Professional Documents
Culture Documents
Cooper 230-12 PDF
Cooper 230-12 PDF
Electrical Apparatus
McGraw-Edison® Type EX-7Li®
Single-Phase Internally Fused Units 230-12
McGraw-Edison Type EX-7Li® CAPACITOR
all-film internally fused capacitors APPLICATION
(Figure 1) feature the latest
Cooper Power Systems design Capacitor application requires an
innovations; extended foil, solder- evaluation of the power system to
less connections, CLEANBREAK® determine:
element fusing system and laser- ■ The kvar requirements.
cut aluminum foil. Designed,
manufactured, and tested to meet ■ The most effective location.
or exceed the requirements of all ■ Interaction with system.
applicable ANSI/IEEE and IEC
standards, their low cost per kvar ■ The necessary protection.
makes these capacitors a simple, In general, capacitors are
economical source of reactive installed:
power on electric power systems
■ At the substation, to supply the
for:
system kvar needs most effec-
■ Power factor correction. tively.
■ Voltage support. ■ At or near the load center, to
■ Loss reduction. obtain the optimum kvar supply
and voltage correction.
■ Improving power transfer Figure 1.
capability. ■ At the end of the line, to The McGraw Edison EX-7Li®
achieve maximum voltage single phase internally fused,
■ Releasing system capacity. correction. all-film capacitor
Internally fused, power capacitors ■ In series with a distribution
can be installed individually or in feeder to minimize flicker and Available capacitor unit ratings can
factory-assembled switched or provide voltage support. be obtained by contacting the
unswitched: factory.
■ In series with a transmission
■ Open style indoor and line to minimize the reactance
substation banks.
CONSTRUCTION
of the line, improving stability
and controlling voltage drop.
FEATURES
■ Metal enclosed banks.
Construction features of McGraw-
Note that Cooper Power Systems RATINGS Edison power capacitors include:
does not recommend the use of
internally fused capacitors on pole McGraw Edison capacitors are ■ CLEANBREAK® element
mounted, distribution rack applica- rated in continuous kvar, voltage, fusing system. Each element is
tions. BIL and frequency and are protected with a series
subjected to all applicable connected CLEANBREAK®
McGraw Edison exclusive all-film, ANSI/IEEE or IEC routine tests. current limiting fuse. This
extended foil/mechanically The capacitor unit rated voltage is patented fusing system incor-
connected capacitors provide: the voltage at rated frequency that porates the following features:
■ Low losses (0.15 watt/kvar). can be applied terminal-to-terminal
continuously. See the standard to ■ Polymer fuse card provides
■ Superior electrical performance which the capacitor unit is manu- isolated fuse mounting
and reliability. factured for guidance in operation which prevents potential
above rated voltage. damage to adjacent
■ Environmentally acceptable capacitor elements and
Edisol® ST Non-PCB dielectric Single-phase capacitor units are fuses.
fluid. designed to produce rated kvar at
rated voltage and frequency within ■ Fuses are individually
■ CLEANBREAK® element mounted within a polymer
fusing system. the tolerance of the applicable
standard. As the capacitor’s kvar fuse tube. The tube protects
output is proportional to the the fuse from damage due to
square of the applied voltage, adjacent element failures
proper application requires atten- and fuse operations. This
tion to the applied voltage. design also requires no
TABLE 1
Bushing Characteristics and Weights
60-Hz Withstand
Approximate Net
Creepage Strike 60-Sec. 10-Sec. Weight/
BIL Distance Distance Dry Wet Bushing
(kV) (mm) (mm) (kV) (kV) (kg)
75** 264 159 35 30 1.4
95 264 159 35 30 1.4
125 461 242 60 50 2.3
125 559 242 60 50 2.3
2
Printed on Recycled Paper