Standard Specification for


Loadbearing Concrete Masonry Units1
This standard is issued under the fixed designation C 90; the number immediately following the designation indicates the year of original
adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A superscript
epsilon (e) indicates an editorial change since the last revision or reapproval.

This standard has been approved for use by agencies of the Department of Defense.

1. Scope * C 595 Specification for Blended Hydraulic Cements4


1.1 This specification covers hollow and solid (see 6.4 and C 618 Specification for Coal Fly Ash and Raw or Calcined
6.5) concrete masonry units made from portland cement, water, Natural Pozzolan for Use as a Mineral Admixture in
and mineral aggregates with or without the inclusion of other Concrete2
materials. There are three classes of concrete masonry units: C 989 Specification for Ground Granulated Blast-Furnace
(1) normal weight, (2) medium weight, and (3) lightweight. Slag for Use in Concrete and Mortars2
There are two types of concrete masonry units: (1) Type I, C 1157 Performance Specification for Blended Hydraulic
moisture-controlled, and (2) Type II, nonmoisture-controlled. Cement4
These units are suitable for both loadbearing and nonloadbear- C 1209 Terminology of Concrete Masonry Units and Re-
ing applications. lated Units3
1.2 Concrete masonry units covered by this specification are C 1232 Terminology of Masonry3
made from lightweight or normal weight aggregates, or both. C 1314 Test Method for Constructing and Testing Masonry
1.3 The text of this standard references notes and footnotes Prisms Used to Determine Compliance with Specified
which provide explanatory material. These notes and footnotes Compressive Strength of Masonry3
(excluding those in tables and figures) shall not be considered E 519 Test Method for Diagonal Tension (Shear) in Ma-
as requirements of the standard. sonry Assemblages3
1.4 The values stated in inch-pound units are to be regarded E 72 Methods for Conducting Strength Tests of Panels for
as the standard. The values given in parentheses are for Building Construction5
information only. 3. Terminology
NOTE 1—When particular features are desired such as surface textures 3.1 Terminology defined in Terminology C 1209 and Ter-
for appearance or bond, finish, color, or particular properties such as
minology C 1232 shall apply for this specification.
weight classification, higher compressive strength, fire resistance, thermal
performance or acoustical performance, these features should be specified 4. Classification
separately by the purchaser. Local suppliers should be consulted as to the
availability of units having the desired features. 4.1 Types—Two types of concrete masonry units are cov-
ered as follows:
2. Referenced Documents 4.1.1 Type I, Moisture-Controlled Units—Units designated
2.1 ASTM Standards: as Type I shall conform to the requirements of this specifica-
C 33 Specification for Concrete Aggregates2 tion.
C 140 Test Methods for Sampling and Testing Concrete 4.1.2 Type II, Nonmoisture-Controlled Units—Units desig-
Masonry Units and Related Units3 nated as Type II shall conform to the requirements of this
C 150 Specification for Portland Cement4 specification, except the requirements of Table 1.
C 331 Specification for Lightweight Aggregates for Con-
crete Masonry Units2 5. Materials
C 426 Test Method for Drying Shrinkage of Concrete Ma- 5.1 Cementitious Materials—Materials shall conform to the
sonry Units3 following applicable specifications:
5.1.1 Portland Cement— Specification C 150.
5.1.2 Modified Portland Cement—Portland cement con-
1
This specification is under the jurisdiction of ASTM Committee C-15 on forming to Specification C 150, modified as follows:
Manufactured Masonry Units and is the direct responsibility of Subcommittee 5.1.2.1 Limestone—Calcium carbonate, with a minimum
C15.03 on Concrete Masonry Units and Related Units. 85 % CaCO3 content, is permitted to be added to the cement,
Current edition approved Aug. 10, 1999. Published October 1999. Originally
published as C 90 – 31T. Last previous edition C 90 – 99.
2
Annual Book of ASTM Standards, Vol 04.02.
3
Annual Book of ASTM Standards, Vol 04.05.
4 5
Annual Book of ASTM Standards, Vol 04.01. Annual Book of ASTM Standards, Vol 04.07.

*A Summary of Changes section appears at the end of this standard.


Copyright © ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States.

1
C 90
TABLE 1 Moisture Content Requirements for Type I Units TABLE 2 Minimum Thickness of Face Shells and Webs
Moisture Content, max, % of Total Web Thickness (tw)
Absorption (Average of 3 Units) Face Shell
Total Linear Drying Nominal Width (W) of Equivalent Web
HumidityA Conditions at Job Site or Thickness (tfs),
Shrinkage, % Units, in. (mm) Thickness, min,
Point of Use min, in. (mm)A WebsB min, in.
in./linear ftB,C
HumidB IntermediateC AridD (mm)
(mm/linear m)
Less than 0.03 45 40 35
0.03 to less than 0.045 40 35 30 3 (76.2) and 4 (102) 3⁄4 (19) ⁄ (19)
34 15⁄8 (136)
0.045 to 0.065, max 35 30 25 6 (152) 1 (25)D 1 (25) 21⁄4 (188)
A 8 (203) 11⁄4 (32)D 1 (25) 21⁄4 (188)
See Appendix X1 (Fig. X1.1) for map of mean annual relative humidity.
B 10 (254) 13⁄8 (35)D 11⁄8 (29) 21⁄2 (209)
Mean annual relative humidity above 75 %.
C 11⁄4 (32)D,E
Mean annual relative humidity 50 to 75 %.
D 12 (305) and greater 11⁄2(38) 11⁄8 (29) 21⁄2 (209)
Mean annual relative humidity less than 50 %.
11⁄4 (32)D,E
A
Average of measurements on 3 units taken at the thinnest point when
provided these requirements of Specification C 150 as modi- measured as described in Test Methods C 140. When this standard is used for split
face units, a maximum of 10 % of a split face shell area is permitted to have
fied are met: thickness less than those shown, but not less than 3⁄4in. (19.1 mm). When the units
(1) Limitation on Insoluble Residue—1.5 %. are solid grouted the 10 % limit does not apply.
B
(2) Limitation on Air Content of Mortar—Volume percent, Average of measurements on 3 units taken at the thinnest point when
measured as described in Test Methods C 140. The minimum web thickness for
22 % max. units with webs closer than 1 in. (25.4 mm) apart shall be 3⁄4 in. (19.1 mm).
(3) Limitation on Loss on Ignition—7 %. C
Sum of the measured thicknesses of all webs in the unit, multiplied by 12 and
5.1.3 Blended Cements— Specification C 595 or Perfor- divided by the length of the unit. Equivalent web thickness does not apply to the
portion of the unit to be filled with grout. The length of that portion shall be deducted
mance Specification C 1157. from the overall length of the unit for the calculation of the equivalent web
5.1.4 Pozzolans—Specification C 618. thickness.
D
For solid grouted masonry construction, minimum face shell thickness shall be
5.1.5 Blast Furnace Slag Cement—Specification C 989. not less than 5⁄8 in. (16 mm).
5.2 Aggregates—Aggregates shall conform to the following E
This face shell thickness (tfs) is applicable where allowable design load is
specifications, except that grading requirements shall not reduced in proportion to the reduction in thickness from basic face shell thick-
nesses shown, except that allowable design loads on solid grouted units shall not
necessarily apply: be reduced.
5.2.1 Normal Weight Aggregates—Specification C 33.
5.2.2 Lightweight Aggregates—Specification C 331. capability has been established when tested in accordance with the
applicable provisions of Test Methods E 72, C 1314, E 519, or other
5.3 Other Constituents—Air-entraining agents, coloring applicable tests and the appropriate design criteria developed is in
pigments, integral water repellents, finely ground silica, and accordance with applicable building codes.
other constituents shall be previously established as suitable for
6.5 Solid Units:
use in concrete masonry units and shall conform to applicable
6.5.1 The net cross-sectional area of solid units in every
ASTM standards or shall be shown by test or experience not to
plane parallel to the bearing surface shall be not less than 75 %
be detrimental to the durability of the concrete masonry units
of the gross cross-sectional area measured in the same plane.
or any material customarily used in masonry construction.
6.6 End Flanges:
6. Physical Requirements 6.6.1 For units having end flanges, the thickness of each
flange shall not be less than the minimum face shell thickness.
6.1 At the time of delivery to the purchaser, all units shall
conform to the physical requirements prescribed in Table 2 and NOTE 5—Flanges beveled at the ends for mortarless head joint appli-
Table 3. cations that will be filled with grout are exempt from this requirement.
Flanges which are specially shaped for mortarless head joint applications
NOTE 2—Higher compressive strengths than those listed in Table 3 may which have been shown by testing or field experience to provide
be specified where required by design. Consult with local suppliers to equivalent performance are exempt from this requirement.
determine availability of units of higher compressive strength.
7. Permissible Variations in Dimensions
6.2 At the time of delivery to the purchaser, Type I units
shall conform to the requirements prescribed in Table 1. 7.1 Standard Units— For standard units, no overall dimen-
6.3 At the time of delivery to the purchaser, the linear sion (width, height, and length) shall differ by more than
shrinkage of Type I and Type II units shall not exceed 0.065 %. 61⁄8 in. (3.2 mm) from the specified dimensions.
7.2 Particular Feature Units—For particular feature units,
NOTE 3—The purchaser is the public body or authority, association, dimensions shall be in accordance with the following:
corporation, partnership, or individual entering into a contract or agree-
7.2.1 For molded face units, no overall dimension (width,
ment to purchase or install, or both, concrete masonry units. The time of
delivery to the purchaser is FOB plant when the purchaser or the height, and length) shall differ by more than 61⁄8 in. (3.2 mm)
purchaser’s agent transports the concrete masonry units, or at the time from the specified standard dimension. Dimensions of molded
unloaded at the worksite if the manufacturer or the manufacturer’s agent features shall be within 61⁄16 in. (1.6 mm) of the specified
transports the concrete masonry units. standard dimensions and shall be within 61⁄16 in. (1.6 mm) of
6.4 Hollow Units: the specified placement of the molded feature.
6.4.1 Face shell thickness (tfs) and web thickness (tw) shall NOTE 6—Molded features include, but are not limited to: ribs, scores,
conform to the requirements prescribed in Table 2. hex-shapes, and patterns.
NOTE 4—Web thickness (tw) not conforming to the requirements 7.2.2 For split-faced units, all non-split overall dimensions
prescribed in Table 2 may be approved, provided equivalent structural shall differ by not more than 61⁄8 in. (3.2 mm) from the

2
C 90
TABLE 3 Strength and Absorption Requirements
Compressive Strength,Amin, psi (MPa) Water Absorption, max, lb/ft3(kg/m3) (Average of 3 Units)
Average Net Area Weight Classification—Oven-Dry Weight of Concrete, lb/ft3 (kg/m3)
Lightweight, less than Medium Weight, 105 to Normal Weight, 125 (2000)
Average of 3 Units Individual Unit
105 (1680) less than 125 (1680–2000) or more
1900 (13.1) 1700 (11.7) 18 (288) 15 (240) 13 (208)

specified standard dimensions. On faces that are split, overall 9.2 Sample and test units in accordance with Test Methods
dimension will vary. Consult with local suppliers to determine C 140.
achievable dimensional tolerances. 9.3 Total linear drying shrinkage shall be based on tests of
7.2.3 For slump units, no overall height dimension shall concrete masonry units made with the same materials, concrete
differ by more than 61⁄8 in. (3.2 mm) from the specified mix design, manufacturing process, and curing method, con-
standard dimension. On faces that are slumped, overall dimen- ducted in accordance with Test Method C 426 and not more
sions will vary. Consult with local suppliers to determine than 24 months prior to delivery.
achievable dimensional tolerances.
8. Finish and Appearance 10. Compliance
8.1 All units shall be sound and free of cracks or other 10.1 If a sample fails to conform to the specified require-
defects that interfere with the proper placement of the unit or ments, the manufacturer shall be permitted to remove units
significantly impair the strength or permanence of the construc- from the shipment. A new sample shall be selected by the
tion. Minor cracks incidental to the usual method of manufac- purchaser from remaining units from the shipment with a
ture or minor chipping resulting from customary methods of similar configuration and dimension and tested at the expense
handling in shipment and delivery are not grounds for rejec- of the manufacturer. If the second sample meets the specified
tion. requirements, the remaining portion of the shipment repre-
8.2 Where units are to be used in exposed wall construction, sented by the sample meets the specified requirements. If the
the face or faces that are to be exposed shall not show chips or second sample fails to meet the specified requirements, the
cracks, not otherwise permitted, or other imperfections when remaining portion of the shipment represented by the sample
viewed from a distance of not less than 20 ft (6.1 m) under
fails to meet the specified requirements.
diffused lighting.
8.2.1 Five percent of a shipment containing chips not larger NOTE 7—Unless otherwise specified in the purchase order, the cost of
than 1 in. (25.4 mm) in any dimension, or cracks not wider than tests is typically borne as follows: (1) if the results of the tests show that
0.02 in. (0.5 mm) and not longer than 25 % of the nominal the units do not conform to the requirements of this specification, the cost
height of the unit is permitted. is typically borne by the seller; (2) if the results of the tests show that the
8.3 The color and texture of units shall be specified by the units conform to the specification requirements, the cost is typically borne
purchaser. The finished surfaces that will be exposed in place by the purchaser.
shall conform to an approved sample consisting of not less than
11. Keywords
four units, representing the range of texture and color permit-
ted. 11.1 absorption; climatic map; concrete masonry units;
equivalent web thickness; face shell; flange; lightweight; linear
9. Sampling and Testing shrinkage; loadbearing; medium weight; moisture-controlled;
9.1 The purchaser or authorized representative shall be normal weight; webs
accorded proper facilities to inspect and sample the units at the
place of manufacture from the lots ready for delivery.

3
C 90

APPENDIXES

(Nonmandatory Information)

X1. CLIMATIC MAP

NOTE 1—Based on 1:30 AM and PM and 7:30 AM and PM Eastern Standard Time, observations for 20 years or more through 1964.
FIG. X1.1 Selected Climatic Maps of the United States

X2. WATER PENETRATION RESISTANCE

X2.1 Exterior walls are often subjected to moisture pen- flashing, and drainage should be provided. Proper water
etration from one or more sources. For example, basement penetration resistant treatments should be applied to the walls.
walls may be exposed to water from saturated soil. Above- While it is not within the scope of Specification C 90 to include
grade exterior walls are usually exposed to wind-driven rain. information on resistance to water penetration, such informa-
To prevent water penetration, proper detailing, construction, tion and guidelines are available from other organizations.

4
C 90
SUMMARY OF CHANGES

Committee C-15 has identified the location of selected changes to this standard since the C 90-99 edition that
may impact the use of this standard.

(1) The notations for face shell and web thickness were
changed from FST and WT to tfs and tw, respectively.

The American Society for Testing and Materials takes no position respecting the validity of any patent rights asserted in connection
with any item mentioned in this standard. Users of this standard are expressly advised that determination of the validity of any such
patent rights, and the risk of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM Headquarters. Your comments will receive careful consideration at a meeting of the responsible
technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should make your
views known to the ASTM Committee on Standards, 100 Barr Harbor Drive, West Conshohocken, PA 19428.

This standard is copyrighted by ASTM, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, United States. Individual
reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above address or at 610-832-9585
(phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website (http://www.astm.org).