output of Urst< activated
TYPE: OPEN
Open PS=0 irrespective to source
Open (Prot) Open due to OC1+, OC2+, OC3+, OC1- , OC2- , OC3- , EF1+, EF2+, EF3+, EF1-, EF2- ,
EF3- , SEF+, SEF- , EFLL, OCLL, UF, UV1, UV2 or UV3 tripping
Open (OC1+) Open due to OC1+ tripping
Open (OC2+) Open due to OC2+ tripping
Open (OC3+) Open due to OC3+ tripping
Open (OC1- ) Open due to OC1- tripping
Signal Description
Open (OC2- ) Open due to OC2- tripping
Open (OC3- ) Open due to OC3- tripping
Open (EF1+) Open due to EF1+ tripping
Open (EF2+) Open due to EF2+ tripping
Open (EF3+) Open due to EF3+ tripping
Open (EF1-) Open due to EF1- tripping
Open (EF2- ) Open due to EF2- tripping
Open (EF3- ) Open due to EF3- tripping
Open (SEF+) Open due to SEF+ tripping
Open (SEF- ) Open due to SEF- tripping
Open (OCLL) Open due to OCLL tripping
Open (EFLL) Open due to EFLL tripping
Open (UV1) Open due to UV1 tripping
Open (UV2) Open due to UV2 tripping
Open (UV3) Open due to UV3 tripping
Open (UF) Open due to UF tripping
Open (Remote) Open due to SCADA or I/O control signal
Open (SCADA) Open due to SCADA control signal
Open (I/O) Open due to I/O control signal
Open (Local) Open due to MMI, PC control signal or manual tripping
Open (MMI) Open due to MMI control signal
Open (PC) Open due to PC control signal
Open (Manual) Open due to manual tripping (no origin discovered)
TYPE: ALARM
Alarm Alarm output of any of OC1+, OC2+, OC3+, OC1- , OC2- , OC3- , EF1+, EF2+, EF3+, EF1-,
EF2- , EF3- , SEF+, SEF-, EFLL, OCLL, UF, UV1, UV2, UV3 elements activated
A(OC1+) Alarm output of OC1+ activated
A(OC2+) Alarm output of OC2+ activated
A(OC3+) Alarm output of OC3+ activated
A(OC1- ) Alarm output of OC1- activated
A(OC2- ) Alarm output of OC2- activated
A(OC3- ) Alarm output of OC3- activated
A(EF1+) Alarm output of EF1+ activated
A(EF2+) Alarm output of EF2+ activated
A(EF3+) Alarm output of EF3+ activated
A(EF1-) Alarm output of EF1- activated
A(EF2- ) Alarm output of EF2- activated
A(EF3- ) Alarm output of EF3- activated
A(SEF+) Alarm output of SEF+ activated
A(SEF- ) Alarm output of SEF- activated
A(UV1) Alarm output of UV1 activated
A(UV2) Alarm output of UV2 activated
A(UF) Alarm output of UV3 activated
A (F<) Alarm output of UF activated
TYPE: CLOSED
Closed PS=1 irrespective to origin
Closed (AR) Closed due to AR OCEF, AR SEF, AR UV, ABR control signal
Closed (AR OCEF) Closed due to AR OCEF reclosing
Signal Description
Closed (AR SEF) Closed due to AR SEF reclosing
Closed (AR UV) Closed due to AR UV reclosing
Closed (ABR) Closed due to ABR closing
Closed (Remote) Closed due to SCADA or I/O control signal
Closed (SCADA) Closed due to SCADA control signal
Closed (I/O) Closed due to I/O control signal
Closed (Local) Closed due to MMI, PC control signal or undefined closed
Closed (MMI) Closed due to MMI control signal
Closed (PC) Close due to PC control signal
Closed (undef) Source of close undefined, recognized after On (Power) or servicing
TYPE: STATUS
Prot On Protection is switched on
Group1 On Active Group 1
Group2 On Active Group 2
Group3 On Active Group 3
Group4 On Active Group 4
EF On Earth overcurrent element is switched on
SEF On Sensitive Earth fault element is switched on
UV On Undervoltage element is switched on
UF On Underfrequency element is switched on
CLP On Cold load pickup element is switched on
LL On Live line element is switched on
AR=On OC/EF, UV, SEF reclosing and ABR are switched on
ABR On Automatic backfeed restoration is switched on
Connection “CONNECT” string received from DCE or the DCD signal has changed state from low to
established high.
Connection Hangup due to inactive timeout or received “NO CARRIER” string from DCE or the DCD
completed signal has changed from high to low.
Signal Description
I/O1 fault I/O1 internal fault detected
I/O2 fault I/O2 internal fault detected
DCE Error DSR signal is low, CTS signal is low or receive “ERROR” string when commands are sent
to DCE.
TYPE: WARNING
Warning Any warning signal activated
Standby UPS controller set into Standby state
Off UPS controller is set into Off state
Shutdown UPS controller is set into Shutdown state
Battery supply UPS is in Battery supply mode
AC supply UPS is in AC supply mode
Driver not ready Driver is not ready to execute next control signal
Memory error Corrupted memory cell found
OSM coil isolated OSM coil open circuit detected
Relevant
signal/parameter
Event title
Old value Source of event Critical parameter
Title New
value
Pickup Start P(E) 01 OC1+, OC2+, OC3+ Iop and A,B or C phase for:
OC1-, OC2-, OC3-,
EF1+, EF2+, EF3+, OC1+, OC2+, OC3+, OC1- ,OC2-, OC3-,
EF1-, EF2-, EF3-, OCLL
SEF+, SEF-, OCLL, I op for EF1+, EF2+, EF3+, EF1-, EF2- ,
EFLL, UF, UV1, UV2, EF3-, EFLL, SEF+, SEF-
UV3, Uabc<, Urst<,
Uabc>, Urst>, LSD Up AB, BC or CA phase for UV2
Up for UV1, Uabc>, Urst>
Fp for UF
End P(E) 10 OC1+, OC2+, OC3+ Maximum current registered during pickup
OC1-, OC2-, OC3-, duration and A. B or C phase for OC1+,
EF1+, EF2+, EF3+, OC2+, OC3+, OC1-, OC2-, OC3-, OCLL
EF1-, EF2-, EF3-, SEF+,
SEF-, OCLL, EFLL, UF, Maximum current registered during pickup
UV1, UV2, UV3, Uabc<, duration for EF1+, EF2+, EF3+, EF1-, EF2-,
Urst<, Uabc>, Urst>, EF3-, EFLL, SEF+, SEF-
LSD Maximum voltage registered during pickup
duration for Uabc>, Urst>
Minimum voltage registered during pickup
duration for UV1
Minimum voltage registered during pickup
duration and AB, BC or CA phase for UV2
Minimum frequency registered during pickup
duration for UF
Timer Start Input current below Imax OC2+, OC2- Imax and A, B or C phase for OC2+, OC2-
freezing above
Imax Imax for EF2+, EF2-
End Input current above Imax OC2+, OC2- , EF2+, A, B or C phase for OC2+, OC2-
below EF2-
Imax
Alarm N/A A(E) 01 OC1+, OC2+, OC3+ Iop and A,B or C phase for OC1+, OC2+,
OC1-, OC2-, OC3-, OC3+, OC1- , OC2- , OC3-
EF1+, EF2+, EF3+,
EF1-, EF2-, EF3-, Iop for EF1+, EF2+, EF3+, EF1-,EF2- , EF3-
SEF+, SEF-, UF, UV1, , SEF+, SEF-,
UV2, UV3 Up for UV1
Up for AB, BC or CA phase for UV2
Fp for UF
Reset N/A N(E) above 00 OC1+, OC2+, OC3+, A, B or C phase for OC1+, OC2+, OC3+,
OC1-, OC2- , OC3-, OC1-, OC2- , OC3-
EF1+, EF2+, EF3+,
EF1-, EF2-, EF3- ,
SEF+, SEF-, OCLL,
EFLL, AR OCEF, AR
SEF
Relevant
signal/parameter
Event title
Old value Source of event Critical parameter
Title New
value
Trip N/A T(E) 01 OC1+, OC2+, OC3+, R (trip to reclose) or L (Trip to lockout) and
OC1-, OC2-, OC3-, A,B or C phase for OC1+, OC2+, OC3+,
EF1+, EF2+, EF3+, OC1-, OC2-, OC3-
EF1-, EF2-, EF3-,
SEF+, SEF-, OCLL, R (trip to reclose) or L (Trip to lockout)
EFLL, UF, UV1, UV2, selection for EF1+, EF2+, EF3+, EF1-, EF2- ,
UV3, MMI, PC, I/O, EF3- , SEF+, SEF-, UV1, UV3
SCADA R (trip to reclose) or L (Trip to lockout) and
AB, BC or CA phase for UV2
Close N/A C(E) 01 AR OCEF, AR SEF AR N/A
UV, ABR ,MMI PC, I/O,
SCADA
Time N/A Toat 0Tat RTA Tta
addition
Trec start N(CLP) 0above 0 CLP CLM
Relevant
signal/parameter
Event title
Old value Source of event Critical parameter
Title New
value
Off (Power) N/A Off(Power) 01 MMI, PC, I/O, SCADA N/A
Relevant
signal/parameter
Event title
Old value Source of event Critical parameter
Title New
value
Driver SC Start Driver SC 01 UPS N/A
Relevant
signal/parameter
Event title
Old value Source of event Critical parameter
Title New
value
I/O1 Start I/O1 comms 01 ISC N/A
comms error
error
End I/O1 comms 10 ISC N/A
error
I/O2 Start I/O2 comms 01 ISC N/A
comms error
error
End I/O2 comms 10 ISC N/A
error
Tmpm Start Tmpm 01 ISC N/A
comms comms error
error
End Tmpm 10 ISC N/A
comms error
RTC Start RTC comms 01 ISC N/A
comms error
error
End RTC comms 10 ISC N/A
error
DCE Error Start DCE Error DSR = 0 or Comms N/A
CTS = 0 or
“ERROR”
string
received on
DCE
commands
End DCE Error DSR=0 Comms N/A
DSR=1 or
CTS=0
CTS=1 or
receive “OK”
string on
DCE
commands
Notes:
Groups 1 to 4 have the same settings as shown for group 1
Within the Group 1 – 4 settings, the Group Names can only be assigned or edited using TELUS software
Within the OC and EF settings, User Defined 1 (UD1) characteristic points can only be assigned or edited using
TELUS software
Notes: (1) This menu appears during the data saving process initiated by switching power Off.
(2) This menu appears when power cannot be switched off (eg due to UPS comms error).
(3) This menu appears when an incorrect password has been entered
(4) This menu appears when a correct password has been entered
(5) This menu appears when the password entered at NEW and CONFIRM are the same
(6) This menu appears when the password entered at NEW and CONFIRM are different.
5 2
GRP4 VRC
VRC mode Ring
GRP4 OC GROUPS SETTINGS UM 0.9
GRP4 OC1+
OC1+ OC2+ OC3+ 1 NORMAL
TCC type ANSI SI GRP4 ABR
OC1- OC2- OC3- 2 BUSHFIRE
Ip,A 0020 ABR mode D
3 BACKFED
TM 5.00 Tr,s 1.00
GRP4 EF 4 RESERVE
MIN 1.50 AutoOpen mode D
EF1+ EF2+ EF3+
Tmin,s 0.05 T_ao,min 120
EF1- EF2- EF3-
Tmax,s 100.00 Operations 01
Ta,s 0.50 GRP4 SETTINGS PF Dir Changed D
GRP4 LL OC EF LL SEF PF Reduced D
OCLL EFLL % of PF Reduced 50
T_ao,s 180
GRP4 EF2- UF UV ABR VRC
GRP4 SEF GRP4 UV
TCC type IEC I SEF+ SEF- UV1 UM 0.90
Ip,A 0040 UV1 Tt,s 10.00
TM 1.00 AR: OCEF SEF UV
GRP4 SEF+ UV2 UM 0.90
MIN 1.00 UV2 Tt,s 9.50
MAX mode Disable Ip,A 0010
Tt,s 5.00 DE: OC EF SEF UV3 Tt,s 0.00
MAX 05.00
Tmin,s 0.10 Tres,s 5.10 GRP 4 UF
Tmax,s 80.00 UF mode Disable
CLP IR RTA
Ta,s 1.00 Fp,Hz 49.65
GRP4 DE OC
Tres,s 10.00 0 Tt,s 10.00
At, 60
DE control map: GRP4 IR GRP4 AR UV
OC1+ E IRM 4.2 Tr,s 20.53
OC2+ E Tir,s 10.50
GRP4 OCLL
GRP4 OCLL OC3+ E
AR map:
TCC type ANSI STEI UV1 R
Ip,A
Ip,A 0064
0100
OC1- D UV2 L
OC2- D GRP4 CLP
TMTt,s 0.00
0.10 CLM 1.9 UV3 L
OC3- D AutoClose mode D
MIN 1.00 Tcl,min 20
Tmin,s 0.00 Trec, min 30 AutoClose T,s 120
Tmax,s 05.00 GRP4 DE EF
At, 0 15 GRP4 AR SEF
Ta,s 0.00 AR map:
Tres,s 0.00 DE control map:
GRP4 RTA VRC Control E
EF1+ E
RTA Mode Trans Tr1,s 0.10
EF2+ E
Tat,s 2.00 Tr2,s 12.50
EF3+ E
EF1- D Tr3,s 120.00
EF2- D Tres,s 12.00
EF3- D LSRM Mode D
LSRM Time,s 015.00
GRP4 DE SEF AR SEF MAP
At, 0 0 AR OCEF MAP
Trips 4: 1 2 3 4
DE control map: Trips 4: 1 2 3 4
SEF+ R R R L
SEF+ E SST OC+ + - - -
SEF- R R R L
SEF- E OC1+ R R R L
OC2+ R R D D
OC3+ R L L L GRP4 AR OCEF
GRP4 DE SEF (3 ) ENTER PASSWORD AR map:
At 0
0 (1) SST OC- + - - -
Password XXXX ZCS mode E
DE control map: OC1- D D D D
OC2- D D D D VRC Control E
SEF+ E (2) Invalid password Tr1,s 0
SEF- E OC3- D D D D
Press <Esc> SST EF+ + - - - Tr2,s 10.00
EF1+ R R R L Tr3,s 100.00
EF2+ D D D D Tres,s 10.00
EF3+ L L L L LSRM Mode D
SST EF- + - - - LSRM Time,s015.00
EF1- D D D D
EF2- D D D D
EF3- D D D D
Notes: (1) This menu appears when user tries to edit password protected parameter
(2) This menu appears when password has been entered
(3) This menu appears when correct password has been entered
3 ME SETTINGS
SCADA SETTINGS Umax,kV 12.0
Comm device Modem Frated,Hz 50
Protocol DNP3 LSD_level,kV 0.5
SCADA time Local SYSTEM SETTINGS Tlp,minutes 15
Port Settings OSM # 00136
IEC101 Settings ME settings
OSM sensors coeff:
DNP3 Settings I/O settings CIa,V/kA 2.5001 I/O1 mode changing
MODBUS Settings UPS settings CIb,V/kA 2.5016 Please wait
SCADA settings CIc,V/kA 2.4910
MODBUS SETTINGS PC settings CIn,V/kA 2.4879
Slave addr 001 RTC settings CUa,V/kV 0.1578 I/O1 mode changed
CUb,V/kV 0.1765 Press <Esc>
MMI settings
CUc,V/kV 0.1546
DNP3 SETTINGS
CUr,V/kV 0.1456
Slave addr 00005
CUs,V/kV 0.1763
Master addr 00003 MMI SETTINGS No link to I/O1
CUt,V/kV 0.1560
Unsolicited On Fast keys control: Cannot change mode (1)
Prot On/Off E Press <Esc>
IEC101 SETTINGS I/O SETTINGS
EF On/Off D
Link addr 00005 I/O1 mode Test
SEF On/Off E
ASDU addr 00005 I/O2 mode E I/O1 I6 SETTINGS
AR On/Off E (3)
MSP addr 00001 -------Inputs------ Off(prot)
LL On/Off E
MDP addr 01000 I/O1: 1 2 3 4 5 6 (2)
Groups 1-4 E
CSC addr 02000 I/O2: 1 2 3 4 5 6
CDC addr 03000 Delayed close D (3) I/O2 O6 SETTINGS
Close delay,s 030
------Outputs------
MME addr 10000 I/O1: 1 2 3 4 5 6 (2) Trec,s 010.00
CSE addr 20000 I/O2: 1 2 3 4 5 6 Tres,s 000.00
PME addr 30000 Signal map:
MIT addr 40000 1 Closed
UPS SETTINGS 2 Disable
PORT SETTINGS Shutdown level 0.2 3 Disable
Port type RS232 Crated, A*h 26 4 Disable
Baud rate 19200 T_ext, min 001 5 Disable
Duplex type Full Tres_ext, hrs 000 6 Disable
Parity None 7 Disable
8 Disable
PC SETTINGS
Baud rate: 19200
RTC SETTINGS
Date fmt DD/MM/YY
Time fmt 24 hours
03 /01 /02 14 :37 :43
Index
A H
Accuracy Hazard Statements....................................................... 2
Measurement ........................................................... 5 Humidity ..................................................................... 3
Protection ................................................................ 6 HV Arrestors ............................................................. 66
Sensor ...................................................................... 3 HV Terminals ............................................................ 11
Altitude.................................................................... 3, 5
I
Auto Reclose
Phase and Earth Overcurrent ................................. 37 Inrush Restraint ......................................................... 36
Sensitive Earth Fault ............................................. 41 Installation
Under Voltage ....................................................... 43 OSM ...................................................................... 66
Automatic Backfeed Restoration............................... 46 RC Cubicle ............................................................ 67
Auxiliary Supply ....................................................... 81 IO Module ................................................................... 8
configuration ......................................................... 19 IO Modules ............................................................... 22
connector ............................................................... 19 testing .................................................................... 62
wiring .................................................................... 22
B
L
Battery ................................................................... 8, 70
block diagram ............................................................ 13 LCD........................................................................... 15
Breaking Duty ............................................................. 4 LCD Control ............................................................. 16
Load profile ............................................................... 49
C
Local Control ............................................................ 16
Change Messages .............................................. 49, 102 Loss of Supply .......................................................... 44
Close Open (CO) Operations .................................... 48
M
Cold Load Pickup ...................................................... 35
Communications ....................................................... 20 Magnetic Actuator....................................................... 9
Contact Wear............................................................. 70 Main Circuit Bushings ................................................ 9
Control Cable ...................................................... 62, 78 Main Processor Module ............................................ 15
Control Mode ............................................................ 16 Maintenance .............................................................. 70
Counters .................................................................... 50 Malfunction Events ............................................. 61, 75
Creepage.................................................................... 11 Measurements
Cross Section current ................................................................... 64
OSM ........................................................................ 9 voltage ................................................................... 65
Current Sensing ..................................................... 3, 11 Mechanical Trip .................................................... 9, 11
Curve Modifiers ........................................................ 34 MMI ............................................................ 15, 17, 104
Modem ...................................................................... 12
D
Mounting Bracket ..................................................... 65
Date / Time................................................................ 61 MPM ................................................................... 13, 15
Diagnostic Events...................................................... 73
O
Dimensions
OSM .................................................................. 3, 10 Operator Interface ..................................................... 15
RC Cubicle ........................................................ 5, 15 OSM 15 Terminal Stems ........................................... 64
Directional Protection ............................................... 85 OSM Ratings ............................................................... 3
Driver Module ..................................................... 13, 26 Overcurrent
Directional............................................................. 34
E
Earth ...................................................................... 31
Earthing ......................................................... 10, 15, 67 Live Line ............................................................... 42
EMC ...................................................................... 7, 13 Phase ..................................................................... 31
Event Log ............................................................ 49, 97
P
F
Padlock ...................................................................... 12
Fast Keys ................................................................... 18 Password ................................................................... 61
Fault profile ............................................................... 49 Phase sequence .......................................................... 27
Position Indicator ...................................................... 11