Variable Flow
Primary Pumping
Variable Flow Primary Pumping Chilled Water System
Variable flow primary pumping systems utilize a distribution of the chilled water and thus less total
variable capacity cooling system and a variable pump energy is required. Also, less pump energy
flow water pumping system to modulate cooling is required because no secondary pump water
and water flow to meet chilled water needs and save valves, fittings, strainers and other secondary
operating energy costs. Cooling capacity is modu- pumping water system components are required.
lated with variable capacity compressors based on Installation costs and ongoing maintenance costs
the desired leaving water temperature. Water flow for variable flow primary pumping systems are
is modulated with VFD controlled variable flow less than with primary/secondary pumping systems
primary pumps based on the differential pressure because secondary pumps and secondary pumping
across the water system. system components are not included in the system.
Usable building space can be saved, or the size
Benefits of the mechanical room can be reduced, with
Primary Pump
Chiller
VFD
Flow Meter
Air-Cooled Condenser
Reducing water flow through the complete system Pump Energy Saving
saves pump energy because only the water flow
required by the load is chilled and delivered. With
a variable flow primary pumping system, at the
A s the load on the chilled water system is
reduced, the water flow through the chiller
(production) and to the load (distribution) is
majority of loading conditions no chilled water is reduced. Reducing the speed of the centrifugal
returned back to the chiller, without being used by primary pumps, with pump VFDs, reduces the
the load. water flow. Less energy is required to operate a
pump at a lower speed.
The ability to vary the water flow through the chiller
has many benefits. It allows production pump
energy savings and compressor energy savings
during part load operation. The quick unloading
capabilities of variable capacity compressors makes Example
varying water flow through the chiller possible, A building includes a single 200 ton chiller
because a consistent leaving water temperature can with variable flow primary pumping and
be maintained over a variety of loading conditions. twenty 4,000 cfm chilled water air handling
This reduces the likelihood of nuisance trips of units. At design conditions, each air handling
the chiller safeties, which prevent the chiller from unit requires 24 gpm of 44°F chilled water
freezing, and it also optimizes performance of the and the chiller provides 480 gpm of 44°F
chiller system. chilled water with a 1760 rpm water pump at
11.5 bhp.
A supply water bypass with modulating valve and
return water flow sensor is required with variable Now, assume a part load condition when
flow primary pumping systems. During low load only 5 of the 20 air handling units require
conditions this system ensures a minimum water cooling. The chilled water required is only
flow through the chiller. The modulating valve and approximately 30% of the design water flow,
return water flow sensor only allow the bypass to or 150 gpm at 44°F.
be used at low load conditions to maximize energy
efficiency at other loading conditions. Using the performance curve of the primary
pump shown below, as the speed of the pump
An additional benefit of the ability to vary the is reduced to 948 rpm with a VFD, the flow
water flow through the chiller is to minimize is reduced to 150 gpm and the required brake
the efficiency losses during “low ΔT syndrome” horsepower is reduced from 11.5 bhp to
conditions. A low ΔT across the chiller (Entering 1.4 bhp.
Water Temperature - Leaving Water Temperature)
can be caused by improper coil and control
18
17
100
90 15
Flow 1
11.5 BHP 12
70
11
60
480 GPM
9
e
50
mixing. To combat a low ΔT a variable flow primary
v
8
ur
C
em
st 7
40 Sy
20
3
M
HP 948 RP
not possible with any other pumping system. 10 2
1
0 0
100 200 300 400 500 600 700 800 900
GPM
Constant Flow Pumping compared with Water flow to the load is modulated
Variable Flow Primary Pumping based on the differential pressure
Constant flow pumping systems utilize a variable capacity across the chilled water loop.
cooling system and a constant flow water pumping system.
Cooling capacity is modulated based on the desired leaving water During part load operation variable
temperature. Water constantly flows through the system. flow primary pumping systems save
additional pump energy, compared
with constant flow primary/variable
flow secondary systems, by reducing
Condenser / Cooling Tower
water flow in both the chilled water
Chiller production and distribution loops
Primary Pump
with VFD controlled primary pumps.
Pump energy is also saved because
Air Handling Units
there are no secondary pump water
Three-Way Valves
valves, fittings, strainers and other
secondary pumping water system
components to overcome. With less
Constant Flow Pumping System water flowing through the chiller,
variable flow primary pumping also
saves compressor energy with variable
Variable flow primary pumping saves pump energy by reducing capacity compressors. Variable flow
water flow through the system with VFD controlled pumps primary pumping can also minimize
during part load operation. With less water flowing through the efficiency losses during “low ΔT
chiller, variable flow primary pumping also saves compressor syndrome” conditions because of the
energy with variable capacity compressors. Installation costs are ability to vary water flow through the
similar; the additional required component is the pump VFD in chiller. Variable flow primary pumping
the variable flow system. Variable flow primary pumping can also systems always use less energy than
minimize efficiency losses during “low ΔT syndrome” conditions primary/secondary systems.
because of the ability to vary water flow through the chiller.
In addition to energy savings, variable
flow primary pumping also has
Constant Flow Primary/Variable Flow other benefits when compared with
primary/secondary pumping. Because
Secondary Pumping compared with Variable secondary pumps and secondary
Flow Primary Pumping
Constant flow primary/variable flow
secondary pumping systems utilize
a variable capacity cooling system, Condenser / Cooling Tower