Discrimination Report for Anson Road Project

Discrimination for MSB -L4 -HSP

Coordination upstream E2.2N 1600 and downstream E2.2N 1250

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Green)


Downstream ACB E2.2N Ekip Dip LSI 1250 (Red)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream E2.2N 1250 when set breaker below:

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1600 1 12 9 0.2 Off
E2.2N 1250 0.92 12 7 0.1 Off

E L S PL 19 0 1 78 J U N 1/8
Coordination for upstream E2.2N 1600 and downstream T5S

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Green)


Downstream MCCB T5S630 PR221DS LS/I 630 (Red)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream T5S with different trip current (such as T5S 400A etc)

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1600 1 12 9 0.2 Off
T5S 630 1 3 OFF OFF 3

2/8
Coordination for upstream E2.2N 1600 and downstream XT3S

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Green)


Downstream MCCB XT3S 250 TMD 250-2500 (black)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT3S with different trip current (such as XT3S 200A)

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1600 1 12 9 0.2 Off
XT3S MAX Not adjustable Not adjustable Not adjustable Not adjustable

3/8
Coordination for upstream E2.2N 1600 and downstream XT2S

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Green)


Downstream MCCB XT2S 160 TMA 160-1600 (blue)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT2S with different trip current (such as XT2S 100A)

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1600 1 12 9 0.2 Off
XT2S MAX (250A) Not adjustable Not adjustable Not adjustable Max (1600A)

4/8
Discrimination for EMSB -L4 -HSP

Coordination for upstream E2.2N 1250 and downstream T5N

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Red)


Downstream MCCB T5N400 PR221DS LS/I 400 (Blue)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream T5N 400

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1250 0.92 12 7 0.1 Off
T5N 400 1 3 Off Off 6.5

5/8
Coordination for upstream E2.2N 1250 and downstream XT3N

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Red)


Downstream MCCB XT3N 250 TMD 250-2500 (Green)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT3N with different trip current ( such as XT3N 200 )

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1250 0.92 12 7 0.1 Off
XT3N Max ( 250) Not adjustable Not available Not available Max ( 2500)

6/8
Coordination for upstream E2.2N 1250 and downstream XT1N

Upstream ACB E2.2N 1600 Ekip Dip LSI 1600 (Red)


Downstream MCCB XT1N 160 TMD 160-1600 (Black)

Upon above simulation, total discrimination can be achieved between upstream E2.2N 1600 and down-
stream XT1N with different trip current ( such as XT1N 100, 63 )

Breaker L(I1) T1 sec S(I2) T2 sec I3


E2.2N 1250 0.92 12 7 0.1 Off
XT1N Max ( 250) Not adjustable Not available Not available Max ( 2500)

7/8
Appendix: Discrimination Table

Selectivity/Discrimination tables which have been factory tested are provide by ABB to demonstrate
where total discrimination can be achieved

8/8