Professional Documents
Culture Documents
DSEGenset
ELECTRO-MAGNETIC COMPATIBILITY
SYNCHRONISING AUTO MAINS FAILURE BS EN 61000-6-2
EMC Generic Immunity Standard for
CONTROL MODULE the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE8620 is an Auto Mains Comprehensive communications With all communication ports
TEMPERATURE
(Utility) Failure Control Module are also available via RS232, capable of being active at the same BS EN 60068-2-1
suitable for paralleling single RS485 & Ethernet for remote PC time, the DSE8xxx Series is ideal Ab/Ae Cold Test -30 oC
gensets (diesel or gas) with the control and monitoring, and for a wide variety of demanding BS EN 60068-2-2
load share applications. Bb/Be Dry Heat +70 oC
mains (utility) supply. Designed to integration into building
synchronise a single genset with a management systems. VIBRATION
single mains (utility) supply, the The comprehensive event log will KEY LOAD SHARE FEATURES: BS EN 60068-2-6
• Peak lopping/sharing Ten sweeps in each of three
DSE8620 will automatically control record up to 250 events to facilitate major axes
the change over from mains (utility) maintenance. • Manual voltage/frequency 5 Hz to 8 Hz @ +/-7.5 mm,
to generator supply or run the adjustment 8 Hz to 500 Hz @ 2 gn
generator in synchronisation with An extensive number of fixed and • R.O.C.O.F. and vector shift HUMIDITY
the mains (utility) to provide flexible monitoring and protection protection BS EN 60068-2-30
• Generator load demand Db Damp Heat Cyclic 20/55 oC
no-break, peak lopping and peak features are included. Easy @ 95% RH 48 Hours
shaving power solutions. alteration of the sequences, timers • Mains (Utility) de-coupling BS EN 60068-2-78
• Mains (Utility) de-coupling Cab Damp Heat Static 40 oC
and alarms can be made using the @ 93% RH 48 Hours
The module can indicate DSE PC Configuration Suite test mode
operational status and fault Software. Selected configuration is • Direct governor & AVR control. SHOCK
• Volts and frequency matching. BS EN 60068-2-27
conditions on the LCD screen also available via the module’s front Three shocks in each of three major axes
(multiple languages available), by panel. • kW & kV Ar load sharing 15 gn in 11 mS
illuminated LED, audible sounder DEGREES OF PROTECTION
and SMS messaging. PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DSENET RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V
ETHERNET
+
DEUTZ
DSE8620 ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) SENSING N/C VOLT FREE N/O VOLT GENERATOR SENSING CHARGE FUEL & CRANK ELECTRONIC
OUTPUT FREE OUTPUT ALTERNATOR OUTPUTS ENGINES &
FLEXIBLE WITH CAN MAGNETIC PICK-UP
VOLTS CURRENT CURRENT VOLTS
D+
W/L +
ISSUE 1
®
DSEGenset
DSE8620 SPECIFICATION
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
FEATURES supply was at least 10 V before dropout
and
supply recovers to 5 V. This is achieved
without the need for internal batteries
OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (START)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-099/05/11 (4)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457