You are on page 1of 3

EWG 01.

1, RWG 4020, potentiometer

Technical data Electronic position transmitters/potentiometer

EWG 01.1
Contactless and wear-free sensing of the valve position by means of Hall sensors for signalling the valve position.

Data 3-wire or 4-wire system 2-wire system


Output current IA 0 – 20 mA, 4 – 20 mA 4 – 20 mA
Power supply UV1) 24 V DC (18 – 32 V) 24 V DC (18 – 32 V)
Max. current consumption LED off = 26 mA, LED on = 27 mA 20 mA
Max. load RB 600 Ω (UV – 12 V)/20 mA
Impact of power supply 0.1 %
Load influence 0.1 %
Temperature impact < 0.1 ‰/K
Ambient temperature –60 °C to +80 °C2)/+90 °C2)

Notes on table
1) Power supply Power supply possible via: AC, AM controls or external power supply
2) Ambient temperature Depending on temperature range of the actuator: Refer to name plate

Wiring

2-wire system 3-wire system 4-wire system

EWG 01.1 EWG 01.1 EWG 01.1

4 1 1 2 4 Plug/socket connector XK 1 2 3 4
Plug/socket connector XK Plug/socket connector XK
for customer connection for customer connection
for customer connection
21 22 23 24 20 21 22 23 24
20 21 22 23 24

0 – 20 mA
+24 V 0 V 4 – 20 mA 0 – 20 mA
4 – 20 mA 4 – 20 mA
+24 V 0 V

LED
S1 (0/4 mA) S2 (20 mA)

Measuring point 1 (+)


2-wire system
Measuring point 2 (–) 0/4 – 20 mA
3-wire and 4-wire system

Setting: Setting is performed via push buttons S1 (0/4 mA) and S2 (20 mA). Refer to operation instructions relating to actuator.

Inverse operation: Observe inversed assignment of push buttons S1 and S2 during setting.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.388/001/en Issue 1.15 Page 1/3


EWG 01.1, RWG 4020, potentiometer

Technical data Electronic position transmitters/potentiometer

RWG 4020
On the basis of the actual potentiometer value, the RWG generates a current signal for signalling the valve position.

Data 3-wire or 4-wire system 2-wire system


Output current IA 0 – 20 mA, 4 – 20 mA 4 – 20 mA
1)
Power supply UV 24 V DC (18 – 32 V) 14 V DC + (I x RB), max. 30 V
Max. current consumption 24 mA at 20 mA output current 20 mA
Max. load RB 600 Ω (UV – 14 V)/20 mA
Impact of power supply 0.1 %/V 0.1 %/V
Load influence 0.1 %/(0 – 600 Ω) 0.1 %/100 Ω
Temperature impact < 0.3 ‰/K
Ambient temperature –60 °C to +80 °C2)/+90 °C2)
Transmitter potentiometer 5 kΩ

Notes on table
1) Power supply Power supply possible via: AC, AM controls or external power supply
2) Ambient temperature Depending on temperature range of the actuator: Refer to name plate

Wiring

2-wire system 3-wire system 4-wire system

RWG 4020 RWG 4020 RWG 4020

Plug/socket connector XK Plug/socket connector XK Plug/socket connector XK


for customer connection for customer connection
for customer connection
21 22 23 24 20 21 22 23 24
20 21 22 23 24

0 – 20 mA
+24 V 0 V 4 – 20 mA 0 – 20 mA
4 – 20 mA 4 – 20 mA
+24 V 0 V

(0/4 mA) (20 mA)


N R2 M

Measuring point 1 (+)


3-wire and 4-wire system
Measuring point 2 (–) 0/4 – 20 mA
2-wire system

Setting: Refer to the operation instructions relating to actuator.

Inverse operation: For inverse operation, exchange terminals 7 (red/RD) and 5 (black/BK) on position transmitter board.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.388/001/en Issue 1.15 Page 2/3


EWG 01.1, RWG 4020, potentiometer

Technical data Electronic position transmitters/potentiometer

Potentiometer
Travel sensor for recording the valve position.

Precision wire Precision film


Precision wire Precision film
Data potentiometer potentiometer
potentiometer potentiometer
in tandem version in tandem version
Recommended for OPEN-CLOSE duty Modulating duty OPEN-CLOSE duty Modulating duty
Independent linearity ≤1%
Resistance (standard) 0.2 kΩ 5 kΩ 0.2/0.2 kΩ 1 kΩ/5 kΩ
Resistance (option)3) 0.1 kΩ 1 kΩ 0.5/0.5 kΩ 1 kΩ/1 kΩ
0.5 kΩ 1.0/1.0 kΩ 5 kΩ/5 kΩ
1.0 kΩ 0.1/5.0 kΩ
2.0 kΩ 0.2/5.0 kΩ
5.0 kΩ 1.0/5.0 kΩ
5.0/5.0 kΩ
Resistance tolerance +/– 5 % +/– 10 % +/– 5 % +/– 10 %
Rated power 1.5 W 0.5 W 1.5 W 0.5 W
Max. wiper current 30 mA 0.1 mA 30 mA 0.1 mA
Lifetime 100,000 cycles 5•106 cycles 100,000 cycles 5•106 cycles
Synchronous operation – – +/– 1.5 % +/– 2.0 %
2)
Ambient temperature – 60 to +120 °C – 60 to +90 °C – 60 to +120 °C – 60 to +90 °C

Notes on table
2) Ambient temperature Depending on temperature range of the actuator: Refer to name plate
3) Resistance (option) Further options on request

The position of the valve can be transmitted as a continuous signal by a potentiometer. The potentiometer is installed in the control unit of the actuator.
We recommend:
Using the potentiometer as voltage divider. Depending on the supply voltage, suitable series resistors are to be provided. Please observe max. rated
power.
For the tandem version, two signals can be evaluated by two potentiometers, e,g, one signal for external controls or one signal for AUMA AC integral
controls.

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

Y004.388/001/en Issue 1.15 Page 3/3