Your system for fire detection, Application: complex building and Sinteso control panel FC2080 –

alarming and control: Sinteso large campus uniquely safe and flexible
Power supply I/O card (FUE) FCI2007-A1 ➔ 0 to 7x
– Transmission unit for alarms and faults
– Max. 1x per card cage (5 slots) FCA2008-A1
Ethernet Management 3 Power supply ➔ 1 to 4x** Order no.: S54400-A20-A1
FS cloud Customer platform from
Carrier (19“, power supply) FHA2022-A1
network
Siemens
Network in a complex building, Description ➔ 1 to 4x** I/O card (programmable) FCI2008-A1
applications 1
for example a hospital. In complex buildings, the fire safety system can – 19“ carrier incl. 2x power supply
(150 W) cascaded
➔ 0 to 10x
– 12x open collector inputs/outputs
be adapted to local circumstances. The control 2 Order no.: S54400-B24-A1 Order no.: S54400-A6-A1
Remote access to panels as well as fire terminals are networked 3
Remote access
with SintesoView/ management platform together via clusters (FCnet/SAFEDLINK). These
FG2004 Router + Firewall + VPN Power supply kit (150 W, B) FP2005-A1 I/O card (sounder/monitored) FCI2009-A1
Sinteso Touch
(Sinteso Connect clusters are interconnected via industrial LAN
technology per backbone (FCnet/LAN) to create ➔ 0 to 1x per each FHA2022-A1 ➔ 0 to 7x
X300 Gateway) Remote access with
4 5a 5a – For extending the FHA2022-A1 by 150 W – 8x monitored outputs
Ethernet switch Sinteso Mobile an EN 54-compliant overall system.
(modular) Order no.: A5Q00018779 – Max. 1x per card cage (5 slots) FCA2008-A1
FN2012-A1 Order no.: S54400-A21-A1
6a 6a
7 Battery pan (19“) FHA2021-A11
Backbone (FCnet/LAN) Benefits ➔ 1x per each FHA2022-A1
–O
 nly one remote transmission to fire brigade – Battery pan incl. 2x tension belts Extensions extinguishing
Ethernet switch (modular) Ethernet switch (modular) Ethernet switch (modular)
necessary for entire system –F or max. 2x batteries 100 Ah
FN2012-A1 FN2012-A1 FN2012-A1 4 5b (to be ordered separately) 5b Card cage ➔ 0 to 8x
–O
 ne interface to common pager system
–O
 verview of entire system from any configured Order no.: S54400-B23-A1
Card cage (1 sector) FCA2046-A1
terminal 3 6b 8 Order no.: S54392-B8-A1
–F
 iber-optic backbone with high immunity to Mechanical installation
Manual call point
electromagnetic disturbance Multi-sector extinguishing
FDM223 –S
 ystem-wide EN 54-compliant operation
–T
 imely hand-over thanks to parallel commis-
4 1 9“ carriers Cable kit (FCA2046-XCM2003) FCA2051-A1
– Connection to the extinguishing terminal
sioning of individual panels or clusters Carrier (19“, card cage) FHA2023-A1 ➔ 0 to 3x XCM2003-A2
–D
 istributed intelligence: complete control in –F
 or max. 2x card cages (5 slots) FCA2008-A1 – 1x per extinguishing sector
FDnet Fire terminal
the event of a fire is mapped in a cluster; this 9 Order no.: S54400-B25-A1 Order no.: S54392-K13-A1
Sounder (touch) FT2080 enables ideal adaptation to structural as well
Fire control panel Fire control panel Fire terminal Carrier (19“, option) FHA2024-A1 ➔ 0 to 8x
FDS224-R
FC2020 FC2020 FT2040
as process requirements Cable kit (FCA2046-FCA2046) FCA2049-A1
–F
 or options, max. height 135 mm on two-level
Cluster Sinorix
extinguishing 3 hat rail, length 430 mm; max. 1x key safe
– Connection to the next FCA2046 card cage
Order no.: S54392-K15-A1
(FCnet/SAFEDLINK) solution adapter SDA 300 (IFAM co.)
Sounder base
Extinguishing terminal Order no.: S54400-B26-A1 Cable kit (FHA2053-FHA2053) FCA2048-A1
FDSB291 Floor repeater
terminal FT2010 (4 sectors) XCM2003-A2 – Connection to the next FHA2053 carrier
Extinguishing carrier (19“, card cage) Order no.: S54392-K16-A1
Fire control panel Fire control panel
FC2060 FC2080 1 FHA2058-A1 ➔ 0 to 2x
– For max. 4x card cages FCA2046-A1 Cable kit (2nd 19”, FCA2053) FCA2050-A1
3 Order no.: S54392-B7-A1 – Connection to the second 19” housing
Fire damper with actuator ASA neural Extensive network spanning large distances, Description Order no.: S54392-K14-A1
fire detector
FDOOTC241 for example a production plant. A campus comprises numerous, independent
Extensions fire
Fault transmission
buildings. These have their own organization 1 6b Extinguishing cards ➔ 0 to 8x
Manual call Input module
and structure that can be mapped ideally with 5a Card cage ➔ 0 to 6x Extinguishing card XCI2005-A1 ➔ 0 to 8x
Input/output module a cluster of up to 16 panels. The backbone Card cage (5 slots) FCA2008-A1
Alarm transmission point FDCI222 Order no.: S54392-A7-A1
FDCIO222/224 FDM221 connects these clusters to an EN 54-compliant Basic equipment – Slots for max. 5 module bus cards
network. Order no.: S54400-B28-A1
Voice sounder Operation
beacon ASA – Neural
Fire control panel
1 Pedestal cabinet ➔ 1x*
FDS227-RR Collective
detector
fire detector
FDOOT241-A FC2040 Benefits Housing (19“ pedestal cabinet) FH2080-AA 6a Module bus cards ➔ 0 to 37x 7 Operating unit ➔ 0 to 1x

Sinteso –
– Housing incl. base, door and plan compartment A3 Line card (FDnet) FCL2001-A1 ➔ 0 to 30x Operating unit FCM2028-A2 ➔ 0 to 1x
FDnet ASA – Heat detector
FDT241
– Intelligently arranged network structure with
clearly defined clusters
– Dimensions incl. base: – 4x FDnet lines and max. 252 addresses – Standard operating unit
Sounder beacon 601x2204x615 mm (WxHxD) Order no.: A5Q00009875
base FDSB226-WR Radio Radio manual –O  nly one control panel necessary to access – Communication over FCnet
Stub line Order no.: S54400-C103-A1
gateway call point entire system with all subnetworks Order no.: S54400-F83-A1
Line card (collective) FCL2002-A1 ➔ 0 to 30x
FDnet FDCW241 FDM273

panels, network
Aspirating – Backbone is EMC-protected and EN 54-compliant – 8x collective lines
smoke detectors –S  imultaneous work at multiple stations allows 2 Processor unit ➔ 1x* Order no.: A5Q00010502 8 Operating add-ons ➔ 0 to 2x***
Floor repeater FDA221/FDA241 for efficient commissioning
ASA – Neural Manual call point Processor unit (19“, FC2080) FCC2002-A1 ➔ 1x
display FT2011 ASA – Flame Operating add-on (2xLED display) FCM2038-A2
radio fire FDM223-Ex –C  an be connected to a pager system for the –C  ard cage (CPU) with Line card (MS9i) FCL2003-A1 ➔ 0 to 30x
Input/output Wide- detector detector ➔ 0 to 2x per operating unit
FDF241-9 entire system, possible from a central point •C PU card (FC2080) incl. network module – 2x MS9i lines and max. 100 addresses – 48x LED groups

and accessories
module spectrum FDOOT271 ASA – Multi-sensor detector
FDCIO222 smoke FDOOT241-A9-Ex –D  istributed intelligence: complete control (SAFEDLINK, CC) FN2010-A1 Order no.: A5Q00010044 Order no.: S54400-B146-A1
detector in the event of a fire is mapped in a cluster; •C ommunication card (FC2080) incl. network
FDO221 this enables ideal adaptation to structural module (SAFEDLINK, CC) FN2010-A1 Line card (AnalogPLUS) FCL2005-A1 ➔ 0 to 30x Operating add-on (4xLED display) FCM2036-A2
ASA – Wide- Air sampling Aspirating and process conditions •1 free slot for an optional second – 4x AnalogPLUS lines and max. 126 addresses ➔ 0 to 1x per operating unit
spectrum smoke smoke detection kit smoke detector –S  ecurity personnel have entire campus in view CPU card (FC2080) per line
detector FDO241 FDBZ290 ICAM IAS – 96x LED groups
Extinguishing Alarm – The right information at the right place: • 2 free slots for module bus cards Order no.: S54400-A107-A1
ASA – Linear Mimic Order no.: S54400-B147-A1

Planning Tool
control unit XC1001-A indicator
Line adapter (Ex) smoke detector display driver predefined views can be displayed according –C  ard cage (5 slots) with slots for
FDCAI221
FDCL221-Ex FDL241-9 FT2001-A1 to customer requirements over the entire max. 5 module bus cards Line card (interactive) FCL2006-A1 ➔ 0 to 30x
system; all controls can be configured to – Cable kit for connecting an optional operating unit – 1x interactive line and max. 126 addresses 9 Extinguishing terminal ➔ 0 to 2x
fulfill site-specific requirements Order no.: S54400-B17-A1 Order no.: S54400-A108-A1 Extinguishing terminal (4 sectors) XCM2003-A2
I mportant notice: ➔ 0 to 2x
Simplified drawing without additional network hardware and
CPU card (FC2080) FCC2004-A1 ➔ 0 to 1x Line card (interactive Ex) FCL2007-A1 Order no.: S54392-B4-A1
ASA – Neural Sinorix safety components. Allowed configurations are described in the – Second CPU card for redundant operation ➔ 0 to 30x Extinguishing terminal (1 sector) XCM2002-A2
siemens.com/sinteso fire detector extinguishing document “Network Security Guidelines”, Doc. ID A6V101039125. Backbone (FCnet/LAN) Order no.: S54400-A18-A1 – 1x interactive Ex line and max. 32 addresses
Manual release FDOOT241-A9 solution Contact your Siemens IT Security expert for details. Cluster (FCnet/SAFEDLINK) ➔ 0 to 2x
Order no.: S54400-A134-A1 Order no.: S54392-B3-A1

* Number of units to be installed


** if 3 or 4: split into two housings
*** max. 120 LED groups per operating unit

Topology 1 Topology 2 Integrated Extinguishing control planning


© Siemens Switzerland Ltd, 2019
are binding only when they are expressly agreed upon in the concluded contract.
course of further development of the products. The requested performance features
specifically reflect those described, or which may undergo modification in the
Up to 16 panels can be networked in a cluster (FCnet/SAFEDLINK) – if connected Up to 64 panels in one EN 54-compliant system with widely varying combinations Single-sector extinguishing
to a management platform. Without a management platform, even up to 32 panels of clusters and backbone – and with connection to a management platform via a
contains general descriptions and/or performance features which may not always
Subject to changes and errors. The information given in this document only Combined fire detection and extinguishing control panel FC20 operating as a single-sector extinguishing system. FC20 works with most types of extinguishing

Article no. BT_0083_EN (Status 04/2019) can be networked. customer network. systems for room or object protection. A single-sector installation consists of a single flooding zone and cylinder bank. In case of a fire, the extinguishing
agent flows through the manifolds to the flooding zone and is distributed there by the nozzles. The system can be optionally configured with a reserve
cylinder battery.

Tel +41 58 724 24 24


Remote transmission
Management
Ethernet Management
to fire brigade Flooding zone
platform from
Customer
Switzerland
platform from
Siemens FS cloud Siemens
network
6300 Zug
Theilerstrasse 1a applications
Global Headquarters
Smart Infrastructure
Remote access Remote access to Control and Indication Discharged contact Automatic fire detectors
with SintesoView/ management platform Equipment
FG2004 Router + Firewall + VPN
Sinteso Touch Fire safety
(Sinteso Connect
Siemens Switzerland Ltd 2019
EN54-2 (PSE: EN54-4)
X300 Gateway) Remote access with
Published by FC2020 / FC2040
Ethernet switch Sinteso Mobile
(modular)
FN2012-A1
Extinguishing terminal
(remote) XT2001-A2
Remote access to Backbone (FCnet/LAN)
Ethernet management platform
Ethernet switch (modular) Ethernet switch (modular) Ethernet switch (modular) Ethernet switch (modular)
FN2012-A1 FN2012-A1 FN2012-A1 FN2012-A1 Alarm sounder

Actuator
Loss of agent Ventilation system
contact
Without connection to a Optical Signaling
management platform: Equipment
up to 32 panels can be
networked in a cluster.
Overpressure
flap
Electrical automatic control and delay Emergency hold
device components for gas DM1103-S
extinguishing system operating system
EN12094-1

Cluster Fault transmission Cluster Cluster Extinguishing control kit (1 sector) XCA2005-A1
Extinguishing terminal (1 sector) XCM2002-A2
Cylinder battery Manual release
DM1103-L Alarm indicator
(FCnet/SAFEDLINK) (FCnet/SAFEDLINK) (FCnet/SAFEDLINK)
Alarm transmission

Caption:
FDnet
Electrical line
Manifold (distribution pipe)
Control pipe

Multi-sector extinguishing
Combined fire detection and extinguishing control panel FC2080 operating as a multi-sector extinguishing system. A multi-sector installation consists of a
Fault transmission
single cylinder bank shared with multiple flooding zones, via selector valves. In case of a fire in one of the flooding zones, the corresponding selector valve
is opened and the necessary groups of cylinders are released. The extinguishing agent flows through the manifolds to the flooding zone. The system can
also be optionally configured with a reserve cylinder battery.
siemens.com/perfect-places Alarm transmission

#CreatingPerfectPlaces I mportant notice: I mportant notice:


Simplified drawing without additional network hardware and Simplified drawing without additional network hardware and
safety components. Allowed configurations are described in the safety components. Allowed configurations are described in the
document “Network Security Guidelines”, Doc. ID A6V101039125. document “Network Security Guidelines”, Doc. ID A6V101039125.
that’s Ingenuity for life. Contact your Siemens IT Security expert for details. Contact your Siemens IT Security expert for details.
Automatische Brandmelder Automatische Brandmelder
When building technology creates perfect places – Characteristics of topology example Key data Characteristics of topology example Key data
– Easy networking of panels – Max. number of networkable panels: 32 –E
 N 54-compliant networking of up to 64 panels –M
 ax. number of networkable panels
– Operation of panels as standalone solution or – Max. number of networkable panels if via backbone incl. clusters (EN 54-compliant): 64
networked with a total length of up to 1,280 km connected to a management platform: 16 –E
 xtensive networks spanning long distances –M
 ax. number of clusters: 14
...
For every stage of life.
Löschbereich 1 Löschbereich 16
– Existing cable infrastructure can be used – Max. distance between panels with –H
 ighest system availability thanks to system- –M
 ax. number of networkable panels Gruppen- Gruppen-
ventil 2 ventil 1
copper cable: wide redundancy per cluster: 16
our aim is to create perfect places.
• without repeater: 1 km –P
 anels in different clusters can communicate –N
 umber of panels with system-wide view: 5
Überdruckklappe Überdruckklappe
With our people and technology, our products and services, • with repeater (FN2002-A1): 2 km with each other
– Max. distance between panels with –E
 ven with these network structures, a

Löschmittelüberwachung
fiber-optic cable: system-wide transmission system including
you improve their lives. • multi mode (FN2007-A1): 4 km firefighting periphery can be implemented Alarmindikatoren Alarmindikatoren

Improve the places where they spend their lives and • single mode (FN2006-A1): 40 km at a central contact point
–M  ax. number of panels with –D
 istributed building complexes can be
system-wide view: 5 ideally protected Löschmittelbehälterbatterie
People spend about 90 percent of their time indoors. –B
 ackbone realized with fiber-optic cable
Sinteso Planning Tool Panels, network and accessories
SintesoView/Sinteso Touch, Sinteso Mobile
For remote operation using SintesoView and Sinteso
Ethernet
Management
Touch, a Windows-enabled device is either connected
Customer
Management
Network components Extension and networking options
to the Internet or customer network via LAN, WLAN,
or mobile network operator. The signals are then FS cloud network
platform from
Siemens
platform Panels Slide-in/card options
transmitted to an Ethernet switch that connects to applications Third-party interface Backbone Fiber-optic converter
the backbone. This connection is protected against The building management platform Modbus gateway NK8237.2 Ethernet switch (modular) FN2012-A1, Optical fiber networking
unauthorized access by a firewall. A license key Desigo CC™ is connected via Ethernet. The NK8237 is used as a gateway be- Order no.: S54400-B152-A1 modules FN2006-A1 (SM)
provides access to the fire protection system. The It is either directly connected to the tween Sinteso and Modbus devices. and FN2007-A1 (MM)
The Ethernet switch connects clusters
device serves as a virtual terminal, offering the Remote access with Remote access to backbone (via Ethernet switch) or via It provides for bidirectional Modbus to the backbone. In case of increased With these optical fiber network­
management platform the customer network. In each case the Line card (FDnet) Line card (collective) Line card (MS9i) Line card Line card Line card I/O card (FUE) I/O card I/O card
same user interface as the operating station or SintesoView/Sinteso Touch Router + Firewall + VPN RTU and TCP connectivity to Sinteso redundancy requirements, a cluster can ing modules, Sinteso stations can
FCL2003-A1 (AnalogPLUS) (interactive) (interactive Ex) FCI2007-A1 (programmable) (sounder/monitored)
adequate safety measures (e.g. Firewall, FCL2001-A1 FCL2002-A1
panel (FT2080, FT2040, FC20xx) in the fire detec- fire protection systems. It has protec- be linked to the backbone using a second be linked to the FCnet/SAFEDLINK For 2 MS9i address- FCL2005-A1 FCL2006-A1 FCL2007-A1 For alarm and fault FCI2008-A1 FCI2009-A1
For 252 FDnet To connect collective
tion network. VPN etc) have to be used. Web clients tion, routing and logging capabilities system bus over great distances
Remote access with panel and a second switch. This applies, devices on max. Siemens standard detectors able lines (max. 100 For 4 addressable For 1 addressable For 1 addressable transmission. 12 programmable 8 monitored
I mportant notice: and apps for smartphones and tablets built in. The gateway does not replace by glass fiber cable. The redundant addresses). AnalogPLUS lines interactive line interactive Ex line inputs/outputs with sounder lines or
FG2004 Sinteso Mobile for example, for clusters with more 4 loops or 8 stubs. on 8 stubs (MS7/9, MS24, Order no.:
The user interface of the Sinteso Mobile app for Simplified drawing without additional network hardware provide remote access to the manage- the firewall which protects the Sinteso than 512 detectors/manual call points or clusters feed allows EN 54-compliant DS11/Sigmacon/ Order no.: (max. 126 addresses (max. 126 addresses). (max. 32 addresses). S54400-A20-A1 selectable behavior monitored outputs.
Order no.:
Android smartphones has a tabular design and (Sinteso Connect and safety components. Allowed configurations are ment platform. system against unauthorized access networking even if the network- SynoLINE600, FDOOT241-9 A5Q00010044 per line). Order no.: Order no.: in degrade mode. Order no.:
with remote transmission in systems with more A5Q00009875
allows complete system access. Alarms and faults X300 Gateway) Ethernet switch described in the document “Network Security Guidelines”, and cyber attacks. ing module is remote. and FDOOT241-A9). Order no.: S54400-A108-A1 S54400-A134-A1 Order no.: S54400-A21-A1
than 512 detectors.
are distinguished by color. Doc. ID A6V101039125. Contact your Siemens IT Security Order no.: A5Q00010502 S54400-A107-A1 S54400-A6-A1
(modular) expert for details. Order no.: S54461-C7-A1 – 4 Ethernet interfaces Characteristics:
FN2012-A1 – 2 slots for optional Ethernet modules (ring). – Two independent, galvanically
FC2020 – – – – – – – – –

Backbone Fire control panel (4-loop) Fire control panel Fire control panel Fire control panel
These must be ordered separately:
•V N2001 Ethernet module (copper/electric),
separated channels
– SC connections for optical FC2030
FC2040


















(FCnet/LAN) max. 100 m cables
FC2040-GA* FC2040-AA FC2040-AE FC2040-AG – Two redundant, monitored FC2060 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Order no.: S54400-A42-A1
consisting of: consisting of: consisting of: power feeds EN 54-approved FC2080 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
consisting of: • VN2002 Ethernet module (multi mode),
Clusters can be networked via an Ethernet back- Operating unit Operating unit Operating unit – Earth fault monitoring Panels Slide-in/card options
Operating unit optical Ethernet, max. 4 km
bone, using industrial LAN technology. Siemens is – Optional: event printer FTO2001 – Optional: event printer FTO2001 – Optional: event printer FTO2001 – Installation in the station or
– Optional: event printer FTO2001 Order no.: S54400-A43-A1
the first manufacturer who offers this as EN 54- – Optional: key switch KABA FTO2005 – Optional: key switch KABA FTO2005 –O ptional: key switch KABA remote
– Optional: key switch KABA FTO2005 • VN2003 Ethernet module (single mode),
approved solution. With standard IT architecture, FTO2005 – Can be installed upright or
Operating add-on Operating add-on Operating add-on optical Ethernet, max. 40 km
building structures and organizational processes horizontally on a DIN rail
– Optional: 48 or 96 display groups – Optional: 48 or 96 display groups – 48 display groups each with one Operating add-on Order no.: S54400-A44-A1
can be ideally represented. – FN2006-A1: Single-mode Network module (SAFEDLINK) CPU card RS232 module RS485 module (isolated) Loop extension (FDnet) Sounder module Extinguishing card
each with one green/red and one each with one green/red and one green/red and one yellow LED –9
 6 display groups each with one
– Fault output: relay contact, floating transmission up to 40 km FN2001-A1 FCC2004-A1 (isolated) FCA2002-A1 FCI2003-A1 FCA2005-A1 XCI2005-A1
Characteristics of networking via backbone yellow LED (overall) yellow LED (overall) (overall) green/red and one yellow LED With this module, the station can be For redundant FCA2001-A1 This is needed, for example, for oper- The loop extension makes The sounder module Consisting of:
–E  thernet switch to connect a cluster (FCnet/ – Optional: 96 display groups each with The FN2012-A1 additionally needs the connection Order no.: S54400-A109-A1 networked via the cluster. For this CPU operation. This module is ating the following modules: it possible to double the has connections for 4 – Module for one extinguishing sector
Housing Housing Housing
SAFEDLINK) to the backbone (FCnet/LAN) one green/red and one yellow LED module (MoNet) FCA2031-A1 –F
 N2007-A1: Multi-mode purpose it is necessary to install a Order no.: needed, for exam- – Fire brigade display panel (FAT) [DE] number of loops (e.g. from conventional sounder – 10 configurable monitored outputs
– Large: 430x796x260 mm (WxHxD) – Comfort: 430x796x160 mm (WxHxD) – Comfort: 430x796x160 mm
– Redundant transmission thanks to circular wiring System-wide view Order no.: S54400-A153-A1 transmission up to 4 km
network module. In case of additional S54400-A18-A1 ple, for operating –F  ire brigade display panel with 2 loops to 4 loops or from lines (primary lines; (actuators, alarm and peripheral devices)
– 150 W power supply – 150 W power supply Housing (WxHxD) requirements in terms of the degrade an event printer. It integrated fire brigade operating 4 loops to 8 loops) while 4x up to – 10 configurable monitored inputs
–R  edundant connection possible due to two with the fire terminal – Max. battery capacity: 2x26 Ah – Comfort: 430x796x160 mm (WxHxD) – 150 W power supply For installation in panels or additional housings, Order no.: S54400-A110-A1 mode function, 2 network modules can is plugged into the panel retaining a constant total 1 A, max. 2 A total). (monitoring of extinguishing devices)
– Max. battery capacity: 2x26 Ah
Ethernet switches FT2040-EZ use the following installation kits: be installed. PMI mainboard. (FAT and FBF) [DE & CZ] number of addresses on The sounder mod- – 6 driver outputs
Order no.: S54400-C3-A3 – 150 W power supply – Max. battery capacity: 2x26 Ah
– Increased EMC protection thanks to fiber-optic Order no.: A5Q00016100 For example for: The RS232 module – EVAC module [NL] the periphery board (e.g. 2 ule is screwed to – Connection for remote terminal
– Max. battery capacity: 2x26 Ah Order no.: A5Q00016854 – FHA2029-A1 for Eco, Standard, Comfort housings –N etworked panels with more than is not contained – UGA 20 [FR] loops with 126 addresses the assembly plate
cabling Order no.: S54400-B79-A1
Order no.: S54392-A7-A1
Order no.: A5Q00016852 512 FDnet devices in the set for the The RS485 module (isolated) is each or 4 loops with 63 ad- FHA2007-A1.
–E  asily programmable, EN 54-compliant system- –N etworked panel with connection to event printer. plugged into the PMI mainboard. dresses each).
Card cage (1 sector exting.)
wide control Ethernet switch – FHA2030-A1 for Large, Large Extension housings
remote transmission and with more
Order no.: FCA2046-A1
– Configurable view of each panel Backbone (FCnet/LAN) * (Figure analog to FC2040-AA)
(modular)
FN2012-A1
Order no.: S54400-B81-A1 than 512 FDnet devices
Order no.:
A5Q00005327
Order no.: A5Q00009923 Order no.: A5Q00010136 A5Q00014866 Consisting of:
– Card holder for one extinguishing card
–E  ach panel can be used as a router panel (please Order no.: A5Q00012851
Order no.: S54392-B8-A1
read separate documentation). FC2020 ✔ – ✔ ✔ ✔ ✔ ✔
In the basic version each FC2040
Key data control panel contains:
FC2030 ✔ – ✔ ✔ ✔ 1) ✔ –
– Max. number of panels in EN 54 system: 64 Alarm transmission Repeater (SAFEDLINK) FN2002-A1 FC2040 ✔ – ✔ ✔ ✔ ✔ ✔
– Max. number of panels in a cluster: 16 Fault transmission The repeater doubles the range between FC2060 ✔ – ✔ ✔ ✔ 1) ✔ –
Fire controls
– Max. number of networkable clusters: 14 Monitoring of 2 con­ventional 2 FCnet stations (from 1,000 m to 2,000 m). FC2080 – ✔ – – – ✔ ✔
– Number of panels placed directly on backbone: 4* sounder lines A separate power supply is needed. 1)
Only usable on periphery board
– Number of panels with system-wide view: 5* Order no.: S24236-B2502-A1
– Max. distance between clusters
Fiber optic multi mode (FN2012-A1 with License key Without S1 (FCA2033-A1) S2 (FCA2034-A1) S3 (FCA2035-A1) S4 (FCA2036-A1)
Ethernet module (MM) VN2002-A1): 4,000 m Cluster (FCnet/SAFEDLINK) license
Fiber optic single mode (FN2012-A1 with key Order no.: Order no.: Order no.: Order no.:
Ethernet module (SM) VN2003-A1): 40,000 m S54400-P154-A1 S54400-P155-A1 S54400-P156-A1 S54400-P157-A1
* more with appropriate system topology
The following guidelines must be considered Fire control panel Fire control panel Fire control panel Fire control panel Management platform from Siemens ✔ ✔ ✔ ✔ ✔
SintesoView, Sinteso Touch and
– To fulfill the EN 54 norm, only 1 Ethernet switch
is required to connect control panels with less FC2020 (2-loop) FC2030 (modular) FC2060 (modular) FC2080 (modular)** BACnet 3rd-party provider (supervision)
– ✔ ✔ ✔ ✔

than 512 fire detectors to the backbone. BACnet 3rd-party provider


– – ✔ ✔ ✔
Description Fire control panel FC2040 (4-loop) Description Description Description (supervision and basic commands)
BACnet 3rd-party provider
The FC2020 is a compact 2-loop fire control panel. The FC2030 is a modular fire control panel. The FC2060 is a modular fire control panel. The FC2080 is a modular fire control panel. – – – ✔ ✔
(supervision and extended commands)
Description Technical data
Cluster Fire control panel FC2020-AZ
consisting of:
It has the following features:
– 2 FDnet loops
It has the following features:
– 2 FDnet loops
It has the following features:
– 4 FDnet loops
It has the following features:
– Housing (19“ pedestal cabinet) BACnet 3rd-party provider
– – – – ✔
The FC2040 is a compact 4-loop fire control panel. FDnet detector lines (activation and deactivation commands)
(FCnet/SAFEDLINK) Operating unit
– Optional: event printer FTO2001
– Integrated inputs/outputs for peripherals
– Integrated operating unit
It has the following features:
– 4 FDnet loops
– Number of addresses: max. 504
– Number of loops/stubs: 4/8
– 2 slots for additional module bus cards
– Integrated inputs/outputs for peripherals
– 5 slots for additional module bus cards
– Integrated inputs/outputs for peripherals
– Processor unit (19“, FC2080) with
• CPU card Sinteso Mobile – – – ✔ ✔
– Optional: key switch KABA FTO2005 – Integrated power supply – Integrated operating unit – Integrated operating unit • Communication card
Via the powerful FCnet/SAFEDLINK, up to 32 panels – Integrated inputs/outputs for peripherals – Optional with loop extension: 8 loops/16 stubs
– Automatic configuration – Integrated power supply – Integrated power supply • SAFEDLINK modules
can be networked (fire control panels and fire Housing – Integrated operating unit Inputs and outputs
– Networkability via FCnet/SAFEDLINK – Automatic configuration – Automatic configuration • Optional: redundant 2nd CPU card
terminals). – Standard: 430x398x160 mm (WxHxD) – Integrated power supply – 1 relay output for RT alarm
Characteristics of networking via the system bus
– 70 W power supply
or Ethernet
– Automatic configuration – 1 relay output for RT fault
– Networkability via FCnet/SAFEDLINK or Ethernet –N  etworkability via FCnet/SAFEDLINK
or Ethernet
(hot pluggable)
• Slots for max. 7 module bus cards
Housings
– Max. battery capacity: 2x12 Ah – Networkability via FCnet/SAFEDLINK – 1 monitored alarm output
– Wiring with two-wire lines Technical data or Ethernet – 1 monitored fault output
Technical data – Power supply up to 450 W
Housing (Eco) FH2001-A1 Housing (Large extension)
– Redundant transmission thanks to circular wiring Order no.: A5Q00015550 Technical data – Optional operating unit
FDnet detector lines – 2 monitored sounder outputs (1 A each) FDnet detector lines –N  etworkability via FCnet/SAFEDLINK – Max. battery capacity: 2x7 Ah FH2004-A1
– Increased safety due to degrade mode using a
– Number of addresses: max. 252 – 12 configurable inputs/outputs 24 V – Number of addresses: max. 756 FDnet detector lines or Ethernet – 430x398x80 mm (WxHxD) Housing for larger batteries
second network module
– Number of loops/stubs: 2/4 – 1 Ethernet connection (RJ45) – Number of integrated loops/stubs: 2/4 – Number of addresses: max. 1,512 –O ptional: power supply kit (70 W) – Max. battery capacity: 2x65 Ah
– No additional cabling necessary for degrade
mode; even for systems with more than 512 fire – Optional with loop extension: – Optional: sounder module for splitting – Optional: extendable up to 12/24 loops/stubs – Number of integrated loops/stubs: 4/8 Technical data FP2003-A1 – 430x398x260 mm (WxHxD)
4 loops/8 stubs the sounder line output into 4 monitored – Optional: extendable up to 28/56 loops/stubs – Optional: event printer FTO2001-A1 – Optional: power supply kit (70 W)
detectors Fire control panel FC2020-EZ Inputs and outputs FDnet detector lines
outputs (2 A) –O ptional: 48 or 96 display groups each FP2003-A1 or
– Configurable view of individual panels Inputs and outputs – 1 relay output for RT alarm Inputs and outputs – Number of addresses: max. 5,000
consisting of: with one green/red and one yellow LED – Optional: power supply kit (150 W)
Key data – 1 relay output for RT alarm – 1 relay output for RT fault – 1 relay output for RT alarm –O ptional: extendable
Operating unit (overall) FP2004-A1 and additional power
– Max. number of panels in a cluster: 32 – 1 relay output for RT fault – 1 monitored alarm output – 1 relay output for RT fault up to 120/240 loops/stubs
– 24 display groups each with one green/ Order no.: A5Q00016865 supply (150 W) FP2005-A1
– Max. number of panels in a cluster – 1 monitored alarm output – 1 monitored fault output – 1 monitored alarm output
if connected to a management platform: 16
red and one yellow LED
– Optional: key switch KABA FTO2005
– 1 monitored fault output
– 1 monitored sounder output (1 A)
Fire control Fire terminal FT2040/FT2080 – 1 monitored sounder output (1 A)
– 8 configurable inputs/outputs 24 V
– 1 monitored fault output
– 2 monitored sounder outputs (1 A each)
Options
– Max. 6 additional card cages (5 slots) Housing (Standard) FH2002-A1
– Optional: event printer FTO2001-A1
– Optional: 48 or 96 display groups each
– Max. distance between panels with
copper cable
• without repeater: 1 km
Housing
– Standard: 430x398x160 mm (WxHxD)
– 8 configurable inputs/outputs 24 V
– 1 Ethernet connection (RJ45)
panel with Description Technical data
– 1 Ethernet connection (RJ45)
– Optional: sounder module for splitting the sounder
– 12 configurable inputs/outputs 24 V
– 1 Ethernet connection (RJ45)
–M ax. 37 slots for additional
module bus cards
– Max. battery capacity: 2x12 Ah
– 430x398x160 mm (WxHxD)
with one green/red and one yellow LED
(overall)
• Max. 30 FDnet line cards
• with repeater:
– Max. distance between panels with
2 km – 70 W power supply
– Max. battery capacity: 2x12 Ah
– Optional: sounder module for splitting the
sounder line output into 4 monitored outputs (2 A)
extinguishing The FT20xx has the following features:
– Integrated operating unit
– DC 24 V system power supply
– Alarm current: 130 mA
line output into 4 monitored outputs –O ptional: sounder module for splitting the
sounder line output into 4 monitored outputs
• Max. 30 collective line cards
–O ptional: power supply kit (70 W)
FP2003-A1 or
Order no.: A5Q00018778

• Max. 30 MS9i line cards


fiber-optic cable
• multi mode (FN2007-A1): 4 km
Order no.: A5Q00016827
control – Separate DC 24 V supply input possible
– Redundant DC 24 V supply input
• FT2040: 430 mA
• FT2080: 700 mA
• Max. 30 AnalogPLUS line cards
• Max. 30 interactive line cards
–O ptional: power supply kit (150 W)
FP2004-A1 and additional power
Housing (Large) FH2005-A1
Housing for larger batteries
supply (150 W) FP2005-A1 – Max. battery capacity: 2x65 Ah
• single mode (FN2006-A1): 40 km – Networkability via FCnet/SAFEDLINK • Max. 30 interactive Ex line cards – Optional: event printer FTO2001-A1 – 430x796x260 mm (WxHxD)
– Max. number of panels with or Ethernet • Max. 7 I/O cards for alarm and fault transmission –O ptional: 48 or 96 display groups each – Optional: power supply kit (70 W)
system-wide view: 5 • Max. 10 programmable I/O cards with one green/red and one yellow LED FP2003-A1 or
• Max. 7 I/O cards for monitored sounder lines (overall) – Optional: power supply kit (150 W)
• Max 16 extinguishing sectors (8 sectors per housing) FP2004-A1 and additional power
Order no.: A5Q00018931
FDnet Note: Picture shows FC2080 with optional fire terminal (touch) FT2080
and operating add-ons FCM2007-A1 and SCM2003-A2 built in. Housing (Comfort) FH2003-A1
supply (150 W) FP2005-A1
– Optional: event printer FTO2001-A1
– Max. battery capacity: 2x26 Ah – Optional: 48 or 96 display groups each
The FDnet (Field Device network) is a modern, with one green/red and one yellow LED
** for further details, please see front page – 430x796x160 mm (WxHxD)
multipurpose bus system. It allows rapid, fail-safe (overall)
–O ptional: power supply kit (70 W)
communication between the Sinteso™ bus elements
In the basic version In the basic version FP2003-A1 or Order no.: A5Q00019543
and the fire control panel. each FC2020 control Fire terminal FT2040-AZ Fire terminal (touch) FT2080-A1 each FC2060 control
–O ptional: power supply kit (150 W)
panel contains: panel contains:
Characteristics of networking via the detector FP2004-A1 and additional power 19" mounting kit FHA2016-A1
Alarm transmission consisting of: consisting of: Alarm transmission
bus
– Use of all cable types (with/without shielding)
Fault transmission
Fire controls
Operating unit Operating unit Fault transmission
Fire controls
FDnet supply (150 W) FP2005-A1
– Optional: event printer FTO2001-A1
Enables all fire control panels and
operator terminals to be mounted in a
– Integration of radial cable networks without Monitoring of 1 – Optional: event printer FTO2001 – 12“ color display Monitoring of 2
con­ventional sounder line con­ventional sounder lines –O ptional: 48 or 96 display groups each 19‘‘ frame; 430x100x324 mm (WxHxD)
modifications to cable network – Optional: key switch KABA FTO2005 – Resolution 1280x800 pixels
with one green/red and one yellow LED Order no.: A5Q00020179
– No shielding necessary Fire control panel FC2020/2040-AA Housing Order no.: S54400-C120-A1 (overall)
Fire control panel FC2020-AA Fire control panel FC2020-AE Fire control panel FC2030-AA Fire control panel FC2060-AA
– Turbo isolators for uninterrupted detection and with extinguishing control – Eco: 430x398x80 mm (WxHxD) Housing
consisting of: consisting of: consisting of: consisting of: Order no.: A5Q00009906
alarming consisting of: – Optional: 70 W power supply – Standard (FH2002-A1)* Floor repeater display Floor repeater terminal
– 2-wire loop Operating unit Operating unit – Max. battery capacity: 2x7 Ah – Desktop (FHA2040-A1)* Operating unit Operating unit FT2011 FT2010
Fire control panel
– Power supply to all bus elements via the FDnet – Optional: event printer FTO2001 – Optional: event printer FTO2001 – Optional: 48 or 96 display groups each – Back (FHA2039-A1)* – Optional: event printer FTO2001 – Optional: event printer FTO2001 Used for the display of mes- Used for the display and control
(except input/output module FDCIO221, zone – Optional: key switch KABA FTO2005 – Optional: key switch KABA FTO2005
– 2-loop panel FC2020-AA
Order no.: A5Q00016829
with one green/red and one yellow LED – Fire terminal board (FTI2001-A1)* –O ptional: key switch set KABA FTO2005 –O ptional: key switch set KABA sages from the monitored area. of messages from the monitored Power supply
module FDCI223, “transponder” FDCIO223, Operating add-on Operating add-on in Eco housing with 48 display groups Operating add-on FTO2005 area. Power supply kit (150 W)
– 4-loop panel FC2040-AA * must be ordered separately Order no.: A5Q00017706
extinguishing control unit XC10, aspirating smoke – Optional: 48 or 96 display groups – 48 display groups each with one green/ (FH2001-E1) or with 96 display groups –O
 ptional: 48 or 96 display groups, each with Operating add-on Power supply kit A (70 W) FP2004-A1
Order no.: A5Q00016100 Order no.: A5Q00014104
detectors FDA221/FDA241) each with one green/red and one red and one yellow LED (FH2001-G1) one green/red and one yellow LED (overall) –O
 ptional: 48 or 96 display groups, Shared properties FP120-Z1 Power supply for installation in empty housings.
Key data yellow LED (overall) – Optional: 96 display groups each with Extinguishing terminal (1 sector) Order no.: A5Q00016702 each with one green/red and one –B acklit display with plain text display The autonomous power supply converts the mains Optional: Additional power supply with FP2005-A1
Housing
– Up to 40 T-taps one green/red and one yellow LED XCM2002-A2 yellow LED (overall) (6 lines of 40 characters each) voltage to system voltage and charges the batteries. is possible.
Housing Optional Optional: – Comfort: 430x796x160 mm (WxHxD)
– Max. 252 bus elements per loop (overall) Order no.: S54392-B3-A1 –P ower supply and communication Order no.: S54400-S122-A1
– Comfort: 430x796x160 mm (WxHxD) remote panel Fire terminal FT2040-EZ – 150 W power supply Housing Order no.: A5Q00020825
– Cable lengths up to 3.3 km with up to 252 bus – 150 W power supply Housing Extinguishing control kit (1 sector) consisting of: – Max. battery capacity: 2x26 Ah – Large: 430x796x260 mm (WxHxD) (individually addressed) via FDnet,
elements XT2001-A2 additional 24 V supply possible Power supply kit (70 W)
– Max. battery capacity: 2x26 Ah – Comfort: 430x796x160 mm (WxHxD) XCA2005-A1 – 150 W power supply Additional power supply (150 W)
Order no.: Operating unit Order no.: S54400-C2-A1 – 282x207x79 mm (WxHxD)
– 150 W power supply – Extinguishing card XCI2005-A1 –O ptional: up to two 150 W additional FP2015-A1 FP2005-A1
Order no.: A5Q00016829 S54392-F2-A1 – 24 display groups each with one green/ – Max. 8 FT2010/FT2011 per FC2020
– Max. battery capacity: 2x26 Ah – Card cage (1 sector exting.) FCA2046-A1 power supplies (FP2005-A1) For the independent power supply Additional power supply can be connected
red and one yellow LED – Max. 16 FT2010/FT2011 per FC2040
– Accessory kit FCA2047-A1 – Max. battery capacity: 2x45 Ah of fire terminals such as FT2040. in the housing directly after FP2004-A1.
Detailed planning information Order no.: A5Q00016851
– Card cage connection FCA2006 Order no.: A5Q00016720 – Max. 50 FT2010/FT2011 per FC2060 Order no.: S54400-B121-A1
Order no.: A5Q00023048 Order no.: A5Q00018779
Detailed information for planning of the system are Order no.: S54392-S20-A1
available in the planning document, Doc. ID 008843.

Operating add-ons
Extinguishing terminal (1 sector) Extinguishing terminal (4 sectors) Operating add-on (2xLED incl.) Operating add-on (4xLED incl.) Key switch Kaba FTO2005-C1 Key switch Nordic FTO2006-B1 Event printer FTO2001-A1 Event printer DL3750+
Legend for the interfaces: XCM2002-A2 XCM2003-A2 FCM2038-A2 FCM2036-A2 Kaba lock cylinder with installation ac- Key set with mounting acces- The event printer FTO2001-A1 is installed directly in Monitored external event printer for serial
Serial interfaces  ne each optional RS232 and/or
O Consisting of: For FC2080 only. This contains 48 display groups each with one This contains 96 display groups cessories and keys Kaba 8 #100. Usable sories. Optionally applicable for the control panel or in the terminal. It is a thermal connection or via Ethernet.
RS485 interface (can also be freely combined) – 1 extinguishing terminal Consisting of: green/red and one yellow LED. Any events can be each with one green/red and one optionally for enabling operation. operation clearance. printer which logs all events. Optional: RS232 module (isolated) FCA2001-A1
per control panel or terminal – Configurable leds and push buttons – 4 extinguishing terminals allocated to the LEDs; 427x200x25 mm (WxHxD). yellow LED. Any events can be al- Order no.: A5Q00010113 Order no.: A5Q00010129 An RS232 module (isolated) FCA2001-A1 is required Order no.: A5Q00023962
Backbone (FCnet/LAN) Network to connect clusters – 4 digit display to show countdown – Configurable leds and push buttons Optional: event printer FTO2001-A1 located to the LEDs; 427x200x25 for operating the event printer. This is not contained
Cluster (FCnet/SAFEDLINK) Network to connect panels pre-warning time – 4 digit display to show countdown Order no.: S54400-B146-A1 mm (WxHxD). Extinguishing key switch Kaba Extinguishing key switch in the printer set and must be ordered separately.
FDnet Network to connect Sinteso devices Order no.: S54392-B3-A1 pre-warning time Order no.: S54400-B147-A1 XTO2002-C1 Nordic XTO2003-B1 Order no.: A5Q00010126 © Siemens 2013
Order no.: S54392-B4-A1 Order no.: S54392-B12-A1 Order no.: S54392-B11-A1 © Siemens 2019