AquaCell Plus
AquaCell systems are a fully tried and tested modular technique Helping SUDS and planning approval
for managing excessive rainfall. Units are assembled to create
The proven qualities and performance of AquaCell systems
an underground structure as either temporary storage tank or
not only support the achievement of SUDS, they can also
soakaway.
help reinforce and enhance planning applications, and enable
There are 3 types of unit: development to proceed.
These being:
AquaCell Core
1. Manifold Configuration – this configuration utilizes standard
for trafficked locations (page 11), and
pipe and fittings (see page 23)
2. Box Configuration – this configuration utilizes the AquaCell Core
AquaCell Plus units (see page 23)
for extra deep installations and/or inspectability (pages 12-13) 3. Central Pipe Configuration – this configuration utilizes standard
perferated TwinWall pipe and fittings (see page 23)
For quick, versatile assembly
The lightweight polypropylene, high void units are securely
linked together using special clips and shear connectors.
AquaCell Plus
Approved under BBA Agrément
Certificate No.03/4018, Detail Sheet 3
Principal Components
Ancillary Components
6LB105
Clip
(Used to hold units
together horizontally)
6UR141 6TW141 6D099 6LB102
UltraRib S/S Adaptor TwinWall S/S Adaptor OsmaDrain S/S Reducer Shear Connector
(Fits into pre-formed socket to (Fits into pre-formed socket to 160mm x 110mm (fits into (Used to hold units
connect to 150mm UltraRib) connect to 150mm TwinWall) pre-formed socket to connect together vertically)
to 110mm OsmaDrain)
4D916 6D129
160mm OsmaDrain OsmaDrain S/S Adaptor –
P/E Adaptor Thinwall Clay Spigot
(Fits into pre-formed socket as (For use with 6D916 when
an extension connection piece) connecting to a BS EN 295
Thinwall Clay Spigot)
6LB300 6LB600
Domestic Silt Trap Silt Trap
(Bucket and extension piece available) (Use extension kit if required)
AquaCell Eco
6LB025
Roundabouts
AquaCell Eco
6LB025
l 1,400 unit storage tank to store run-off from expanding retail park
Roads
AquaCell Core
6LB100
For any installation where extra depth and/or Extra deep installations
inspectability is required.
Installation depth
l Maximum to base of units*: 5.08 metres Non-trafficked areas
*in best soil conditions
Other features
Specific to AquaCell Plus:
AquaCell Plus
6LB200
End cap for when an
inspection channel
is not required
Inspection chambers
An inspection chamber should precede the inlet pipework
for the AquaCell structure:
NO YES
NO YES
NO YES
NO YES
Will the tank need to be installed
extra deep (ie deeper than 4.1m
Will the tank be more than 4.25m deep? in ideal soil conditions)?
NO YES NO YES
Notes:
AquaCell Eco cannot be used directly
with AquaCell Plus.
If the tanks need to be inspectable, contact
Wavin Technical Design on 0844 8565161.
0.3-0.5m
minimum 0.6-0.75m
cover depth minimum
cover depth
Max. depth
to 1.5m
Max. depth
Max. depth to 4.1m
to 4.25m
Max. depth Max. depth
to 5.08m to 4.78m
Non-trafficked Trafficked
This helps minimise
continuous vertical joints
5 in the assembly, and gives
the structure extra stability.
3 3
No extra connectors required with AquaCell
A significant advantage of AquaCell unit design is that
brick-bonding placement does not require extra connectors.
1 1
All three AquaCell systems may be placed in this way, unless
inspection channels and cleaning access are required using
2 2
Suitable box Suitable box AquaCell Plus (see NOTE).
system = ? system = ? NOTE: AquaCell Plus units incorporate integral inspection
4 4
channels. These are designed for combined alignment to create
viewing tunnels at the base of an assembled structure.
If either of these criteria is not the case, or cannot be confirmed Construction traffic on site
for any reason, a soakaway system may not be suitable for the If construction plant (e.g. excavators or loaders) are likely to run
application. over the installation:
This may be designed to be online or offline (see pages 26-32 l HGVs MUST NOT run over installed AquaCell Eco units
for typical details).
Backfilling
However, if the site is subject to groundwater or a high water When backfilling AquaCell Eco installations:
table, it is important to ensure that the tank is not vulnerable to
l Machines placing the material must be located OFF the units
flotation. Sufficient weight from soil, or other covering placed over
the AquaCell units, must be sufficient to counter any buoyancy l Only light compaction should be applied to the material
uplift force of that water.
If Type 1 sub-base (or similar) material over AquaCell Eco units
Site assessment requires compaction:
Ground conditions may be established as part of a geotechnical l First layer should be 300mm thick before any compaction
assessment. This may include tests for infiltration and ground
water level. l NO vibratory mechanism should be used for compacting
this first layer
If there is no confirmation that such assessments have been
conducted, or resulting conclusions are unavailable, a trial pit l MAXIMUM roller size: 2300 kg per metre width
AquaCell Units
100mm
Permeable geotextile*
Pre-formed socket
100mm
AquaCell Units
100mm
Suitable impermeable
geomembrane
Suitable protective
geotextile layer
Pre-formed socket
100mm
6. Wrap the geomembrane around the AquaCell structure and seal to manufacturers
recommendations.*
7. If side connections into the AquaCell units is required, (other than the preformed socket),
use the appropriate Flange Adaptor (6LB104 or 6LB105). Fix the flange adaptor to the unit
using self-tapping screws. Drill a hole through the Flange Adaptor and connect the
pipework.
8. In order to prevent silt from entering the tank, clogging inlet pipework and reducing storage
capacity, it is recommended that the Domestic Silt Trap (6LB300) or the standard Silt Trap
(6LB600) is installed prior to the inlet pipework – see page 20 for installation guidelines.
9. Wrap and overlap the geotextile covering the entire AquaCell structure, to protect the
geomembrane.
10. Lay 100mm of coarse sand between the trench walls and the AquaCell units and compact.
11. Lay 100mm bed of coarse sand over the geotextile and compact. Backfill with stone free
as-dug material.
NB: A storage tank must be vented, and it is recommended that one vent pipe, 110mm in
diameter is provided per 7,500 square metres of impermeable catchment area on a site,
see page 18 for design.
Silt Trap
AquaCell Units
Permeable
Geotextile Wrap Jubilee clip
Geomembrane Wrap
Installation Procedure
Flange Adaptor
(6LB104/6LB16) 1. Fix Flange Adaptor to the AquaCell unit
with self tapping screws.
AquaCell Units
Geomembrane wrap
AquaCell Units
Typical Installation
Procedure
1. Fix OsmaDrain Reducer to the AquaCell
tank with self-tapping screws.
2. Drill through geomembrane and AquaCell
unit with a long 150mm Crown Drill Bit
Cutter.
3. Insert pipework into OsmaDrain Reducer
to form air vent.
Introduction
The connections shown here in schematic form, are the 3 options used to connect
AquaCell box
AquaCell box unit assemblies to control chambers. They provide a controlled feed unit assembly
into and out of the AquaCell box unit assemblies, and are used for either infiltration
or attenuation schemes.
Cover and frame
Manifold Connection
Using standard pipes and fittings
150mm/225mm UltraRib
Pipe
Sump
NOTE: The configuration of pipes in a manifold arrangement will vary to suit site conditions and aniticip[ated stormwater intensity.
See pages 27, 29 and 31 for this option in context.
Pipe
Sump
Pipe
Sump
T S
Key
S = AquaCell units soakaway
(See note 2)
S T
T = 250mm Dia Silt Trap
Deep Soakaway
Non-traffic load area Ground level
Notes
1. Soakaways should
be sited at least 5m
Min depth* away from the building
(Ref BS EN 752-4)
* For information
110mm Domestic
OsmaDrain Silt Trap regarding cover depths
and installation depths,
see page 15.
AquaCell Units
Min depth*
Installation
depth*
225mm UltraRib
For minimum depth of
cover contact Wavin
150mm UltraRib
Silt trap
Ventilation box
Precast
150mm concrete surround
Precast concrete
concrete chamber
chamber sections and
sections and A cover slab
cover slab
Flow control
Water Water
flow flow
Sump Sump
A
Water Water
flow flow
Sump
Cross Section A-A AquaCell Plus units 2. Then, during a storm event, the AquaCell box unit
used as the lower
storage assembly quickly fills with water via the box feed
layer
connection.
3. After storm event, water flows back out of the AquaCell
box unit storage assembly, finding its own level, and into
the downstream control chamber.
4. The water then flows through the vortex flow control valve.
Ventilation box
Precast
150mm concrete surround
Precast concrete
concrete chamber
chamber sections and
sections and A cover slab
cover slab
Flow control
Water Water
flow flow
Sump Sump
A
Water Water
flow flow
Sump
Plan
Cover and frame Flow control
3-pipe manifold
Ventilation box
Precast
150mm concrete surround
Precast concrete
concrete chamber
chamber A sections and
sections and cover slab
cover slab
Flow control
Water Water
flow flow
Sump A Sump
Water Water
flow flow
Sump
Coarse sand or non angular granular 14mm - 20mm single size granular
material base and surround bedding/backfill material
Ventilation box
Water
flow
Flow control Water
flow
Sump Sump
A
AquaCell unit assembly
Bypass pipe
Water Water
flow flow
Sump
Ventilation box
Precast
Coarse sand or non angular granular 150mm concrete surround concrete
material base and surround chamber
sections and
A cover slab
Weir
wall Flow
control Water
flow
Sump
A
Long Section
AquaCell unit assembly Geomembrane wrap with outer
protective geotextile wrap
Non-return flap valve
Water
flow
Weir
wall
Plan
Precast concrete 150mm concrete
chamber sections surround
Water
Geomembrane wrap with outer flow
protective geotextile wrap
Ventilation box
Precast
Coarse sand or non angular granular 150mm concrete surround concrete
material base and surround chamber
sections and
cover slab
A
Weir
wall
Flow
control Water
flow
Sump
A
Long Section
AquaCell unit assembly Geomembrane wrap with outer
protective geotextile wrap
Non-return flap valve
Water
flow
Weir
wall
Water
flow
Ventilation box
Precast
Coarse sand or non angular granular
150mm concrete surround concrete
material base and surround
chamber
sections and
A cover slab
Weir
wall
Flow
control Water
flow
Long Section
A Sump
Wavin TwinWall half-perforated pipe
AquaCell unit assembly
Wavin TwinWall half-perforated pipe 14mm - 20mm single size granular Non-return flap valve
bedding/backfill material
Flow control
Water
flow
Water
Water flow during storm event Water flow after storm event flow
Plan
14mm - 20mm single size granular bedding/backfill material
Ground level
AquaCell Eco
AquaCell Core
AquaCell Plus
Notes
For bedding specification information refer to page 18 or 19.
Introduction to Garastor*
The development of sites results in a large proportion of area
being covered by impermeable surfaces such as roofs, car parks
and roads. Surface water run-off therefore increases up to 80%.
Building Regulations and guidance now requires a sustainable
approach to development, which minimises the effects of run-off
to that of a greenfield site (20%).
How it works
Storm or surface water flows through two 110mm diameter
incoming pipes. If the flow is light to moderate, the water is simply
stored in the chamber before being slowly released through a
30mm orifice. However, if the inflow is heavy, excess water in
the chamber discharges through a 150mm diameter pipe into
the water storage area (either the undercroft of a garage or an
AquaCell tank). The water is temporarily stored until the water
level inside the chamber has dropped sufficiently, and the water
can flow out to the drainage system via the 110mm outflow pipe.
500mm diameter
4D920
Cover and Frame
installation guidelines.
Such a solution may be entirely based on a tailored combination l PolyChannel SKS range: heavy duty channel
of our engineered systems. for applications up to F900
In other cases, Intesio technology can be integrated with ‘soft’ Also from Wavin: AquaGrid pervious paving.
SUDS techniques, such as ponds and swales, to help achieve
required water management criteria for site concerned. Flow control valves
The Vortex valve range that can be custom-built to suit
site conditions:
Oil separators
A range of chambers, tested to BS EN 858-1
Class 1, and included on the Environment Agency
recommended list. To fulfil PPG3 requirements for
cleansing of surface run-off.
Rainwater re-use
Intesio sustainable schemes can also exploit stored
rainwater. These reduce use of potable mains water for
non-potable purposes.
This may be at the very earliest stage – or when initial plans have
already been developed. There are no pre-conditions for your
asking us to become involved.
info@intesio.co.uk
The Intesio Team has the essential experience and design insight
to help engineer the best possible solution, in its widest sense,
every time.
Wavin operates a programme of continuous product development, and therefore reserves the right to modify or
amend the specification of their products without notice. All information in this publication is given in good faith, and
believed to be correct at the time of going to press. However, no responsibility can be accepted for any errors,
omissions or incorrect assumptions. Users should satisfy themselves that products are suitable for the purpose and
application intended.