FC -1631

Actual Fault Noticed Rectifiers not starting


Rectification Details Rectifier modules has been replaced
immediately with new ones.
Date of clearance of fault 2015-06-26
"Value of stores tested" of the154393
faulty item/ equipment
Total value of stores tested" of 4477404.83
the above item/equipment
IC date(GPMS)  2014-07-25
Analysis of fault (Mandatory After analyzing the fault, it was observed that,
Due to heavy power fluctuation at input mains,
the intensity of surge, developed was beyond
the specified limit of class-B, SPD hence
rectifier modules gone faulty.
Warranty date 2015-07-24

Any suggestion(s) to avoid Manufacturer has provided check list for


recurrence (preventive maintenance of site condition parameters like
measures class B, SPD connections, input voltage and
proper earthing arrangement.
Remarks By Feedback Admin The case has been attended by manufacturer
and satisfactory report is issued by
complainant. Since manufacturer has
provided check list for better maintenance of
site to avoid the recurrence of fault in future
therefore case may be closed.
DET Remarks Due to nonfunctioning of class- B, SPD,
rectifier modules were damage (Because of
mains voltage fluctuation) Rectifier modules
have been replaced immediately with new
ones. Manufacturer has provided a detailed
check list for maintenance of power plant to
avoid the recurrence of fault in future
therefore case is recommended for closer
please.