You are on page 1of 1

FREQUENCY GUARD FOR SINGLE OR THREE PHASE SYSTEMS KPF221x

• Precision High / Low Frequency Protection

• Ranges 45-55Hz, 55-65Hz and 45-65Hz

• Quartz Controlled Frequency Protection and Meter

• Definite time trip delays

• Complies with G59 requirements

• Optional very fast analogue output (<50mS), (F-versions)

Specifications Description
Auxiliary Voltage: 100-120V, 200-240V, The digitally controlled KPF221x provide precision (0.2%) high/low frequency protection.
380-415V, 440-460 or 480VAC
40-70Hz (Fuse 0,5A) A digital, crystal controlled frequency window discriminator controls operation and delay of the frequency low/high
Optional Auxiliary alarm relays. The unit measures the zero point crossing of the voltage true r.m.s. value, and accuracy is independent
Voltage: 24, 48 or 110VDC (Fuse 2A) of any wave form distortion.
Supply tolerance: ± 10%
Power rating: 1,5VA The auxiliary voltage is supplied from the unit voltage input.ADC auxiliary voltage input is optionally available.Agreen
Contact rating: AC: 100VA - 250V/2A max. LED indicates POWER on. Start of monitoring function is delayed when power is switched on (default 2 secs delay). In
DC: 50W - 100V/1A max. this way false tripping during power up is avoided. The precision DIN96 meter reads the frequency directly in Hz, and
Adjustments: Trip level Delay has low-reflection glass to ease reading at a distance.
Trip level High
45-55Hz & 55-65Hz: 0% to +10% 0-30 secs The frequency meter and the triple-zone status LEDs at a glance gives the clear safety message:
45-65Hz: 0% to +20% 0-30 secs LOWALARM - NORMAL - HIGHALARM
Trip level Low
45-55Hz & 55-65Hz: 0% to -10% 0-30 secs The unit has C/O relay outputs for Frequency High Trip (R1) and Frequency Low Trip (R2). Atrip LED flashes when the
45-65Hz: 0% to -20% 0-30 secs trip level is passed, the relay trips after elapsed delay. The frequency differential set points can be user-adjusted to suit
Analogue outputs: Up to 20mA, max 500ohm most applications. Trip levels and delays are settable on unit rear.
(other on request) Up to 10V, min 100kohm
Temperature: -20 to +70ºC Red alarm lamps FREQUENCY LOW or FREQUENCY HIGH flash instantly (approx. 1 flash per second) on passing
Weight: 0.64kgs the frequency differential set points. The lamp changes state and the alarm relay operates after the pre-set delay. If a
Front protection: IP52 (IP65 optional) fault condition ends during the delay interval, the timer will automatically reset.

Dimensions The F-versions have an fast response mAoutput signal proportional to the Hz range.
Mounting Bracket SUPPLY
12
1
Standard scale: 45-55Hz, 55-65Hz or 45-65Hz L3 L2 L1
13
14 2
15 3
Models Latch Output Fail safe 55 12 KPF221x
16
AC Aux 1
17 4
KPF221E - - X Supply
18
26
KPF221F - X X High 13 R1 (Standard) 2
19
20
27 KPF221G* X - X 50
5 KPF221GF* X X X 14 3
22
29 30
6 Mounting Bracket
Normal
21
7 KPF221H - - - 15
30
31
8
KPF221HF - X - 4
9
32
Co mp ort
10 KPF221HG* X - - Low 16 R2
92mm 99mm KPF221HGF* X X - 45 17 26
115mm Delay in direction of arrows. Relay Reset
18 27
KPF221E, KPF221F, KPF221G*, KPF221GF* Any latched relay is reset
19 by linking terminals 29 and
High Low Fail safe Latch
30 or by interrupting the
R1   * 20 voltage input to terminal 1. 5
DIN96 R2   *
+ 22 Analogue Output 6
PANEL (KPF221E is the standard version)
CUTOUT (Optional) 7
- 21
92 x 92mm KPF221H, KPF221HF, KPF221HG*, KPF221HGF* Reset 8
High Low Fail safe Latch 29 30
R1  * - 9
31 DC Aux Supply
1.25 to 8mm R2  * + 10
(Optional)
thick Relays shown de-energised. 32
A fail-safe relay energises when unit is powered.

The unit meets EN 61010-1 Cat. III, Pollution degree 2 and the relevant environmental The MEGACON policy is one of
and EMC tests specified in EN 61326-2-4 to comply with the requirements of the major continuous improvement, ORDERING EXAMPLE:
Classification Societies. conseq uently e quipmen t Type: KPF221F
supplied may vary in detail from Aux. Supply: 200-240V
this publication. Input: 230V
Range: 45-55Hz
Analogue O/P: 4-20mA

Norway
Denmark
United Kingdom
REF: Datasheet.KPF221x - REV: 2.01/05.2019
www.megacon.com © All rights reserved to Megacon
ELECTRONIC CONTROL AND INSTRUMENTATION Megacon reserves the right to make any changes to the information at any time

You might also like