Full Modularization, Intelligent Management

PART 1 PART 2 PART 3


PA R T
ONE

O ve r v i ew
Secret▲

Drive for Growth

ZTE energy has more than 1500 engineers, 80% of whom are
senior engineers or experts

ZTE energy has more than 600 worldwide patents

4 R&D centers in China:


Shenzhen, Nanjing, Wuhan and Chongqing

4
Secret▲

Reliable Data Center Partner


11-year experience in data center field
Leading block DC innovation
Leading modular DC industry
Leading telecom DC solution

2009 2014 2015 2017 2019

Industry Leader
Technology Leadership l Large-scale application of
Wide Application l Application of Indirect fully-modular warehouse
Applied to BAT & major evaporative cooling data center
Industry Fisrt l
operators l First application of fully- l Large-scale overseas
Entered the data Constructed the
modular warehouse application of edge-DCs
largest MDC in Asia l Becomes a leading E2E
center field data center
DC solution provider

5
Secret▲

Continuous Innovation for the 5G Era

Core-DC

Regional-DC
Edge-DC Full Scenario: a full series of
data center products and
solutions covering full scenario
including Core-DC, Regional-DC
Outdoor Indoor Warehouse and Edge-DC.
End-to-end: provides full lifecycle
data center services including
CDC6220 CDC6240 CDC6300 MiniDC2000 FlexDC6100 MDC8200 CDC8100
consulting, planning, design,
MDC8300 construction and O&M
management.

Full Modularization: extends


modular design of IT cabinets to
all the other data center
Indirect subsystems, such as cooling,
UPS HVDC PDR In-Row Cooling Evaporative Rack iDCIM
cooling
power distribution, management,
and OA.

6
PA R T
TWO

Edge Data Center


Solution
Secret▲

ZTE Edge Data Center Solution Highlights


ZTE's edge data center solution consists of cabinets, power supply, cooling, management and ICT equipment, which can be
customized according to indoor or outdoor use. It features high integration, fast deployment, green & energy saving, and
intelligent management.

High Integration Fast Deployment Energy Saving Intelligent Management


Ø Efficient integration of M&E and Ø Highly integrated and modular Ø Efficient power supply and Ø Multiple protocols supported and
ICT devices design cooling unified management
Ø 3 power supply modes Ø The data center modules are Ø Adjust the power capacity and Ø Visual and remote management
Ø Cold and hot isolation to prefabricated in factory cooling capacity as required through all types of terminals
optimize air flow Ø Modular construction and Ø New-generation indirect Ø All-round security protection and
convenient installation evaporation cooling technology reliability assurance

8
Secret▲

ZTE Edge Data Center Solution Overview

Micromodular
data center Container Cluster

Municipal iDCIM
Core

District
Convergence

MiniDC All-in-one Container

Access

Indoor Edge DC Outdoor Edge DC

9
Secret▲

Micromodular Data Center Solution

ZTE ZEGO micromodular data center integrates cabinets, cooling, power distribution, cabling, management and lighting
subsystems. Its application scenario is Indoor Edge DC (Municipal Core and District Convergence) .

iDCIM interface PDU PDR Cabinet LED tube Cable tray Base Moveable skylight

NVR

Mobile APP

MDC8200 MDC8300 FlexDC6100 iDCIM server

UPS/HVDC Battery In-Row cooling Water leakage Access control Temperature & humidity Camera Management cabinet
detection rope Sensor
10
Secret▲

Technical Specifications
MDC8200 MDC8300 FlexDC6100

With In-Row Cooling With Underfloor Cooling With Decoupling Design

• Max. 42 cabinets • Qty. of cabinets: customizable • Max. 42 cabinets


• Recommend power density: • Recommend power density: 3~5kW • Recommend power density:
4~12kW • Cabinet dimensions (H*W*D): 4~12kW
• Cabinet dimensions (H*W*D): 2000/2200*600*1200mm • Cabinet dimensions (H*W*D):
2000/2200*600*1200mm • Cold aisle containment by default 2000/2200*600*1200mm
• Cold aisle containment by default (width:1.2m) • Cold aisle containment by
(width:1.2m) default(width:1.2m)
• Supporting non-standard cabinet
dimensions

11
Secret▲

Solution Advantages

Flexible Investment Fast Deployment Energy Saving Intelligent Management

Ø Expansion per MDC, Ø Factory prefabrication, on- Ø Aisle containment avoids Ø Unified management of
matching explosive site installation, easy and hot and cold air mixture infrastructure and IT
service growth fast Ø Various free cooling equipment
Ø Staged investment, low Ø Delivery within 90 days solutions, HVDC and Ø 3D user interface that is
initial investment, better (standard configuration) green energy easy to use
ROI Ø Remote management
function

12
Secret▲

MiniDC Solution
ZTE ZEGO MiniDC integrates power distribution, cabling, monitoring, cooling, sensor, access control. It uses fully-enclosed
design featuring low noise and electromagnetic and interference prevention. It can be transported as a whole machine and is
plug-and-play. Its application scenario is Indoor Edge DC (District Convergence and Access) .

Smoke Temperature and


sensor unit humidity sensor

Monitoring unit PDU

Door contact/lock
UPS unit

Battery Cooling unit

13
Secret▲

Technical Specifications

MiniDC2000 All-in-one MiniDC2000 Twins MiniDC2000 Triple

• Total IT power consumption: • Total IT power consumption: • Total IT power consumption:


≤2.7kW ≤6kW ≤10kW
• Available space: 20U • Available space: 44U • Available space: 70U

14
Secret▲

Solution Advantages

Fast deployment Secure and reliable


Prefabricated in factory to minimize on-site installation One-hour battery backup, support for emergency response,
time to 3 hours. It is plug-and-play. log management and access control monitoring

High-efficient integration Intelligent management


All-in-one design, saving site space resources and 7x24-hour intelligent management, rapid fault locating and
reducing construction costs problem solving

Flexible expansion Energy saving


Fully-enclosed design, low noise and dust-proof, Cold / hot aisle isolation, efficient cooling, optimized
flexible deployment, and elastic expansion airflow organization

15
Secret▲

Container Data Center Solution

Container Data Center integrates all subsystems including cabinets, cabling, power distribution, cooling, fire
fighting, lighting, management into one or more standard containers (20-feet or 40-feet). Each container is
prefabricated, pre-installed and pre-commissioning in factory. The application scenario of container data center is
Outdoor Edge DC (Municipal Core, District Convergence and Access)

Container Cluster All-in-one Container

Cable tray Fire control Battery

AC Outdoor IT Room
Unit

NOC (iDCIM)

Power Room

AC outdoor unit IT cabinet In-row AC UPS PDR

16
Secret▲

Technical Specifications

CDC6300 CDC6240 CDC6220

• Container cluster • All-in-one Container • All-in-one Container


• 20 or 40 feet container with • 40 feet standard container • 20 feet standard container
3300/3600mm in height. • 8 or 10 cabinets, dimensions • 4 cabinets, dimensions (W*D*H,
• 30 to 200 cabinets, dimensions (W*D*H, mm): 600*1000*2000 mm): 600*1000*2000
(W*D*H, mm): 600*1000*2000 • In-row cooling or CRAC • In-row cooling
• 4kW to 12kW per cabinet • 4kW to 8kW per cabinet • 5kW to 10kW per cabinet

17
Secret▲

Solution Advantages

Energy Saving Intelligent Management


Ø PUE low to 1.2~1.5 Ø Unified management for
Ø More than 60% energy saving infrastructure
Ø TCO decreases up to 30% Ø 3D visible portal, easy to read
and understand
Ø Remote access function

Fast Deployment Flexible Expansion


Ø Factory prefabrication, short TTM Ø Expansion per CDC, matching
Ø No civil engineering, on-site explosive service expansion
installation Ø Staged investment, low initial
Ø Suitable for harsh environment, investment, better ROI
easy to move Ø High power density, saving space

18
Secret▲

Mass Edge DC Access and Smooth Extension

The management of edge DC supports two-layer or


three-layer structure. Each edge DC is configured with
iDCIM
Core DC /
a collector or server which is connected with the unified
Regional DC iDCIM platform. The iDCIM system supports the
measurement of up to 1 million parameters. Its
capacity can be dynamically expanded by adding
management servers.

10000* 1250* 100* 100* 1250* 2500*


Indoor Egde DC Indoor Egde DC Indoor Egde DC Outdoor Egde DC Outdoor Egde DC Outdoor Egde DC
(Access) (Convergence) (Core) (Core) (Convergence) (Access)

19
Secret▲

Functional Architecture of iDCIM System

Display screen Phone/Pad PC


Portal
Display
Web Service (2D/3D)

O&M Management Business Management Basic Management


Security Protection Report Mgmt Assets Mgmt Configuration Mgmt Rights Mgmt

Business Virtual DC Alarm Mgmt Capacity Mgmt Display Mgmt Interface Mgmt
Application
Availability Mgmt Patrol Inspection Tenant Mgmt Topology Mgmt

Process Mgmt Energy Mgmt Log Mgt

Basic
Service Unified Resource Management Unified Alarm Management Unified Performance Management

Data
Infrastructure Power and Environment Monitoring Access Control Group Control System ··· Third Party System
Collection

20
Secret▲

Multiple Protocols Supported and Unified Management

Enterprise / Park
Management System

Northbound
interface

Infrastructure SNMP WEBSERVICE ODCC 3rd Party

Sensor PDR BACnet SNMP BA


Southbound
SNMP Web
Chiller Battery interface Fire control
Service
OPC Security
Pump UPS/HVDC
HTTP Protection
YDN23
Power and
Tower HVAC BACnet
HTTP iDCIM Environment

Camera Door MODBUS Lighting


MODBUS

21
Secret▲

All-round Security Protection and Reliability Assurance

Security monitoring: access control through card,


01 password or biometric identification, and inside and outside
video surveillance with no dead angle through HD infrared
cameras.

Alarm management: real-time alarm detection, fast fault


02 location, building alarm knowledge base, and precise fault
recovery.

Availability management: annual availability curve of the

03 data center and statistics of the alarms to find the major


reason affecting availability.

Linkage control: fire control and access control linkage, fire


control and sound-light alarm linkage, access control and
04 sound-light alarm linkage, power and environment linkage.

Rights management: security control over user's operation


05 and access resources, security event information record and
uniform security policy.

22
Secret▲

Visual and Remote Management of All Types of Terminals

3D/2D

1. Access anytime anywhere: display screen, PC, PAD, APP

2. Multiple alarm types: SMS, Email, telephone, voice, sound-light

3. Precise fault location and remote control

23
PA R T
THREE

Application Cases
Secret▲

Global Data Center Partners

China Mobile
China Telcom
China Unicom
Tencent
Alibaba
France Baidu
Gov
Algeria
Hong Kong
Bangladesh
Ethiopia
Philippines
Nicaragua
Uganda Kenya Thailand
Tanzania Indonesia
Zimbabwe Mozambique
Chile
Lesotho

280+ Cases 90,000+ Cabinets 1,000,000+m2 Construction Area


25
Secret▲

China Telecom Deployed the First Container Edge DC in Philippines

Challenges
• It takes long time for civil work.
• Complex topography, long distance, difficult site
investigation, changeable climate
ZTE Solution
• 20-foot all-in-one container data center
• Power: one set of 1000A DC power (4-hour battery
backup time); One set of integrated UPS (15-minute
battery backup time); Diesel generator.
• Cooling Capacity: 12.5kW per CRAC, N+1 redundancy
• iDCIM: video surveillance, access control, fire control
and remote control
Highlights
• Highly integrated design, fast deployment
• Integrated and intelligent management system to
enable all-around unattended services
• Environment and power monitoring to ensure safety
26
Secret▲

Network Architecture

Micromodular Data Center


Core layer
or Container Cluster

Same site Same site

Convergence Micromodular Data Center


IPRAN layer or All-in-one Container

PeOTN+IPRAN

Access layer
PeOTN IPRAN

27
Secret▲

China Telecom Deployed Edge DC in Xiong'an Intelligent Transport

Challenges
• Need to be flexible to deploy and easy to manage
• Tight construction period for rapid service launch
• High server (MEC server) power consumption
ZTE Solution
• All-in-one container, 10kW per cabinet
• Power: one set of 600A DC power, four sets of 100Ah
SmartLi Lithium-iron batteries
• Cooling capacity: 25kW per In-row AC, 1+1 redundancy
• iDCIM: video surveillance, access control, fire control
and remote control
Highlights
• All-in-one container: easy to deploy
• Product arrived within 20 days and deployment
completed in 3 days: rapid service launch
• 2-hour battery backup: uninterrupted service
• Intelligent management: 7x24 unattended service
28
Secret▲

System Architecture

• Build LT-V and 5G networks • All-in-one container with isolated


• Deploy a perception system cold/hot aisle
including camera and laser radar • Modular power distribution and in-row
• Enable coordinated data AC unit, SmartLi Lithium-iron batteries
processing based on MEC and Edge DC • Intelligent management (iDCIM)for
cloud computing MEC Server 7x24-hour unattended service
Switch

BBU

5GC Internet

a collaborative service system that integrates vehicle, road, network and cloud
29
Secret▲

China CITIC Bank MDC and Mini DC Data Center


Hardware infrastructure of the core room can no longer meet the requirements of construction specifications. With the rapid development of Internet finance, cloud
computing and big data, the processing capacity and data scale of commercial bank data centers have shown an exponential growth trend. The shortcomings of high
energy consumption, high construction, low utilization rate, and low use efficiency of the existing core room are becoming more and more obvious, and the operating
cost is facing severe tests.

High efficiency, Reliable, Green data center

Headquarter Different scenario different


Different standards Small branch
Branch bank solution

Hard to meet the growing Modular design, prefabricated,


redundant parts, Green

Micro-modular Mini data


High Opex, High Cost data center center Intelligent management, 40%
reduction of maintenance

30
Secret▲

Reliable and Secure Financial Data Center (Indonesia BOC)

Data Center for Banking Service


l The Bank of China (Indonesia) required to build a secure
and reliable data center to support its local businesses.

Solution
l Modular Design, 16 racks, 4kW per rack

l In-row AC, cold aisle containment

l Key components redundancy

l Ensure stable and safe operation of banking business

31
Full Modularization, Intelligent Management