You are on page 1of 7

Project :

Owner :
Address :

FEEDER AND BRANCH CIRCUITS CALCULATIONS

FOR CICUIT 1: LIGHTING LOADS @ 100 V.A. PER FIXTURES


TOTAL V.A = 18 X 100 = 1800 VA
180 0
I1¿ =7.83 AMPS ; %VD = 0.78% IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 15AT , 100AF , 2P CB

FOR CIRCUIT 2: LIGHTING OUTLETS @ 100 V.A. PER FIXTURES


TOTAL V.A. = 200 X 100 = 2000 VA
2000
I2¿ =8.70 AMPS ; %VD = 0.87% IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 15AT , 100AF , 2P CB

FOR CIRCUIT 3: LIGHTING OUTLETS @ 100 V.A. PER FIXTURES


TOTAL V.A. = 16 X 100 = 1600 VA
1600
I3¿ =6.96 AMPS ; %VD = 0.70% IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 15AT , 100AF , 2P CB

FOR CIRCUIT 4: LIGHTING OUTLETS @ 100 V.A. PER FIXTURES


TOTAL V.A. = 16 X 100 = 1600 VA
160 0
I4¿ =6.96 AMPS ; %VD = 0.70% IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 20mm DIA . PVC 30AT , 100AF , 2P CB

FOR CIRCUIT 5: LIGHTING OUTLETS @ 100 V.A. PER FIXTURES


TOTAL V.A. = 13 X 100 = 1300 VA
1300
I5¿ =5.65 AMPS ; %VD 0.57 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 15AT , 100AF , 2P CB

FOR CIRCUIT 6: LIGHTING OUTLETS @ 100 V.A. PER FIXTURES


TOTAL V.A. = 12 X 100 = 1200 VA
1200
I6¿ =5.22 AMPS ; %VD = 0.52 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 15AT , 100AF , 2P CB

FOR CIRCUIT 7: LIGHTING OUTLETS @ 100 V.A. PER FIXTURES


TOTAL V.A. = 14 X 100 = 1400 VA
1400
I7¿ =6.09 AMPS ; %VD = 0.61 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 15AT , 100AF , 2P CB

Page 1 of 7
Project :
Owner :
Address :

FOR CIRCUIT 8: CONVENIENCE OUTLETS @ 200 V.A. PER FIXTURES


TOTAL V.A. = 5 X 200 = 2000 VA
20 00
I8¿ =4.35 AMPS ; %VD 0.44 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB
FOR CIRCUIT 9: CONVENIENCE OUTLETS @ 200 V.A. PER FIXTURES
TOTAL V.A. = 4 X 200 = 800 VA
800
I9¿ =3.48 AMPS ; %VD 0.35 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 10: CONVENIENCE OUTLETS @ 200 V.A. PER FIXTURES


TOTAL V.A. = 3 X 200 = 600 VA
600
I10¿ =2.61 AMPS ; %VD 0.26 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 11: CONVENIENCE OUTLETS @ 200 V.A. PER FIXTURES


TOTAL V.A. = 4 X 200 = 800 VA
8 00
I11¿ =3.48 AMPS ; %VD 0.35 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 12: CONVENIENCE OUTLET (REFRIGERATOR) @ 1200 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1200 = 1200 VA
1200
I12¿ =5.22 AMPS ; %VD 0.52 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 30AT , 100AF , 2P CB

FOR CIRCUIT 13: CONVENIENCE OUTLET (RANGE) @ 1500 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1500 = 1500 VA
1500
I13¿ 6.52 AMPS ; %VD 0.65 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 30AT , 100AF , 2P CB

FOR CIRCUIT 14: CONVENIENCE OUTLET (ACU) @ 1500 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1500 = 1500 VA
1500
I14¿ 6.52 AMPS ; %VD 0.65 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 15: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 4 X 200 = 800 VA

Page 2 of 7
Project :
Owner :
Address :

800
I15¿ 3.48 AMPS ; %VD 0.35 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 16: CONVENIENCE OUTLET (ACU) @ 1500 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1500 = 1500 VA
1500
I16¿ 6.52 AMPS ; %VD 0.65 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 17: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 4 X 200 = 800 VA
800
I17¿ 3.48 AMPS ; %VD 0.35 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 18: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 6 X 200 = 1200 VA
1200
I18¿ 5.22 AMPS ; %VD 0.52 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 19: CONVENIENCE OUTLET (ACU) @ 1500 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1500 = 1500 VA
1500
I19¿ 6.52 AMPS ; %VD 0.65 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 20: CONVENIENCE OUTLET (ACU) @ 1500 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1500 = 1500 VA
1500
I20¿ 6.52 AMPS ; %VD 0.65 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 21: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 3 X 200 = 600 VA
600
I21¿ 2.61 AMPS ; %VD 0.26 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 22: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 4 X 200 = 800 VA

Page 3 of 7
Project :
Owner :
Address :

800
I22¿ 3.48 AMPS ; %VD 0.35 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 23: CONVENIENCE OUTLET (ACU) @ 1500 V.A. PER FIXTURES
TOTAL V.A. = 1 X 1500 = 1500 VA
1500
I23¿ 6.52 AMPS ; %VD 0.65 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 24: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 3 X 200 = 600 VA
600
I24¿ 2.61 AMPS ; %VD 0.26 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR CIRCUIT 25: CONVENIENCE OUTLET @ 200 V.A. PER FIXTURES


TOTAL V.A. = 4 X 200 = 800 VA
800
I25¿ 3.48 AMPS ; %VD 0.35 % IS < 3%
230
THUS USE : 2-3.5 mm2 THHN COPPER WIRE IN 15mm DIA . PVC 20AT , 100AF , 2P CB

FOR FEEDER
IF = I1 + I2 + I3 + I4 + I5 + I6 + I7 + I8 + I9 + I10 + I11 + I12 + I13 + I14 + I15 + I16 + I17 + I18 + I19 + I20 + I21 + I22 + I23 + I24
+ I25 + I SPARE
IF = 7.83 + 8.70 + 6.96 + 6.96 + 5.65 + 5.22 + 6.09 + 4.35 + 3.48 + 2.61 + 3.48 + 5.22 + 6.52 + 6.52 +
1000
3.48 + 6.52 + 3.48 + 5.22 + 6.52 + 6.52 + 2.61 + 3.48 + 6.52 + 2.61 + 3.48 +
230
IF = 130.03 AMPS
SINCE THE BRANCH CIRCUITS USED 20AT AND 3.5mm 2
THUS USE : 2-38mm2 THHN COPPER WIRE, 1-5.538mm2 THW NEUTRAL FEEDER IN 38 mm DIA . RSC
150AT , 50AF , 2P CB

FOR SERVICE ENTRANCE


@ 80% DEMAND FACTOR
I = 130.03 X 0.80 = 110.5 AMP

THUS USE: 2 – 14mm2 THHN COPPER WIRE


1 – 8.0mm2 THHN COPPER WIRE (G)

Page 4 of 7
Project :
Owner :
Address :

BUT SINCE 2 – 14mm2 THHN COPPER WISE IS THE PREFERRED


CONDUCTOR FOR THE FEEDERS AND CONSIDERING FUTURE LOAD
APPLICATIONS, THE USE OF 2- 22mm2 THHN COPPER WIRE CAN BE CONSIDERED
AND USED 1 – 8.0mm2 THHN COPPER WIRE AS GROUND

Page 5 of 7
Project :
Owner :
Address :

VOLTAGE DROP CALCULATION

Circuit No. : 1 Wire Size: 3.5mm2 THHN COPPER WIRE


Voltage : 230 Total VA : 1800

One-way Legnth of Circuit (L) in ft : 139.57 42.00 meter


Conductor Resistance in Ohms per thousand feet (‘R) : 2.075931 @75°C
Load Current (I) : 7.83 purely resistive loads

2x Lx R x I
VD =
1000

2 x 139.57 x 2.075931 x 7.83


VD =
1000

VD = 4.537

7.7219
%VD = = 0.020%
230

Voltage Drop does not exceed 3%


Thus, use 3.5 mm2 THHN Copper Wire

Circuit No. : 2 Wire Size: 3.5mm2 THHN Copper Wire


Voltage : 230 Total VA : 1520

One-way Length of Circuit (L) in ft : 111.5157 33.99 meter


Conductor Resistance in Ohms per thousand feet (‘R) : 2.075931 @75°C
Load Current (I) : 6.61 purely resistive loads

2x Lx R x I
VD =
1000

2 x 111.5157 x 2.075931 x 6.61


VD =
1000

VD = 3.0604

3.0604
%VD = = 0.0133%
230

Page 6 of 7
Project :
Owner :
Address :

Voltage Drop does not exceed 3%


Thus, use 3.5 mm2 THHN Copper Wire

Circuit No. : Gutter Wire Size: 22.0 mm2 THHN COPPER WIRE
Voltage : 230 Total VA : 15694

One-way Legnth of Circuit (L) in ft : 19.69 6.00 meter


Conductor Resistance in Ohms per thousand feet (‘R) : 0.3229226 @75°C
Load Current (I) : 68.20 purely resistive loads

2x Lx R x I
VD =
1000

2 x 19.69 x 0.3229226 x 68.20


VD =
1000

VD = 0.8673

0.8673
%VD = = 0.0037%
230

Voltage Drop does not exceed 5%


Thus, use 22.0 mm2 THHN Copper Wire