You are on page 1of 2

01

Electrical network protection

Sepam series 40

Sepam series 40 is a family of Sepam series 40 and its


current and voltage digital optional modules
protection relays, for medium voltage
1 Base unit, with two types of User Machine
and industrial distribution networks. Interfaces (UMI):
Basic UMI
PE10110_SE

Advanced UMI with graphical LCD screen.


2 Remote advanced UMI.

3 10 logic inputs and 8 outputs relays,


4 outputs on the base unit
+ 1 optional module providing
Characteristics 10 inputs and 4 outputs.

4 Until 2 communication ports +


Conformity to standards 1 front port :
IEC 60255 - Protection relays
Integrated redundancy RSTP
IEC 60529 - Degree of protection IP52 on front panel
IEC 60068 - Operating temperature -25°C to +70°C (-13°F to +158°F) IEC 61850 and Modbus TCP/IP,
IEC 61850-6, 7-1, 7-2, 7,3, 7-4 and 8-1 Communication networks and system in substation Modbus, Modbus TCP/IP,
EIA 364-65A - Conformal coated IIIA IEC 60870-5-103, DNP3 and IEC 61850,
Certifications
communication protocols (wire or fiber optic
CE, UL508, CSA C22.2
network),
Auxiliary power supply
24-250 V DC and 110-240 V AC
Synchronisation through Ethernet SNTP
Overall size of base units (H x W x D) protocol.
222 X 176 X 130 mm
5 Temperature data from 16 sensors,
Pt100, Ni100, or Ni120.

6 1 analog output,
Standard
0-1 mA, 0-10 mA, 4-20 mA or 0-20 mA.
IEC
3 4 61850 7 Software tools:
Sepam parameter and protection setting
and control function customization.
1 Data saved into the relay (48 hours back
up in case of an auxiliary power shutdown.
Local or remote operation via the front and
back ports.
6
PE50546a

2
Electrical network protection Sepam series 40 02

17 types of Sepam series 40


• S40, S41, S42, S43, S44, S50, S51, S52, S53, S54: Substation incomers and feeders protection
• T40, T42, T50, T52: transformer protection.
• M40, M41: motor protection.
• G40: generator protection.
Protection ANSI code S40 S50 S41 S51 S42 S52 S43 S53 S44 S54 T40 T50 T42 T52 M40 M41 G40

S40 S50 T40 M40


Metering to
S44
to
S54
to
T52
to
M41
G40

Network and machine diagnosis

ART. 07900 © Schneider Electric Industries SAS - All rights reserved


DE40548

Switchgear diagnosis

Control & monitoring ANSI code

Additional modules

b standard, v according to parameter setting and MES114/MES114E/MES114F


or MET148-2 input/output module options.
(1) For shunt trip unit or undervoltage trip unit.
(2) 2 modules possible.
(3) Exclusive choice, phase-to-neutral voltage or phase-to-phase voltage for
each of the 2 relays.

Schneider Electric Industries SAS 35 rue Joseph Monier, CS 30323, 92506 Reuil-Malmaison www.schneider-electric.com
PCRED301002EN February 2011