Professional Documents
Culture Documents
Safety Manual
In Accordance with IEC 61508
1 Introduction ................................................................................................................................. 3
1.1 Terms and Abbreviations .......................................................................................................... 3
1.2 Acronyms .................................................................................................................................... 4
1.3 Product Support ......................................................................................................................... 4
1.4 Related Literature ...................................................................................................................... 4
1.5 Reference Standards ................................................................................................................ 5
2 Product Description ................................................................................................................... 5
2.1 Hardware Versions .................................................................................................................... 6
3 Designing a SIF Using a Manufacturer Product .................................................................... 6
3.1 Safety Function .......................................................................................................................... 6
3.2 Environmental Limits ................................................................................................................. 7
3.3 Application Limits & Restrictions ............................................................................................. 7
3.4 Design Verification ..................................................................................................................... 7
3.5 SIL Capability.............................................................................................................................. 7
3.5.1 Systematic Integrity ................................................................................................................... 7
3.5.2 Random Integrity ........................................................................................................................ 7
3.5.3 Safety Parameters ..................................................................................................................... 8
3.6 Connection of the Direct Acting Pneumatic Trip System to the SIS Logic-Solver ........... 8
3.7 General Requirements .............................................................................................................. 8
4 Installation and Commissioning ............................................................................................... 9
4.1 Installation ................................................................................................................................... 9
5.1 Proof Test without Automatic Testing ..................................................................................... 9
5.2 Repair and Replacement ........................................................................................................ 10
5.3 Useful Life ................................................................................................................................. 10
5.4 Manufacturer Notification ........................................................................................................ 11
Page 2 of 11
1 Introduction
This Safety Manual provides information necessary to design, install, verify and maintain
a Safety Instrumented Function (SIF) utilizing the Direct Acting Pneumatic Overspeed
Trip System for Elliott YR steam turbines. The Direct Acting Pneumatic Trip System has
the option of incorporating a Partial Stroke Actuation System.
This manual provides necessary user information and requirements for meeting the IEC
61508 and/or IEC 61511 functional safety standards.
A Failure Modes, Effects, and Diagnostics Analysis report for the Pneumatic Trip System
is available upon request. See Section 1.3 for Product Support information.
Page 3 of 11
1.2 Acronyms
EUC Equipment Under Control
FMEDA Failure Modes, Effects, and Diagnostic Analysis
HFT Hardware Fault Tolerance
MOC Management of Change - Specific procedures to follow for any
work activities in compliance with government regulatory
authorities or requirements of a standard.
MTTR Mean Time to Repair
PFDavg Average Probability of Failure on Demand
PFH Probability of Failure per Hour
PVST Partial Valve Stroke Testing
SFF Safe Failure Fraction - The fraction of the overall failure rate of
an element that results in either a safe fault or a diagnosed
dangerous fault.
SIF Safety Instrumented Function - A set of equipment intended to
reduce the risk due to a specific hazard (a safety loop).
SIL Safety Integrity Level - Discrete level (one out of a possible four)
for specifying the safety integrity requirements of the safety
functions to be allocated to the E/E/PE safety-related systems
where Safety Integrity Level 4 is the highest level and Safety
Integrity Level 1 is the lowest.
SIS Safety Instrumented System – Implementation of one or more
Safety Instrumented Functions. An SIS is composed of any
combination of sensor(s), logic solver(s), and final element(s).
Elliott Company
Industrial Products
901 North Fourth Street
Jeannette, PA 15644
724-527-2811
www.elliott-turbo.com
Page 4 of 11
Guidelines/References:
• Practical SIL Target Selection – Risk Analysis per the IEC 61511 Safety
Lifecycle, ISBN 978-1-934977-03-3, exida
• Control System Safety Evaluation and Reliability, 3rd Edition, ISBN 978-1-
934394-80-9, ISA
• Safety Instrumented Systems Verification, Practical Probabilistic Calculations,
ISBN 1-55617-909-9, ISA
2 Product Description
The Direct Acting Pneumatic Trip System is an overspeed trip system for steam turbines
with an integral trip valve. A single spring-loaded pneumatic cylinder acts directly on the
trip valve. The cylinder is pressurized to open the valve and depressurized to close the
valve. Two redundant and independently controlled solenoids control the actuation of the
pneumatic cylinder and are de-energized to trip. A quick release valve is used to
increase the speed of the cylinder discharge.
Two solenoid configurations are available:
1oo2 – The independently controlled solenoids are pneumatically configured to be in
series. Only one solenoid needs to de-energize for the system to trip and close the trip
valve.
2oo2 – The independently controlled solenoids are pneumatically configured to be in
parallel. Both solenoids need to de-energize for the system to trip and close the trip
valve.
The Partial Stroke Actuation operates independently by pressurizing the opposing side
of the pneumatic cylinder in a controlled manner to exercise the valve without tripping
the turbine. The Partial Stroke Actuation does not interfere with the overspeed trip
function. The Partial Stroke function can be activated by a local selector switch, or it can
be connected to a DCS for remote activation.
See Installation, Operation, and Maintenance Manual for additional setup and
configuration details.
Page 5 of 11
2.1 Hardware Versions
Page 6 of 11
3.2 Environmental Limits
The designer of a SIF must check that the product is rated for use within the expected
environmental limits. Refer to the Elliott Direct Acting Pneumatic Trip System Installation,
Operation, and Maintenance (IO&M) Manual for environmental limits.
The achieved Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
design must be verified by the designer via a calculation of PFDavg or PFH, considering
safety architecture, proof test interval, proof test effectiveness, average repair time and
the specific failure rates of all products included in the SIF. Each subsystem must be
checked to assure compliance with minimum hardware fault tolerance (HFT)
requirements. The exida exSILentia® tool is recommended for this purpose as it
contains accurate models for the Direct Acting Pneumatic Trip System and its failure
rates.
The failure rate data listed in the FMEDA report are only valid for the useful lifetime of
Direct Acting Pneumatic Trip System. The failure rates will increase sometime after this
time period. Reliability calculations based on the data listed in the FMEDA report for
mission times beyond the lifetime may yield results that are too optimistic, i.e., the
required Safety Integrity Level will not be achieved.
An appropriate MTTR shall be selected based on Elliott and/or plant operation and
maintenance procedures.
Page 7 of 11
The 2H approach involves assessment of the reliability data for the entire element
according to 7.4.4.3.3 of IEC 61508.
The failure rate data used for this analysis meets the exida criteria for Route 2H which is
more stringent than IEC 61508. Therefore, the Pneumatic Trip System meets the
hardware architectural constraints for up to SIL 2 @ HFT=0 (or SIL 3 @ HFT=1) when
the listed failure rates are used.
As an alternative to establishing architectural constraints via Route 1H or Route 2H, the
user of the Pneumatic Trip System may establish the architectural constraints for an
element using the Pneumatic Trip System per 11.4.5 of IEC 61511-1:2016. In which
case the architectural constraints are SIL 2 @ HFT=0 (or SIL 3 @ HFT=1).
The architectural constraint type for the Pneumatic Trip System is A. The hardware fault
tolerance of the device is 0. The SIS designer is responsible for meeting other
requirements of applicable standards for any given SIL.
3.6 Connection of the Direct Acting Pneumatic Trip System to the SIS Logic-Solver
The Direct Acting Pneumatic Trip System is to be used in conjunction with a Woodward
Protech GII overspeed trip control or equivalent, and the Woodward 1680-2030 or
equivalent Sensor.
The steam purity limits for both start-up and continuous operation of steam turbines are
defined in the following table, adapted from Table 9-2 of NEMA SM23-1991 with
Chlorine comment added:
CONTINUOUS STARTUP
CONDUCTIVITY -
O
MICROMHS/CM AT 25 C
DRUM 0.3 1.0
ONCE THROUGH 0.2 0.5
Notes:
1. TDS (total dissolved solids) 100 ppm, max.
2. Other contaminants should be advised by Purchaser and reviewed by Elliott on an
individual basis.
Page 9 of 11
The frequency of proof testing, or proof test interval, is to be determined in reliability
calculations for the safety instrumented functions for which the Direct Acting Pneumatic
Trip System is applied. The proof tests must be performed at least as frequently as
specified in the calculation in order to maintain the required safety integrity of the safety
instrumented function.
The following proof test is recommended. The results of the proof test should be
recorded, and any failures that are detected and that compromise functional safety
should be reported to Elliott.
The suggested Proof Test consists of a full stroke of the Pneumatic Trip System
Step Action
1 Disconnect driven load from turbine.
2 Send a signal to the Pneumatic Trip System to force the Actuator/Valve
assembly to the Fail-Safe state and confirm that the Safe State was achieved
(See Note 1).
3 Inspect the Direct Acting Pneumatic Trip System for any visible damage or
contamination.
4 Record any failures in your company’s SIF inspection database.
5 Close steam pressure isolation valve and allow steam pressure to bleed off.
6 Reconnect driven load and reset Pneumatic Trip Valve.
Note 1. For the test to be determined as effective, the turbine must reduce the speed to
500 RPM within 15 minutes.
This test will detect 95% without PVST and 93% with PVST of possible DU (Dangerous
Undetected) failures in the Direct Acting Pneumatic Trip System.
The person(s) performing the proof test of a Direct Acting Pneumatic Trip System should
be trained in SIS operations, including bypass procedures, valve maintenance and
company Management of Change procedures.
It is recommended that a physical inspection (Step 3 from Table 5) be performed on a
periodic basis with the time interval determined by plant conditions. A maximum
inspection interval of one year is recommended.
Page 10 of 11
5.4 Manufacturer Notification
Any failures that are detected and that compromise functional safety should be reported
to Elliott customer service.
Elliott Company
Industrial Products Division
901 North Fourth Street
Jeannette, PA 15644
724-527-2811
www.elliott-turbo.com
Page 11 of 11