Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream E2.2N 1250 when set breaker below:
E L S PL 19 0 1 78 J U N 1/8
Coordination for upstream E2.2N 1600 and downstream T5S
Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream T5S with different trip current (such as T5S 400A etc)
2/8
Coordination for upstream E2.2N 1600 and downstream XT3S
Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT3S with different trip current (such as XT3S 200A)
3/8
Coordination for upstream E2.2N 1600 and downstream XT2S
Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT2S with different trip current (such as XT2S 100A)
4/8
Discrimination for EMSB -L4 -HSP
Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream T5N 400
5/8
Coordination for upstream E2.2N 1250 and downstream XT3N
Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT3N with different trip current ( such as XT3N 200 )
6/8
Coordination for upstream E2.2N 1250 and downstream XT1N
Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT1N with different trip current ( such as XT1N 100, 63 )
7/8
Appendix: Discrimination Table
Selectivity/Discrimination tables which have been factory tested are provide by ABB to demonstrate
where total discrimination can be achieved
8/8