You are on page 1of 3

Emergency Stop Relays, Safety Gate Monitors

Category 3, EN 954-1
PNOZ V

Technical Data PNOZ V

Electrical Data
Supply Voltage 24 VDC
Tolerance
Power Consumption
Voltage and Current at the Input and,
Reset Cirucits and Feedback Control Loop
85 ... 110 %
Approx. 5 W
24 VDC, 50 mA
1
Switching Capability
Contacts 13-14, 23-24, 33-34, 41-42
in accordance with EN 60947-4-1, 10/91 AC1: 240 V/8 A/2000 VA
400 V/ 5 A/2000 VA
DC1: 24 V/8 A/200 W
in accordance with EN 60947-5-1, 10/91 AC15: 230 V/5 A; DC13: 24 V/4 A
(DC13: 6 cycles/min.)
Contact 57-58
Emergency stop relay and safety gate in accordance with EN 60947-4-1, 10/91 AC1: 240 V/4 A/1000 VA
monitor in accordance with DC1: 24 V/4 A/100 W
VDE 0113-1, 11/98, EN 60204-1, in accordance with EN 60947-5-1, 10/91 AC15: 230 V/4 A; DC13: 24 V/4 A
12/97 and IEC 204-1, 11/98. (DC13: 6 cycles/min.)
Output Contacts 3 safety contacts (N/O)
1 auxiliary contact (N/C)
Features Output Contacts with Delay-on 1 safety contact (N/O)
De-energisation
● Single-channel or dual-channel Contact Fuse Protection 10 A quick or 6 A slow
without the detection of shorts (EN 60947-5-1, 10/91)
across the input contacts Times
● Supply voltage: 24 VDC Delay-on Energisation Approx. 150 ms
● 1 delay-off safety contact Delay-on De-energisation Approx. 50 ms
Delay-on De-energisation, Selectable time ranges:
delayed contact 57/58 Approx. 0.1 ... 3 s; 0.5 ... 30 s; 0.5 ... 300 s;
Approvals
Fixed time ranges:
3 s; 10 s
PNOZ V Recovery Time Approx. 0.3 s
Simultaneity channel 1/2 Approx. 75 ms
Max.Supply Interruption before De-energisation Approx. 35 ms

Mechanical Data
Torque Setting on Connection Terminals 1.2 Nm (screws)
● Maximum Cross Section of 2 x 2.5 mm2
External Conductors Single-core or multi-core
● with crimp connectors
Dimensions (H x W x D) 75 x 90 x 110 mm
Weight 480 g
Description
● Connections for Operating Modes
● 90 mm P-75 housing, DIN Rail – E-STOP button
mounting – safety gate limit switch ● Single-channel operation
● Positive-guided relay outputs, – reset button ● Dual-channel operation
instantaneous: ● LEDs for channel 1/2 and supply ● Automatic reset
– 3 safety contacts (N/O) voltage ● Manual reset
– 1 auxiliary contact (N/C) ● Increase in the number of
● Positive-guided relay outputs, safety contacts available by
delay-off: connecting expander modules.
– 1 safety contact (N/O)
● Delay-off time can be selected:
12 time periods on units with
variable ranges

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-068-05/01


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

1-1
Emergency Stop Relays, Safety Gate Monitors

Category 3, EN 954-1
PNOZ V

Internal Wiring Diagram ● Increase in safety contacts


The number of output contacts can
be increased by using expander
UB Input circuits Reset circuit Feedback Safety Auxiliary Safety modules or relays/contactors with
control loop contacts contact contact positive-guided contacts.

1
A1 A2 S12 S12 S11 S22 S33 S34 Y1 Y2 13 23 33 41 57

F1 K1

K2 1L1
K1 K4 (1L+)
K4
K3 K1 K3 K2
K5 K2 K5 K9 K7

K1 K4 K2 K5 K3
K3 K8 K6
Y1 Y2 57 13

14 24 34 42 58

External Wiring 58 14

● Example 1 ● Example 4
K8 K9 K6 K7
Single-channel E-STOP wiring with Dual-channel safety gate control with 1L2
manual reset. manual reset. (1L-)

S11 S22 S33 Y1 S12 S33 Y1

S1

S1 S11
S2 S3

S2

S12 S12 S34 Y2 S22 S34 Y2

● Example 2 ● Example 5
Dual-channel E-STOP wiring with Dual-channel safety gate control with
manual reset. automatic reset.

S11 S33 Y1 S12 S33 Y1

S1
S1
S2 S11

S2

S12 S22 S34 Y2 S22 S34 Y2

● Example 3 – Key
Single-channel safety gate control
with manual reset.

S11 S22 S33 Y1 S1/2: E-STOP or safety gate switch

S3: Reset button


S2
S1
Switch operated

Gate open

S12 S12 S34 Y2


Gate closed

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-068-05/01


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
Emergency Stop Relays, Safety Gate Monitors

Category 3, EN 954-1
PNOZ V

General Technical Data

Unless stated otherwise in the technical details for the specific unit

1
Electrical Data
Frequency Range AC 50 ... 60 Hz
Residual Ripple DC 160 %
Contact Material AgSnO2
Continuous Duty 100 %
Environmental Data
EMC EN 50081-1, 01/92, EN 50082-2, 03/95
Vibration in accordance with Frequency: 10 ... 55 Hz,
EN 60068-2-6, 04/95 Amplitude: 0.35 mm
Climatic Suitability DIN IEC 60068-2-3, 12/86
Airgap Creepage DIN VDE 0110 part 1, 04/97
Ambient Temperature -10 ... +55 °C
Storage Temperature -40 ... +85 °C
Mechanical Data
Torque Setting on Connection Terminals 0.6 Nm (screws)
Mounting Position Any
Housing Material Thermoplast Noryl SE 100
Protection Mounting: IP 54
Housing: IP 40
Terminal Range: IP 20

The units were tested in accordance with the relevant standards current at
the time of development.

Order References

Type t UB Order No.


PNOZ V 3s 24 V DC 474 789
PNOZ V 30 s 24 V DC 474 790
PNOZ V 3 s fest 24 V DC 474 796
PNOZ V 10 s fest 24 V DC 474 799
PNOZ V 300 s 24 V DC 474 791

Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland NSG-D-2-068-05/01


Telefon +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de

1-3