Professional Documents
Culture Documents
Razoa B320 PDF
Razoa B320 PDF
The model has been created using a relay short form presentation. The manual was
not available
The model consists of 3 distance zones each of them created by the intersection
of a mho and a quadrilateral shape.
As starting element the user can use an overcurrent start or an underimpedance
start.
As underimpedance start the model provides an underimpedance circle
characteristic with a minimum operating current(0.2-1.2 In) and the 8In trip
threshold. The oval starting characteristic isn’t supported. The zero sequence
current measuring function is provided but the setting range is unknown so
default range (0.1-100 In) is used. The 8In trip threshold associated in the
relay to the underimpedance starting element in the model is provided as a
separated block (“Starting underimpedance 8n”). The user must manually put out
of service such block when, instead of the underimpedance starting element, the
overcurrent starting element is used.