Professional Documents
Culture Documents
5-2016 - Control Units Dalgakiran en Rev02 PDF
5-2016 - Control Units Dalgakiran en Rev02 PDF
OPERATING INSTRUCTIONS
EUROPEAN COMMUNITY CONFORMITY STATEMENT
Istanbul - TURKEY
Revision Status
Printed in Istanbul
R & D Department
ii
1. Indicators ....................................................................................................................................... 7
1.1 Logik 8 Control Panel ..................................................................................................................... 7
1.1.1 Home Screen Buttons ................................................................................................... 7
1.1.2 Starting the Compressor ............................................................................................... 7
1.1.3 Monitoring the Service Times........................................................................................ 8
1.1.4 Monitoring the Running Times ...................................................................................... 9
1.1.5 Parameters Used in the Compressor and Their Values ................................................ 9
1.1.6 Descriptions of the Codes Displayed on the Screen of the Compressor...................... 10
1.2 Logik 9 Control Panel ................................................................................................................... 12
1.2.1 Home Screen Buttons ................................................................................................. 13
1.2.2 Starting the Compressor ............................................................................................. 13
1.2.3 Operating the Device .................................................................................................. 14
1.2.3.1 Adjusting the User Parameters and Monitoring the Service Times ..................................... 15
1.2.4 Descriptions of the Codes Displayed on the Screen of the Compressor...................... 17
1.3 DEC 40 Control Panel ................................................................................................................... 20
1.3.1 Switching Between DEC 40 Screens .......................................................................... 21
1.3.2 DEC40 Screenshots ................................................................................................... 21
1.3.3 DEC 40 Operating Modes ........................................................................................... 23
1.3.3.1 Selection of Operating Mode................................................................................................ 23
1.3.3.2 Stop Method ......................................................................................................................... 23
1.3.3.3 Compressor Startup ............................................................................................................. 24
1.3.3.4 Deloading and Reloading of the Compressor ...................................................................... 24
1.3.3.5 Stop and Restart of the Compressor Depending on the Output Pressure........................... 24
1.3.4 Alarms and Warnings.................................................................................................. 24
1.3.5 Alarm History .............................................................................................................. 25
1.4 L25S Control Panel ....................................................................................................................... 26
1.4.1 Home Screen Buttons ................................................................................................. 26
1.4.2 Operating the Device .................................................................................................. 27
1.4.2.1 Adjusting the User Parameters and Monitoring the Service Times ..................................... 28
1.4.2.2 Information on Maintenance Times ...................................................................................... 29
1.4.2.3 Information on Running Times ............................................................................................. 31
1.4.2.4 Alarm Records...................................................................................................................... 32
1.4.2.5 Compressor Configuration Information ................................................................................ 33
1.4.2.6 Selecting the Current Temperature, Pressure Unit and Language...................................... 34
iii
1.4.2.7 Entering Parameter Password ............................................................................................. 35
1.4.2.8 Parameter Listing (User Level) ............................................................................................ 36
1.4.2.9 Warning, Alarm and Failure Screens ................................................................................... 39
1.4.2.10 Alarms That Stop The Compressor Immediately ................................................................. 40
1.5 L26S Control Panel ....................................................................................................................... 41
1.5.1 Home Screen Buttons ................................................................................................. 42
1.5.2 Operating the Device .................................................................................................. 44
1.5.2.1 Entering the Parameter Password ....................................................................................... 45
1.5.2.2 Adjusting the User Parameters and Monitoring the Service Times ..................................... 46
1.5.2.2.1 Information on running time ............................................................................................. 46
1.5.2.2.2 Information on Changing the Password .......................................................................... 47
1.5.2.2.3 Actual Temperature, Pressure Unit and Selection of the Language ...............................48
1.5.2.2.4 Compressor Number Selection ....................................................................................... 49
1.5.2.2.5 Pressure Parameters Selection ....................................................................................... 50
1.5.2.2.6 Timer Parameters Selection ............................................................................................ 51
1.5.2.2.7 Information on the Maintenance Times ........................................................................... 52
1.5.2.2.8 Information on the Maintenance Detected List ................................................................ 53
1.5.2.2.9 Information on the Alarm List........................................................................................... 54
1.5.2.2.10 Weekly Timer Selection ................................................................................................. 54
1.5.2.3 General Operation Displays, Warning and Alarm List ......................................................... 56
1.6 L30P Control Panel ....................................................................................................................... 58
1.6.1 Home Screen View ..................................................................................................... 59
1.6.2 Control Unit Info Screen .............................................................................................. 60
1.6.3 Alarms ........................................................................................................................ 65
1.6.3.1 Alarms that Stop the Compressor Immediately ................................................................... 65
1.6.3.2 Maintenance Messages ....................................................................................................... 66
1.6.3.3 Warning Alarms .................................................................................................................... 66
1.6.3.4 The Messages Seen in the Alarm List ................................................................................. 67
iv
Figure 1 Logik 8 Control Panel .......................................................................................................................... 7
Figure 2 Logik 9 Control Panel ........................................................................................................................ 12
Figure 3 DEC 40 Control Panel ....................................................................................................................... 20
Figure 4L25S Control Panel ............................................................................................................................. 26
Figure 5L26S Control Panel ............................................................................................................................. 41
Figure 6 L30P Control Panel ............................................................................................................................ 58
Figure 7 L30P Home Screen View ................................................................................................................... 59
v
Table 1 Logik 8 Control Panel ............................................................................................................................ 7
Table 2 Parameters Displayed in Logik 8 Screen .............................................................................................. 9
Table 3Alarm and Warning Codes ................................................................................................................... 10
Table 4 Logik 9 Control Panel ....................................................................................................................... 12
Table 5 Logic 9 Home Screen Buttons ............................................................................................................ 13
Table 6 Logik 9 User Menu ............................................................................................................................ 15
Table 7Alarm and Warning Codes ................................................................................................................... 17
Table 8 DEC40 Control Panel .......................................................................................................................... 20
Table 9 DEC40 Screenshots ........................................................................................................................... 21
Table 10 DEC40 Alarms .................................................................................................................................. 25
Table 11 L25S Control Panel ........................................................................................................................... 26
Table 12 Warning Alarms................................................................................................................................. 40
Table 13L26S Control Panel ............................................................................................................................ 41
Table 14 L26S Information Display Icon Descriptions ..................................................................................... 43
Table 15 General Operation Screens .............................................................................................................. 56
Table 16 Warning and Alarms List ................................................................................................................... 57
Table 17 L30P Control Panel ........................................................................................................................... 58
Table 18 L30P Home Screen Data .................................................................................................................. 59
Table 19 Main Sliding Menu Screen ................................................................................................................ 60
Table 20 L30P Compressor Setting Menu ....................................................................................................... 61
Table 21 L30P Pressure Settings .................................................................................................................... 62
Table 22 L30P Temperature Settings .............................................................................................................. 62
Table 23 L30P Start Timer Settings ................................................................................................................. 62
Table 24 Alarms that Stop the Compressor Immediately ................................................................................ 65
Table 25 Maintenance Messages .................................................................................................................... 66
Table 26 Warning Alarms................................................................................................................................. 66
Table 27 The Messages Seen in the Alarm List .............................................................................................. 67
vi
1. Indicators
Ref Description
1 Info screen
2 Warning LED
3 Start
4 Stop
5 Reset
6 Alarm
Reset : Displays and resets the running and maintenance hours, selects parameters, confirms changes,
displays operating temperature.
X10 LED : Reminds you to multiply the numeric value on the screen by 10.
X100 LED : Reminds you to multiply the numeric value on the screen by 100.
When you press button to start the compressor, the operating pressure is displayed on the
screen as .
If the pressure in the pressure line is equal to or higher than the set pressure of the compressor,
message blinks on the screen. The compressor keeps idling as long as p15 (idling time). At
the end of this period, message becomes steady and the compressor
stops. The pressure drops until the compressor stops. If the pressure drops below the set pressure the
compressor switches to load, p15 time is reset and the screen displays the operating pressure.
7
When you press button to stop the compressor, the screen displays message, the
compressor switches to idle first and after idling for 30 seconds, the compressor stops. During 30
seconds, message blinks, the compressor can be restarted by pressing button during
this period.
At the end of the period, "off" message becomes steady and the compressor stops. At this moment
x10 indicator starts blinking.
The compressor cannot be restarted for p17 (safety time). At the end of the period, x10 indicator
goes off and the compressor can be restarted.
When an alarm is emitted, the relevant alarm code is displayed on the screen.
The relevant buttons are located on the right hand side of the screen for convenience. When the screen is
displayed, press the buttons shown on the right hand side to proceed. Press the framed buttons
simultaneously. Press and hold the first one while pressing the other. Press the buttons
shown in the figure respectively
Once you press the buttons shown, compare the screen displayed with the screen shown in the manual to
make sure that you are proceeding correctly. Thus you can proceed step by step. Besides, the order of the
steps are shown on the left hand side of the screen. You can easily carry out the settings and checks shown
by following these steps.
You can display the service times by pressing button for a short time when the compressor is running
1 (Operating Pressure)
2 (Operating Temperature)
7 Check Time.
8
Since the screen can display only 3 digits, the values above 999 hours are displayed in combination with
"x10" or "x100" indicators. In other words; 1800 hours is displayed on the screen in combination with
and “x10” indicator. If the maintenance periods are elapsed, the values are displayed with - (minus).
(if x10 indicator is illuminated, the maintenance is 10 hours late.) If no buttons are pressed for 1
WHILE THE COMPRESSOR IS RUNNING, PRESS BUTTONS TO DISPLAY THE RUNNING HOURS
1 (OPERATING PRESSURE)
5 SOFTWARE VERSION
Pressure Check
0
(0 = Transmitter, 1 = Pressure Switch)
Pressure Transmitter Upper Limit 15 Bar
High Pressure Alarm 8,5 – 11 – 13,7 Bar
Stop Pressure 7,4 – 9,9 – 12,9 Bar
Operating Pressure 6,5 – 9.2 – 12,2 Bar
Pressure Transmitter Range 0
0
Air End Temperature Stop Value 130 C
0
Air End Temperature Alarm Value 108 C
0
Air End Temperature Pre-Alarm Value 103 C
0
Lowest Operating Temperature 0 C
0
Temperature Probe Offset 0 C
Star Running Time 5s
Star Delta Time 35 ms
Delay Before Switching to Loaded State 2s
9
1 min (T 3-20) / 2 min (T 20B-
Idling Time
30)
Variable Idling Time 0
Safety Time 30 s
Air Filter Replacement Time 3000 h
Oil Filter Replacement Time 3000 h
Separator Replacement Time 6000 h
Oil Replacement Time 6000 h
Compressor Check 3000 h
Max. Number of Motor Starts per Hour 20
LOW VOLTAGE ALARM 1
REMOTE START 0
PRESSURE UNIT 0 : Bar 1 : PSI
TEMPERATURE UNIT 0 : Centigrade 1 : Fahrenheit
RL5 SET VALUE 0
FAN OPERATING TEMPERATURE (RL5) 85-90-95 °C
FAN STOP TEMPERATURE DIFFERENCE (RL5) 5
Caution: service times (p18-p22) count down. When the set time is elapsed, - (minus) values are displayed on the screen. (-30 indicates
that the service time is 30 hours late)
NOTE: Before changing any parameter please contact your local service.
10
Pressure Transmitter / Pressure Switch Connection
Error
Emergency Stop Button Pressed
WARNINGS
Time for Air Filter Replacement
11
1.2 Logik 9 Control Panel
Ref Description
1 Fan is Running
2 Compressor is on Load
3 Remote Start/Stop
4 Alarm Detected
7 Master/Slave Operation
12
1.2.1 Home Screen Buttons
Table 5 Logic 9 Home Screen Buttons
When you energize the compressor, the message appears on the screen .
When the button is pressed to start the compressor, at the top of the screen the operating
on the screen .
If the pressure in the pressure line is below the compressor's set pressure value, the compressor
begins to run and in the meantime flashes . When the compressor switches to
13
When the compressor reaches the set pressure value, it switches to idle and will continue to run at
idle as long as the idle period. At the end of the period, message becomes stable and
the compressor stops. If the pressure drops below the compressor's set pressure value, the
compressor switches to load again, idle time is reset and the operating pressure is displayed on the
screen.
When the button is pressed to stop the compressor, the message appears on
the screen, the compressor is switched to idle at first and stops after running at idle for a set period.
During this time, the 'OFF' message and the operating pressure values are displayed intermittently
on the screen, the compressor can be reactivated by pressing the button again within this
period.
At the end of this period, the "OFF" message stable and the compressor stops.
When an alarm occurs, the relevant alarm code is displayed as on the screen .
see the screen, continue by pressing the buttons shown on the right side. Press the buttons
shown as in order.
To ensure that you proceed in the right order after you press the buttons shown, compare the displayed
screen with the screen shown in the book. Thus, you can proceed step by step. Also, to not to confuse the
order, the number of the step is written on the left side of the screen. You can easily make the settings and
controls shown by following these steps.
NOTE: Before changing any parameter please contact your local service.
14
1.2.3.1 Adjusting the User Parameters and Monitoring the Service Times
Operation Button to be
On Screen Display Description
No. Pressed
8
Total working hours
15
Operation Button to be
On Screen Display Description
No. Pressed
9
Load working hours
10
Time to change air filter
11
Time to change oil filter
12
Time to change separator filter
13
Time to change oil
14
Time to check compresör
16 Starts/hour
17
Software release
16
Operation Button to be
On Screen Display Description
No. Pressed
19
It returns to the working screen.
CODE MEANING
ALARMS
17
Emergency Stop Button is Pressed
Security
WARNINGS
18
Time to change oil filter
(the text flashes with the pressure value) The compressor is
about to stop (30 s expiration time is being waited)
19
1.3 DEC 40 Control Panel
20
1.3.1 Switching Between DEC 40 Screens
Normally, the upper screen displays the pressure sensor #1 (or the position of pressure switch #1). The
lower display shows the temperature sensor #1. Browse other screens using the MENU button. To
clarify the read values the reading parameter name and read value are shown in the upper and lower
indicators respectively. Some parameter strings are so long as not to fit in a single indicator. For such
values, when the MENU button is pressed, the parameter name is displayed, and the value is
displayed in both screens when the button is released.
When an alarm is emitted, the alarm code is displayed on the upper screen.
Network frequency Operation
L1-L2 phase-phase voltage Operation
L2-L3 phase-phase voltage Operation
L3-L1 phase-phase voltage Operation
Motor hours remaining to Maintenance A Operation / Program / Alarm
Motor hours remaining to Maintenance B Operation / Program / Alarm
Motor hours remaining to Maintenance C Operation / Program / Alarm
Motor hours remaining to Maintenance D Operation / Program / Alarm
Working hours remaining to Maintenance E Operation / Program / Alarm
Total Working Hours Operation
Working hours at total load (LOAD output active) Operation
Working in load / total working hour percentage Operation
21
Motor PTC value or switch position Operation
Differential pressure value Operation
Number of remaining starts in last 1 hour Operation
Equipment software version Operation
Switch in OFF position Operation
Switch in ON position Operation
Remote stop position (input function) Operation
Remote start position (input function) Operation
Alarm code 01 Operation
Alarm code 99 Operation
Alarm History, 9.Alarms Operation
Program parameter 99 Program
Enter user password Program
Select parameter Program
NOTE: Before changing any parameter please contact your local service.
22
1.3.3 DEC 40 Operating Modes
( word is displayed on screen for 5 sec) or by pressing the RUN button. If the Safety Time is not
yet over, the RUN led flashes till the time is over. When the time is over, and the output pressure is less than
the start pressure limit, the compressor starts up.
In case of an alarm condition, the compressor immediately stops with the alarm code being
displayed on the upper display. Complete list of the alarm codes is provided in 3.6.2.4.
The compressor is normally stopped by the REMOTE STOP signal ( word is displayed on
the operation mode by pressing the RUN button once again. If the STOP button is pressed once
again in the no load mode, the compressor stops immediately. The STOP led flashes till the compressor
completely stops.
If the compressor already operates in no load condition, and the STOP button is pressed, it
goes on operating till the idle working time finishes. It is possible to immediately stop the
23
1.3.3.3 Compressor Startup
If the mains voltage and frequency fall within the preset limits, and the mains phase order is correct, the
POWER Led lights up. The compressor can operate only when the POWER led is illuminated. Otherwise, it
never starts up.
If it is activated by pressing the RUN button, it is set in the Operating Position by giving a remote
START/STOP command. At this step, the unit decides to activate the compressor when the output pressure
drops below the Start Pressure Limit (or when pressure turns the switch off).
Before commissioning the compressor, the STAR relay output is activated. At the end of the Relay Switching
Time, the MAIN relay opens, whereupon the motor is switched on in the STAR switching position.
At the end of the Star Time, the STAR relay releases, and at the end of the Star/Delta Delay Time, the
DELTA relay draws.
At the end of the Load Delay Time, the LOAD relay is released for the compressor to start producing the
compressed air.
1.3.3.5 Stop and Restart of the Compressor Depending on the Output Pressure
If the output pressure remains over the Start Pressure Limit for the Idle Operating Time (or the pressure
switch remains open), the DELTA relay releases first. At the end the Relay Switching Time, the MAIN relay
releases. In this case, the RUN led starts flashing. Set the number of max. compressor starts in 1 hour using
the Hourly Max. Start parameter. If it reaches the maximum possible number of starts, the compressor is
prevented to stop till the time for 1 hour is over, so that the motor goes on working in idle position with no
load.
The alarms are however considered to the highest level failures, resulting in an immediate stop of the motor,
release of the alarm relay (if activated), and emitting the visual warning message. When an error occurs, the
error code is displayed on the upper display, and the related error category LED lights up.
The alarms and warnings are deleted by pushing the MENU button Emergency Stop alarms cannot be
cleared using the push buttons, the signal at the input must be removed.
The service warnings may disallow the motor operation depending on how long the service time
is exceeded.
24
Table 10 DEC40 Alarms
25
1.4 L25S Control Panel
Ref Description
1 Info screen
Alarm / Warning
2
LED
3 Start
4 Stop
5 Enter
6 Down
7 Up
Up: Increases the parameter value and moves upwards in the parameters.
Down: Decreases the parameter value and moves downwards in the parameters.
26
Enter: Selects the value displayed on the screen, confirms the changes and resets the failures displayed on
the screen.
The order of the steps is indicated by bold numbers next to the screen shot in order to avoid mistakes. You
can carry out settings and checks on the device by following the numbers.
press the framed buttons simultaneously. Press and hold the first one while pressing the next one.
27
1.4.2.1 Adjusting the User Parameters and Monitoring the Service Times
Button to
Actio
Screen Shot be Description
n No.
Pressed
28
Button to
Actio
Screen Shot be Description
n No.
Pressed
Button to
Actio
Screen Shot be Description
n No.
Pressed
29
Button to
Actio
Screen Shot be Description
n No.
Pressed
30
1.4.2.3 Information on Running Times
Button to
Actio
Screen Shot be Description
n No.
Pressed
6 Flow rate
31
Button to
Actio
Screen Shot be Description
n No.
Pressed
Button to
Actio
Screen Shot be Description
n No.
Pressed
The last 20 alarms issued by the
compressor are displayed in
descending order starting with the
1
latest alarm. So it is possible to
detect the most frequent failure
easily.
32
1.4.2.5 Compressor Configuration Information
Button to
Actio
Screen Shot be Description
n No.
Pressed
33
1.4.2.6 Selecting the Current Temperature, Pressure Unit and Language
Button to
Actio
Screen Shot be Description
n No.
Pressed
34
Button to
Actio
Screen Shot be Description
n No.
Pressed
The desired language can be
selected by either of the two
buttons. (Italian, English, French,
7
German, Spanish, Portuguese,
Turkish and Russian are
available.)
Actio Button to
Screen Shot Description
n No. be Pressed
35
Actio Button to
Screen Shot Description
n No. be Pressed
NOTE: Press the button any time for five (5) seconds to display the home screen again. If no
buttons are pressed within two (2) minutes, the home screen is displayed automatically.
36
Total Hours: Total running time of the compressor.
Loaded Running Percentage: Rate of the loaded time to the total time.
NOTE: Before changing any parameter please contact your local service.
Serial Number
The serial number of the compressor is recorded here for easy monitoring.
37
The automatic start and stop settings of the compressor are made here. When the button is pressed, OFF-
ON starts blinking. You can make a selection with the Up and Down buttons.
When you press the button when OFF is blinking, the start and stop of the compressor are
made with the button and Clock Timer menu is displayed.
When you press the button when ON is blinking, the start and stop of the compressor are made with
the timer and DAY1 text is displayed. On this screen, 1 stands for Monday and 7 stands for Sunday.
You can select the desired day with the up and down buttons and confirm with the button.
When ON is blinking; you can set the time (hour and minute) when the compressor will start running with the
up and down buttons and, confirm with button. When OFF is blinking; you can set the time when the
compressor will stop in the same manner. (3 ON/OFF values can be entered for each day) once the last
OFF value for the same day is entered, the screen displays “GUN NO. #”. 7 days of the week are set in the
same manner. If you want to copy the settings of the previous day, press and buttons respectively
after the settings are made. If you want to change the settings for a confirmed day press and
buttons respectively. Once the OFF (7th day) value of the last day is entered, the screen displays “DLS
TIME: NO- YES” text. (YES is pre-selected.)
YES: Summer time, it changes on the last Sunday of March and October according to the official time.
• If the 3rd OFF time in the day is later than 23:59, the time value moves to the next day and "DAY1"
text becomes "DAY1-2".
• If the set "OFF" time is the same as the "ON" time before it, this command will not be performed.
EXAMPLE:
38
If the compressor is stopped by the timer, you can press and hold start button for 3 seconds to restart the
compressor.
Compressor Idling.
39
1.4.2.10 Alarms That Stop The Compressor Immediately
Table 12 Warning Alarms
Alarm Code Screen Shot Description
Alarms That Stop The Compressor Immediately
AL01 EMERGENCY STOP Emergency Stop Button Pressed.
AL02 MOTOR OVERLOAD The Main Motor Thermal Switch Stopped The Compressor.
AL03 FAN OVERLOAD The Fan Motor Thermal Switch Stopped The Compressor.
AL04 NO PHASE Power Cut.
Phases Connected Reversely, Replace Two Phases From The
AL05 WRONG PHASE Input Clamp.
AL07 POWER CUT Digital Input control voltage cut.
AL11 HIGH PRESSURE Compressor Exceeded Set Pressure, Contact Service.
AL12 TEMP. PROBE FAILURE Temperature Sensor Failure.
Compressor Stopped Due To High Temperature, Contact
AL13 AIR END HIGH TEMPERATURE Service.
AL14 AIR END LOW TEMPERATURE Airend Temperature Too Low.
AL18 NO POWER Power Cut and Compressor Stopped. Restart Manually.
AL19 CONTROL UNIT Control Unit May Be Out Of Service, Contact Service.
AL20 MOTOR HIGH TEMPERATURE The Main Motor Body Temperature High (PTC On).
AL21 SAFETY PRESSURE SWITCH Internal Pressure High.
AL22 IN7 ON Input 7 On.
AL25 SEPARATOR Internal pressure high. The separator filter might be very dirty.
AL33 RS232 FAILURE Check the connections.
AL44 HIGH BEARING TEMPERATURE Bearing temperature high. Call the authorized service station.
Alarms That Stop The Compressor After 30 Seconds of Idling
AL26 PRESS. SENS. FAILURE Pressure Transmitter Failure
AL28 LOW VOLTAGE Check Power Source.
AL29 SAFETY Service Time During Safety Mode Exceeded.
AL30 CAUTION HIGH TEMPERATURE The Compressor Is About To Stop Due To High Temperature.
Warning Alarms
AL35 SET VALUE ERROR Factory Defaults Restored.
AL36 AIR FILTER Vacuum Switch Off, Check Air Filter.
AL39 LOW VOLTAGE Check Power Source.
AL40 HIGH VOLTAGE Check Power Source.
De-energize and Check Again, If the Failure Persists, Contact
AL41 TIMER FAILURE
Service
AL42 RS232 / COMM. FAILURE Check the connections.
AL47 MAX START/HOUR Maximum Number of Starts per Hour Achieved.
Messages on Maintenance
AL50 AIR FILTER REPLACEMENT Time for Air Filter Replacement.
AL51 OIL FILTER REPLACEMENT Time for Oil Filter Replacement.
AL52 SEP. FILTER REPLACEMENT Time for Separator Filter Replacement.
AL53 OIL REPLACEMENT Time for Oil Replacement.
AL54 COMPRESSOR CHECK Time For Compressor Check.
AL55 BEARING GREASING Time for Greasing the Bearings.
40
1.5 L26S Control Panel
Ref. Description
Information
1
display
Alarm/Warning
2
LED
3 Start
4 Stop
5 Down
6 Up
7 Enter
8 Reset
41
1.5.1 Home Screen Buttons
Start: Allows you to start the compressor.
Up: Allows you to increase your parameter value and move upwards within the parameters.
Down: Allows you to decrease your parameter value and move downwards within the parameters.
Enter: Allows you to choose the value shown on the screen and confirm the changes.
Reset: Allows you to reset the faults shown on the screen and return to the previous menu screen.
Information Display:
1) General icons:
• Discharge operation
• Multiunit operation
• Master\Slave operation
• Maintenance messages
2) Alarm or maintenance messages
3) Start\stop weekly timer
4) Actual Time
5) Fan is running
6) Temperature value
7) Driver information area
8) Compressor status:
9) Pressure zone:
• Working pressure and stop\start pressure
• Auxiliary pressure transducer value (if enabled)
• Motor is running
• Load solenoid valve open
42
Description of the Information Display icons:
Ref Meaning
Discharge is active
Maintenance time
Alarm
Compressor is OFF
Compressor is running
Stopped by the Weekly Timer. It continues to stay on the screen until the next
scheduled start.
Fan is running
43
PID and output 4/20mA enabled
Stop pressure
Start pressure
Motor is running
Unit of measure.
Contrast
Language selection
The order of the steps is indicated by bold numbers next to the screen shot in order to avoid mistakes. You
can carry out settings and checks on the device by following the numbers.
NOTE: Before changing any parameter please contact your local service.
44
1.5.2.1 Entering the Parameter Password
Oper
Button to
ation On Screen Display Description
be Pressed
No.
NOTE: When you are at any point of the menu, press the button for five (5) seconds to return to the
main screen. If no button is pressed within two (2) minutes, it returns to the main screen again.
45
1.5.2.2 Adjusting the User Parameters and Monitoring the Service Times
Oper
Button to be
ation On Screen Display Description
Pressed
No.
Working Hrs,
Starts /hour,
F.A.D.,
46
1.5.2.2.2 Information on Changing the Password
Oper Button to
ation On Screen Display be Description
No. Pressed
47
1.5.2.2.3 Actual Temperature, Pressure Unit and Selection of the Language
Oper Button to
ation On Screen Display be Description
No. Pressed
48
The time period, the date and
time settings of which is required
to be changed is selected with
the enter button and set by the up
5 and down arrow buttons and the
next setting is switched to by
pressing the enter button.
Oper Button to
ation On Screen Display be Description
No. Pressed
49
1.5.2.2.5 Pressure Parameters Selection
Opera Button to
tion On Screen Display be Description
No. Pressed
50
1.5.2.2.6 Timer Parameters Selection
Oper Button to
ation On Screen Display be Description
No. Pressed
51
1.5.2.2.7 Information on the Maintenance Times
Oper Button
ation On Screen Display to be Description
No. Pressed
52
1.5.2.2.8 Information on the Maintenance Detected List
Oper Button to
ation On Screen Display be Description
No. Pressed
53
1.5.2.2.9 Information on the Alarm List
Oper Button to
ation On Screen Display be Description
No. Pressed
The weekly timer operations are made from the menu No. 13 "Timer On/Off".
It is entered by navigating on the menu No. 13 and by the enter key. The T01 "Weekly.Timer.Activation"
parameter is selected by the enter key and the (factory setting "NO") is made "YES". After this parameter is
set to "YES", T02 "Weekly Timer" appears on the screen. It is entered by navigating on the T02 parameter
and by the enter key.
Automatic start and stop time settings of the compressor are made here. "Mon" day option starts flashing.
With the help of the up and down arrow buttons, the required day is selected and confirmed by pressing the
enter key.
54
There are 3 (T1, T2, T3) time intervals adjustable separately for each day. While the ON time of the T1
interval flashes after the day selection: the time value when the compressor will start to run can be adjusted
with the help of the up and down buttons (in hour and minute) and confirmed by pressing the enter key.
Then while OFF time flashes; the time value when the compressor will stop is adjusted in the same way.
It can be set in the same way for the 7 days of the week.
• If the T3/OFF hour within the day is after 23:59, the time value moves to the next day and the next
day appears next to the T3/OFF hour.
• If the set "OFF" time and the "ON" time before it are the same, this application does not take place.
EXAMPLE:
ON OFF
T1 07:30 12:30
T2 13:30 17:30
T3 18:30 23:30
ON OFF
T1 07:30 12:30
T2 13:30 17:30
T3 17:30 17:30
ON OFF
T1 07:30 17:30
T2 17:30 17:30
T3 17:30 17:30
When the compressor is stopped by the timer, if the start button is pressed for 3 seconds the compressor will
start running again.
55
1.5.2.3 General Operation Displays, Warning and Alarm List
Table 15 General Operation Screens
56
If you see a fault message on the screen, please resolve it by learning the fault condition at the first place.
Then, to be able to restart the compressor remove the fault from the screen with the RESET button.
57
Messages Related with the Maintenance
AL50 Change Air Filter Air Filter Replacing Time is Reached
AL51 Change Oil Filter Oil Filter Replacing Time is Reached
AL52 Change Sep. Filter Separator Filter Replacing Time is Reached
AL53 Change Oil Oil Change Time is Reached
AL54 Check Compress. Compressor Control Time is Reached
AL55 Check Bearings Bearing Lubrication Time is Reached
Ref Description
1 Alarm
4 Start
5 Stop
6 Reset
7 Function buttons
58
1.6.1 Home Screen View
Ref Description
Compressor running (if it is blinking, the compressor will either stop or start; if it
1
is invisible the compressor has stopped.)
2 Compressor under load
3 Operating pressure
4 Pressure unit (bar/PSI)
5 Stop pressure
5.1 Operating pressure
6 Set Pressure
8 Fan Running
9 Air End temperature
0 0
10 Temperature unit ( C / F)
14 Remote control and multiple runs
15 Wireless connection
16 Info screen for inverter
17 Pressure levels starting the compressor
18 M/S running
In case of alarm, the inverter info screen displays the alarm. Besides, the alarm indicator on the left
hand side of the LCD is illuminated.
59
NOTE: Changing the Start-Stop Set Pressure: Pressing F1 (SEL) button takes you to the menu and F2
button lets you select the values to be changed. F1 and F2 buttons are used for setting the desired value
and F3 button confirms the setting. F4 button returns to the home screen.
• Main Menu
Logik 30-P control unit has 3 levels of security. (Level 1, Level 2, Level 3)
The changes that can be made are limited according to the level of your password.
Ref Description
1 Password
2 Screen settings
3 Compressor settings
4 Compressor information
5 Pressure
6 Temperature
8 Start timer
9 Maintenance hours
10 Running hours
11 Alarms
12 Reset
13 Weekly time setting
14 Driver
60
• Password
• Screen Settings
• Compressor Settings
This menu allows you to make the basic settings for the compressor.
COMPRESSOR SETTINGS
Settin Pass
Parameter Description Content Value
g word
S01 *Restart Aut = Automatic / Man = Manual Auto/Man Man 1-2-3
YES=Phase control active
S04 Phase Control YES/NO YES 1-2-3
NO=Phase control inactive
YES=Low voltage alarm and warning active
S06 Low Voltage NO=Low voltage alarm and warning YES/NO YES 1-2-3
inactive
* Manual: The compressor doesn't start automatically after shutdown due to power cut and the LCD screen displays "POWER OFF".
Automatic: The compressor waits for the waiting period (Wt5) before restarting after shutdown due to power cut and the LCD screen displays "WAITING".
Once this period has been elapsed, the compressor starts automatically.
The changed set data is saved in the alarm ram and it is cancelled in case of a reset operation.
NOTE: Before changing any parameter please contact your local service.
61
• Pressure
This menu allows you to set the pressure parameters. You can enter the menu by pressing F3 button and
select the parameters depending on the password levels. F1 and F2 buttons are used for selecting the
desired parameter and F3 button confirms the setting. Once the selected parameter is set with F1 and F2
buttons, you can confirm with F3 button.
PRESSURE
Settin Pass
Parameter Description Content Value
g word
WP3 P. Stop Stop pressure Auto/Man 10 bar 3
WPS Set pressure Set value for operating pressure YES/NO 9,0 bar 3
WP4 P. Start Start pressure YES/NO 8.5 bar 3
• Temperature
This menu allows you to set the temperature parameters. You can enter the menu by pressing F3 button and
select the parameters depending on the password levels. F1 and F2 buttons are used for selecting the
desired parameter and F3 button confirms the setting. Once the selected parameter is set with F1 and F2
buttons, you can confirm with F3 button.
TEMPERATURE
Settin Pass
Parameter Description Content Value
g word
0
WT5 Low Temperature Low Air End temperature -10 ÷ +15 0 C 1-2-3
• Start Timer
This menu allows you to set the parameters for start timer.
WORKING HOURS
62
• Maintenance
This menu has two sub-menus. If the menu selected with F1 and F2 is confirmed with F3, the menus below
are displayed:
Maintenance Timer
This menu allows you to set the maintenance hours.
F1 button selects and F3 button confirms. The
examples below show how the SET and RESET
operations for the air filter are performed.
63
Maintenance Listing
• Running Hours
• Alarms
64
1.6.3 Alarms
8 High Pressure The Compressor exceeded the set high pressure value (WP2)
11 Low Temperature Screw temperature has dropped below the set value (WT5)
12 Power Off Power was cut off and the compressor stopped
13 RS 232 Nr.1 Failure Check the connections for the control panel
Supply voltage of the controller dropped below 9V AC, if it is above
14 Low Voltage
10,5V, the error is reset
15 RS 232 no. 1 Failure Check the connections for the Modbus
65
1.6.3.2 Maintenance Messages
Table 25 Maintenance Messages
66
CODE REMARK CAUSES
Auxiliary Temperature Probe If the temperature probe is set to measure the temperature
79
Failure difference (S09 = 2 or 3) is seen.
67