english 3
Type 3280, 3285
Quickstart
4 english
Type 3280, 3285
Authorized use
english 5
Type 3280, 3285
General information
6 english
Type 3280, 3285
Product description
english 7
Type 3280, 3285
Product description
8 english
Type 3280, 3285
Technical data
6 Technical data
Z1 6.1 Conformity
Valve
CMD Xd1 CTRL The motor valve Type 3280 and 3285 is compliant with EU direc-
POS opening
+ -
tives as stated in the EU Declaration of Conformity (if applicable).
Position Position Electromotive Continuous 6.2 Standards
set-point value controller actuator valve
The applied standards, which are used to demonstrate compliance
with the EU Directives, are listed in the EU type test certificate and/
POS
or the EU Declaration of Conformity (if applicable).
Position measuring system Position 6.3 Operating conditions
control circuit
Z2 Warning!
Valve Process
SP Xd2 CMD Position
opening variable Risk of injury due to malfunction if device used outdoors.
+ - control
circuit
▶▶ Do not use the device outdoors and avoid heat sources which
Process set- Process Process may cause the permitted temperature range to be exceeded.
point value controller
▶▶ Protect the device from direct sunlight and humidity.
PV Ambient temperature - 10...+60 °C (observe derating curve,
see chapter “6.5.1”)
Transmitter -10...+50 °C Type 3280, Seat
diameter 8...10, positioner and
Fig. 4: Signal flow diagram process controller process controller restricted
In the case of the running process controller, the process control Medium temperature 0...+70 °C
must be put into operation by the Communicator; otherwise the
Medium temperature for
control will not function.
oxygen 0...+60 °C
The operating instructions for the Bürkert-Communicator Permitted air humidity < 95 %, non-condensing
can be found at www.burkert.com
english 9
Type 3280, 3285
Technical data
3) The KVs value is a flow rate value for water, measurement at +20 °C and
10 english
Type 3280, 3285
Technical data
english 11
Type 3280, 3285
Technical data
12 english
Type 3280, 3285
Technical data
4) Analog version: 3.3 V signal voltage, reliable communication is reduced as the line length and transmission rate increase.
english 13
Type 3280, 3285
Technical data
100
100
90
90
80
Normal operation
Duty cycle [%]
80
70 Normal operation
Low power function
14 english
Type 3280, 3285
Technical data
70
Low power function Electronic valve
60
version Body material
50
Type
40
3280 X DN25 EPDM MS Port connection,
30
D-74653 Ingelfingen
20 NPT 1/4 PN 6 bar Nominal pressure
10
24 V DC 8 W Voltage,
Tamb see manual
5 10 15 20 25 30 35 40 45 50 55 60 65 268611 SN000000
Max. power
Max. ambient temperature [°C] W3ZLT consumption
Fig. 8: Derating curve for Type 3285 Seat diameter 8...25 Positioner Order number,
and process controller and Type 3280 Seat diameter 8...10 Serial number
Positioner and process controller (only up to 50 °C) Ambient temperature
english 15
Type 3280, 3285
Installation
7 Installation →→ Observe flow direction. The arrow on the body indicates the
direction of flow.
Warning! Type 3280: Flow direction below seat, is always closed
against the medium flow;
Risk of injury from improper installation. Type 3285: Flow direction above seat, is always closed with
▶▶ Installation may be carried out only by trained technicians the medium flow.
and with the appropriate tools!
▶▶ Secure system against unintentional activation.
▶▶ Following installation, ensure a controlled or defined restart.
16 english
Type 3280, 3285
Installation
▶▶ Observe applicable accident prevention and safety regula- Socket Circular connector
tions for electrical equipment. M12, 5-pole M12, 8-pole
None of the electrical inputs and outputs of the device Fig. 12: Designation of the circular connector, analog version
are galvanically isolated from the supply voltage.
4 1 4 1
Note!
5 5
Damage to the motor valve due to incorrect supply voltage.
3
•• The supply voltage must correspond with the voltage indi- 2 3 2
→→ Connect the motor valve according to the table. Fig. 13: Designation of the circular connector, digital version
When the supply voltage is applied, the motor valve is ready
for operation.
english 17
Type 3280, 3285
Installation
7.2.1 Pin assignment for on-off 7 Digital output 0...5 V (log. 0), 10...30 V (log. 1), not gal-
Pin Configuration External circuit vanically isolated
18 english
Type 3280, 3285
Installation
english 19
Type 3280, 3285
Installation
20 english
Type 3280, 3285
Installation
2 OFF no function Set-point value no function The detailed description and procedure for inserting the
input 4...20 mA SIM card can be found in operating instruction.
ON no function Set-point value no function
input 0...10 V
7.5 LED display
3 OFF Valve actuating speed: normal büS With the aid of the positioner and process controller version, it is
mode possible to use the Bürkert Communicator Software to toggle the
ON Valve actuating speed: slow mode CANopen LED colors between standard and NAMUR NE 107.
4 OFF Low power function: off no function 7.5.1 Display elements standard
ON Low power function: on, lower no function
force, less heat generation in the LED color Status Display
valve white continuously on Normal operation
yellow continuously on Valve completely open
The change in function does not become effective until the
supply voltage is applied again. A more precise description flashing, color Out of specification: Ambient
of the functions can be found in operating instructions. alternates with conditions or process condi-
the colors tions for the device are outside
7.4 Accepting and saving SIM card data of the valve the specified area. Internal
position device diagnostics point to
(digital version only)
problems in the device or the
The optionally available SIM card can be used to save and transfer process properties
device-specific values and user settings to a different device.
green continuously on Valve closed
Note!
red flashing, color Error, see chapter “9.3
Do not use any commercially available SIM cards for the alternates with Troubleshooting”
device. the colors
The inserted SIM card is a special industrial version which is of the valve
particularly durable and temperature-resistant. Order the SIM position
card via your Bürkert sales department only.
english 21
Type 3280, 3285
Installation
white, flashing Is used to identify a device 7.5.2 Display elements NAMUR NE 107
green or in the büS network. The LED Color Status Display
red „flashing“ status is started in color code
the Bürkert Communicator
green 1 continuously Diagnostics active: Device is
Software when selecting the
on operating faultlessly
device
red 5 continuously Failure, error or fault
orange flashing, color Function check: Work is being on
alternates with carried out on the device; con-
the colors trolled operation is therefore green 1 or 5 flashing Is used to identify a device in
of the valve temporarily not possible or red the büS network. The „flashing“
position status is started in the Bürkert
Communicator Software when
no color or - Valve without power supply selecting the device
LED off
orange 4 continuously Function check: The device is
on being worked on; controlled
operation is therefore tempo-
rarily not possible
yellow 3 continuously Outside the specification: The
on ambient conditions or process
conditions for the device are
outside the specified area.
Device internal diagnostics
point to problems in the device
or with the process properties
no - - Valve without power supply
color
or LED
off
22 english
Type 3280, 3285
Start-up
8 Start-up 9 Maintenance,
troubleshooting
Warning!
Warning!
Danger due to improper operation.
Improper operation may result in injuries as well as damage to Risk of injury from improper maintenance work.
the device and the area around it. ▶▶ Maintenance may be carried out only by trained technicians
▶▶ The operating personnel must know and have understood and with the appropriate tools.
the contents of the operating instructions. ▶▶ Secure system against unintentional activation.
▶▶ Observe the safety instructions and intended use. ▶▶ Following maintenance, ensure a controlled restart.
▶▶ Only adequately trained personnel may operate the device.
9.1 Maintenance
Before start-up, carry out fluid and electrical installation The motor valve Type 3280 and 3285 is maintenance-free under
of the valve. normal conditions.
9.2 Cleaning
8.1 Functions Use the normal cleaning agents to clean the Type 3280 and 3285.
Motor valve Type 3280 and 3285 has different functions which Use no alkaline cleansing agents, as these have a damaging effect
can be configured and parametrized via the DIP switches and on the materials used.
communications software.
9.3 Troubleshooting
A more precise description of the functions can be found In malfunctions occur, check:
in operating instructions under: www.burkert.com •• the port connectors,
•• whether the operating pressure is within the permitted range,
•• the power supply and the standard signals.
english 23
Type 3280, 3285
Maintenance, troubleshooting
24 english
Type 3280, 3285
Maintenance, troubleshooting
Valve is not Low power function activated; motor torque Deactivate low power function
opening or closing for medium pressure too low
correctly
Valve is not sealed Dirt between seal and valve seat Install dirt filter and return device to the manufacturer for cleaning
english 25
Type 3280, 3285
Transport, storage, disposal
Note!
Transport damage.
Inadequately protected devices may be damaged during
transportation.
•• Protect the device against moisture and dirt in shock-
resistant packaging during transportation.
•• Prevent the temperature from exceeding or dropping below the
permitted storage temperature.
•• Using protective caps, protect the electrical interfaces from
damage.
Incorrect storage may damage the device.
•• Store the device in a dry and dust-free location!
•• Storage temperature: -20...+70 °C.
Damage to the environment caused by parts contaminated
with medium.
•• Dispose of the device and packaging in an environmentally
friendly manner.
•• Observe applicable disposal and environmental regulations.
26 english